Change during operation: N = impossible, Y* = possible (enabled by using
FUNC DATA
), Y= possible (enabled by using )
F02 Operation method
The following four values can be selected: 0 Keypad operation [ RUN STOP key]
Factory | Change during |
setting | operation |
0 | N |
The motor runs when the
RUN
key is pressed and decelerates-to-stop when the
STOP
key is
pressed. The rotation direction depends on the FWD and REV terminals as follows: FWD - CM
REV - CM
Operation is impossible when both the FWD and REV terminals or none of them are
1
External signal (Digital input) (FWD, REV)
Forward operation with
STOP key active (See following page chart for detail)
2 External signal (Digital input) (FWD, REV)
Forward operation with
STOP key inactive (See following page chart for detail)
3 External signal (Digital input) (FWD, REV)
Forward operation with
STOP
key active with GE start software (See following page chart for detail)
4
External signal (Digital input) (FWD, REV)
Forward operation with
STOP key inactive with GE start software (See following page chart for detail)
Note: This function can be changed only while the FWD and REV terminals are open.