GE AF-300, C11 Alarm Reset, Keypad panel Normal display Alarm display Display, Alarm output Trip

Page 62

 

Keypad

 

Alarm Name

panel dis-

Contents of operation

 

play

 

Memory Error

Er1

If memory error occurs, such as a missing or invalid data, output is shut down, an

 

 

alarm is issued , and the drive is tripped.

CPU Error

Er3

If CPU error occurs because of noise, etc., output is shut down, an alarm is issued,

 

 

and the drive is tripped.

 

Er6

Detects drive operating procedure error during drive startup. FWD or REV

Operating Error

 

connected to terminal CM when Main power is applied to drive (F02 setting 3 or

 

 

 

 

4). Stop key on keypad is pressed in terminal operation (F02 setting 1 or 3).

RS485 Com-

Er8

If an error occurs in serial communication via the RS485, output is shut down, an

munication

 

alarm is issued , and the drive is tripped. For further details, refer to the instruc-

Error

 

 

tion manual for RS485 communication cards.

 

 

Input phase

Lin

If one of the input three phases is lost or the imbalance ratio between phases ex-

failure (only for

 

ceeds 2%, output is shut down, an alarm is issued, and the drive trips.

3-phase 200V

 

series)

 

 

6-2 Alarm Reset

To release the trip status, enter the reset command by pressing the reset key or from terminal (RST) after re- moving the cause of the trip. Since the reset command is an edge operation, be sure to input a command string

such as OFF ON OFF as shown in Figure 6-2-1.

When releasing the trip status, set the operation command to OFF. When the operation command is set to ON, check that operation starts after resetting.

If the cause of tripping is Er1, reset the error and initialize data. If the drive is not reset, contact GE Fuji.

10ms or more

OFF

Reset command

ON

OFF

Keypad panel

Normal display

 

 

 

 

 

 

 

Alarm display

 

Normal display

display

 

 

 

 

 

 

 

 

 

 

 

OFF

 

ON

 

 

 

OFF

Alarm output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Trip

 

 

Figure. 6-2-1 How to input the reset command

 

!WARNING

1.If alarm reset is activated with operation signal ON, the drive suddenly restarts which may be hazardous. Be sure to disable the operating signal when releas- ing the trip status,

otherwise fire could occur.

