Safety Instructions
Read this operation manual carefully and familiarize yourself with the operation of the drive be-
fore installation, connection (wiring), operation or maintenance and inspection of the device. Be
familiar with the drive, safety information, and safety signs before using the drive. In this instruction manual, safety signs are classified into the following categories.
!WARNING
Improper operation may result in death of serious injury.
!CAUTION
Improper operation may result in slight to medium injury or property damage.
Note: More serious situations than those covered by the CAUTION sign can result depending on the circumstances. It is important that you always follow the instructions
Compliance with UL/cUL standards [Applicable to products with UL/cUL mark]
!CAUTION
1.[WARNING] Take care of electric shock. Be sure to turn the drive off before starting work.
2.[CAUTION] When the charge lamp is lit, the drive is still charged at a dangerous voltage.
3.[WARNING] There are two or more live parts inside the drive.
4.The drive is approved as a part used inside a panel. Install it inside a panel.
5.Perform wiring to the input, output and control terminals of the drive, referring to the table below. Use UL certified round crimp terminal to the input and output terminals with insulation cover or covered with reduced tube to obtain the insulation distance. Use a crimping tool recommended by the terminal manufacturer when fabricating crimp terminals.
6.Install a fuse in the power supply to the drive, referring to the table below.
|
| Tightening torque | Applicable wire diameter |
| Recommended fuse | |||
|
| Lb • Inch[N • m] | [AWG] (mm2)2) | Fuse | ||||
Voltage | Drive type |
|
| |||||
|
|
|
| [A] 3) |
|
| ||
L1/R, L2/S, L3/T | Control | L1/R, L2/S, L3/T 1) | Control | Gould | Bussmann | |||
|
| 1) U. V. W | section | U. V. W | section |
| Company | Company |
input | 6KC1123F12X1** |
|
|
|
| 3 | A4J3 | JKS3 |
6KC1123F25X1** |
|
|
|
| 6 | A4J6 | JKS6 | |
|
|
|
|
|
|
|
| |
6KC1123F50X1** |
|
| 14 (2.1) |
| 10 | A4J10 | JKS10 | |
230V | 10.6 (1.2) |
|
| |||||
|
|
|
|
|
|
| ||
6KC1123001X1** |
|
|
| 15 | A4J15 | JKS15 | ||
|
|
|
| |||||
phase |
|
|
|
|
|
|
|
|
6KC1123002X1** |
|
|
|
| 20 | A4J20 | JKS20 | |
|
|
|
|
|
|
|
| |
6KC1123003X1** |
|
| 12 (3.3) |
| 30 | A4J30 | JKS30 | |
3- |
| 3.5 | 20 | |||||
|
|
|
|
|
| |||
| 6KC1123005X1** | 15.9 (1.8) | 10 (5.3) | 40 | A4J40 | JKS40 | ||
| (0.4) | (0.5) | ||||||
|
|
|
|
|
|
| ||
230V | 6KC1121F12X1** |
|
| 6 | A4J6 | JKS6 | ||
|
|
|
| |||||
6KC1121F25X1** |
|
| 14 (2.1) |
| 6 | A4J6 | JKS6 | |
|
|
|
|
|
|
| ||
phase input | 6KC1121F50X1** | 10.6 (1.2) |
|
| 10 | A4J10 | JKS10 | |
|
|
| ||||||
|
|
|
|
|
|
|
| |
6KC1121001X1** |
|
|
|
| 15 | A4J15 | JKS15 | |
Single- |
|
|
|
|
|
|
|
|
6KC1121002X1** |
|
| 12 (3.3) |
| 30 | A4J30 | JKS30 | |
|
|
|
|
|
|
|
| |
6KC1121003X1** | 15.9 (1.8) |
| 10 (5.3) |
| 40 | A4J40 | JKS40 | |
|
|
| ||||||
|
|
|
|
|
|
|
|
|
1)Only the L1/L and L2/N phases are provided for the
2)Use copper wires of allowable maximum temperature 60 or 75 °C.
3)Use UL certified "fast acting fuse."
Connect the power supply satisfying the characteristics shown in the table below as an input power supply of the drive. (Short circuit rating)
Drive type | Input max. volta | Input current | |
|
|
| |
3 Phase input | AC230V | 5,000 A or less | |
Single phase input | AC240V | ||
|