(3) DC reactor connecting terminal [P1, P(+)]
Use this terminal to connect a input
If no DC reactor is used, do not remove the jumper.
P1 P(+)
(4) Drive grounding terminal[G]
Always ground the drive grounding terminal [G] for safety and noise reduction. Grounding of the metal frames of electric equipment has to be done in accordance with the national and local safety specifications in force.
(a) Connection diagram
Top of drive
Barrier
(b) Cutting of barrier Figure 2-3-2 Connection of DC reactor
1Connect a thick and short wire to the grounding terminal of the drive for connection with a ground electrode pre- pared exclusively for the drive system.
!CAUTION
1.Check that the number of phases and the rated voltage of this product correspond to the number of phases and voltage of the AC power supply, otherwise fire could occur.
2.Do not connect the AC power supply to the output terminals (U, V, W), otherwise injury could occur.
3.Do not connect a braking resistor directly to the DC terminals P(+),
otherwise fire could occur.
2-3-3 Connecting the control terminals
Table
The method of connecting a control circuit terminal de- pends
on how its function is set. Connect the control circuit terminals according to the set functions.
(1) Digital input terminal
Figure 2-3-3 shows the circuit configuration. Use a reliable contact.
+24 to +27Vdc |
|
| FWD or others |
4.7kΩ |
|
CM | |
Figure |