-60-

Image 62
Contents AF-300 C11 TM Table of Contents Safety Instructions Page Compliance with low voltage directive in EU There is a risk of fire Drive may be dropped causing injuryInstructions on use Otherwise fire could occurOtherwise electric shock or fire could occur Instructions on wiringOtherwise, fire could occur Otherwise electric shock could occurThere is a risk of accidents Instructions on operationOtherwise accident could occur Otherwise burns could occurGeneral instructions Instruction on maintenance/inspection, and replacementOtherwise electric shock or injury could occur Preface Factory Installed Options Input PhasesHorsepower GE Product Code AF-300 Drive Family Input Voltage230VAC, 3 phase, 50/60Hz Input 230VAC, Single phase, 50/60Hz InputBefore Using This Product Receiving InspectionsAppearance Handling the Product Storage and transportation Storage precautionsCarrying 1 Storage and transportation environmentAF-300C11 Installation and Connection10 cm 1 Operating environmentOtherwise electric shock and fire could occur 1Basic connectionConnection Connecting the main circuit and ground terminals 1 Functions of main circuit and ground terminalsCutting of barrier -3-2 Connection of DC reactor Connecting the control terminalsConnection diagram 4 Surge absorber connection diagram 7 Control terminal block arrangement 2 Functions of control circuit terminals FWDDX+ Connection examples 200 to 50/60Hz Mccb Fuse Connection to PLC when analog signal is input from PLC Leakage current Harmonic componentNoise OthersOperation Method OperationInspection and Preparation before Operation 1 General operation method1 Running command Trial RunKeypad Panel Names and FunctionsOperating Keypad Panel Is pressed at the same time asProcedure Display Press Function Selection List 1 Table of Function Selection List Selecting FunctionFundamental functions 30Ry operation mode Excited when tripped Normally excited Carrier freq 75kHz is set when 0 is specified Sound toneVoltage adjust To 10.0minX3 terminal function Tions Extension Terminal FunctionsControl Functions of Frequency Jump frequencyMotor Parameters High Performance FunctionsOptional Functions Serial communication optionDetails of Each Function F00 Data protectionF01 Otherwise injuries could occurKey is pressed and decelerates-to-stop when F02 Operation methodMotor runs when GE Start Software Selection During Terminal Operation F03 Maximum output frequency This function sets the maximum output frequencyF06 F04 Base frequencyF05 F07Electronic thermal O/L relayLevel F09 Torque boostF10 F11 Electronic thermal O/L relay Select F12 Electronic thermal O/L relay thermal time constant Operating time? ì? ? ŒcharacteristicsÀ Á Set with F12F15 Frequency limiter High F14 Restart mode after momentary power failurePhase input Single Phase Input F16 Frequency limiter LowBias positive F17 Gain For frequency setting signalF18 Bias frequency Bias negative 20mAdcF22 DC injection brakeBraking time F20 DC injection brake Starting frequencyF21 F24 F23 Starting frequencyF25 Stop frequency F26 Motor sound carrier freqF31 FM terminal Function F30 FM terminal voltage adjustF27 Motor sound sound tone F36 30Ry operation mode Normal Tripped OperationX2 terminal function E01 E02 E03X1 terminal function X3 terminal functionFrom previous C01 C02 C03 Jump frequency 1, 2 C07 Multistep frequency settingP00 Motor characteristics C04 Jump frequency HysteresisH01 Operation time H02 Trip historyData initialization H04 Auto ResetH20 PID control Mode select H03H23 PID control I-gain H21 PID control Feedback signalH22 PID control P-gain H25 PID control Feedback filterOptional RS485 serial communication unit O00 Option selectionRS485 RTU communication 1 List of Protective Functions Protective FunctionList of protective functions Alarm output Trip Alarm ResetKeypad panel Normal display Alarm display Display Otherwise fire could occurLoad excessive? TroubleshootingCase of tripping Consider using DC Power supply voltage within specified value?Does OU activate when load is removed OvervoltageOUHeat sink overheat- ing OH1 Is electronic thermal O/L relay setting correct? Drive overload OLU or motor overload OLProbable faulty drive. Contact GE Fuji Set o00 to Noise source nearby?Input phase failure Lin and imbalance Connect the input wires correctlyMotor does not start When motor rotates but the speed does not change Setting too low?To 0? When motor stalls during accelerationMotor generates ab Function change is disabled Normal heat Set F00 toPeriodic Inspection Maintenance and InspectionDaily Inspection There is danger of electric shockElectrolyte leakage Visual Not abnormal 1 Periodic inspection listDiscoloration and distortion Visual Not abnormal More Overheating? Is off 2Tighten more 3Visual inspection Electrical measurements in the Main Circuit Three-phaseSingle -phase 1 Meter for measuring the main circuit+ + Case of 3-phase input seriesInput series Motor SupplyInquiries about Products and Product Warranty 6Warranty Service Warranty CoverageIN-WARRANTY Failure Checklist Specifications Standard SpecificationsDrive output capacity kVA at Common specifications RUN StopPage Page Page Dimensions 00.2 2 68 17.2 D 00.2 Terminal Terminal 1 M2.5 00.2 2 External Options 1 External Options OptionsBuilt-in Options Applicable DC reactors Connection methodGeneral PrecautionsCompliance with standards L1/L L2/N L1/R L2/S L3/T P1 + N- U THR CMGeneral RFI Filters Electromagnetic Compatibility EMCGeneral 1 RFI filters Dimensions Ferrite Ring DimensionsPage 1 Recommended Installation 2 Recommended installation detail inside the enclosure GE Fuji Drives USA, Inc Roanoke Blvd. Suite