GE C11, AF-300 manual H01 Operation time, H02 Trip history

Page 57

Change during operation: N = impossible, Y* = possible (enabled by using

FUNC DATA

), Y= possible (enabled by using )

H01 Operation time

Factory

Change during

setting

operation

0Monitoring only.

This function displays the integration time of power supply applied to the drive.

0 to 655 are displayed to indicate 0 to 65500 hours.

If the integration time exceeds 65500 hours, 65500 is displayed continuously. While the total of power

supply times is less than one hour, the times are not integrated.

H02 Trip history

Factory

Change during

setting

operation

---Monitoring only.

This function memorizes the history of the last four protection operations.

Each data item can be called using the key.

The calling procedure is shown below:

No.

 

 

 

 

 

 

 

 

 

 

Procedure

 

 

Display ex-

Remarks

 

 

 

 

 

 

 

 

 

 

 

 

 

ample

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

Call

H

0

 

 

2

 

 

H

0

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

Press the

 

 

 

Press the

 

 

O

U

 

2

 

The contents (history) of the latest

 

 

 

 

 

FUNC

 

 

key

 

 

 

 

 

 

key

 

 

 

 

 

 

 

alarm are displayed.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

Press the

 

 

 

Press the

 

 

O

H

 

2

 

The contents of the second latest alarm

 

 

 

 

 

 

 

 

 

 

 

are displayed.

 

 

 

 

 

 

 

 

 

key

 

 

 

 

 

 

 

 

 

 

 

 

 

key

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

Press the

 

 

 

Press the

 

 

O

C

 

1

 

The contents of the third latest alarm

 

 

 

 

 

 

 

 

 

key

 

 

 

 

 

 

 

are displayed.

 

 

 

 

 

 

key

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

Press the

 

 

 

Press the

 

 

-

-

 

-

 

The contents of the fourth latest alarm

 

 

 

 

 

 

 

 

 

 

 

 

are displayed. (This example is for no

 

 

 

 

 

 

 

 

 

 

key

 

 

 

 

 

 

 

 

 

 

 

 

 

key

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

history.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

Press the

 

 

 

 

 

 

 

 

 

 

 

 

 

E

n

 

d

 

 

 

 

 

 

 

 

key

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The contents of a new alarm is stored in the data area for the history of the latest alarm. At this time, the history of the latest alarm is stored in the data area for the second latest alarm. The histories of the second and third latest alarms are moved in this way and the history of the fourth latest alarm is deleted.

Stored trip histories are not deleted although data initialization is executed with H03.

-55-

Image 57
Contents AF-300 C11 TM Table of Contents Safety Instructions Page Compliance with low voltage directive in EU Instructions on use Drive may be dropped causing injuryThere is a risk of fire Otherwise fire could occurOtherwise, fire could occur Instructions on wiringOtherwise electric shock or fire could occur Otherwise electric shock could occurOtherwise accident could occur Instructions on operationThere is a risk of accidents Otherwise burns could occurInstruction on maintenance/inspection, and replacement Otherwise electric shock or injury could occurGeneral instructions Preface Horsepower Input PhasesFactory Installed Options GE Product Code AF-300 Drive Family Input Voltage230VAC, Single phase, 50/60Hz Input 230VAC, 3 phase, 50/60Hz InputReceiving Inspections Before Using This ProductAppearance Handling the Product Carrying Storage precautionsStorage and transportation 1 Storage and transportation environment10 cm Installation and ConnectionAF-300C11 1 Operating environment1Basic connection ConnectionOtherwise electric shock and fire could occur 1 Functions of main circuit and ground terminals Connecting the main circuit and ground terminalsConnecting the control terminals Connection diagramCutting of barrier -3-2 Connection of DC reactor 4 Surge absorber connection diagram 7 Control terminal block arrangement FWD 2 Functions of control circuit terminalsDX+ Connection examples 200 to 50/60Hz Mccb Fuse Connection to PLC when analog signal is input from PLC Noise Harmonic componentLeakage current OthersInspection and Preparation before Operation OperationOperation Method 1 General operation methodTrial Run 1 Running commandNames and Functions Keypad PanelIs pressed at the same time as Operating Keypad PanelProcedure Display Press Selecting Function Fundamental functionsFunction Selection List 1 Table of Function Selection List Voltage adjust Carrier freq 75kHz is set when 0 is specified Sound tone30Ry operation mode Excited when tripped Normally excited To 10.0minControl Functions of Frequency Extension Terminal FunctionsX3 terminal function Tions Jump frequencyHigh Performance Functions Motor ParametersSerial communication option Optional FunctionsF01 F00 Data protectionDetails of Each Function Otherwise injuries could occurF02 Operation method Motor runs whenKey is pressed and decelerates-to-stop when GE Start Software Selection During Terminal Operation This function sets the maximum output frequency F03 Maximum output frequencyF05 F04 Base frequencyF06 F07F09 Torque boost F10 F11 Electronic thermal O/L relay SelectElectronic thermal O/L relayLevel F12 Electronic thermal O/L relay thermal time constant Set with F12 Operating time? ì? ? ŒcharacteristicsÀ ÁPhase input Single Phase Input F14 Restart mode after momentary power failureF15 Frequency limiter High F16 Frequency limiter LowF18 Bias frequency F17 Gain For frequency setting signalBias positive Bias negative 20mAdcF20 DC injection brake Starting frequency F21F22 DC injection brakeBraking time F25 Stop frequency F23 Starting frequencyF24 F26 Motor sound carrier freqF30 FM terminal voltage adjust F27 Motor sound sound toneF31 FM terminal Function Normal Tripped Operation F36 30Ry operation modeX1 terminal function E01 E02 E03X2 terminal function X3 terminal functionFrom previous P00 Motor characteristics C07 Multistep frequency settingC01 C02 C03 Jump frequency 1, 2 C04 Jump frequency HysteresisH02 Trip history H01 Operation timeH20 PID control Mode select H04 Auto ResetData initialization H03H22 PID control P-gain H21 PID control Feedback signalH23 PID control I-gain H25 PID control Feedback filterO00 Option selection RS485 RTU communicationOptional RS485 serial communication unit Protective Function List of protective functions1 List of Protective Functions Keypad panel Normal display Alarm display Display Alarm ResetAlarm output Trip Otherwise fire could occurTroubleshooting Case of trippingLoad excessive? Does OU activate when load is removed Power supply voltage within specified value?Consider using DC OvervoltageOUHeat sink overheat- ing OH1 Drive overload OLU or motor overload OL Is electronic thermal O/L relay setting correct?Noise source nearby? Probable faulty drive. Contact GE Fuji Set o00 toConnect the input wires correctly Input phase failure Lin and imbalanceMotor does not start Setting too low? When motor rotates but the speed does not changeMotor generates ab Function change is disabled Normal heat When motor stalls during accelerationTo 0? Set F00 toDaily Inspection Maintenance and InspectionPeriodic Inspection There is danger of electric shock1 Periodic inspection list Discoloration and distortion Visual Not abnormalElectrolyte leakage Visual Not abnormal More Overheating? Is off 2Tighten more 3Visual inspection Single -phase Three-phaseElectrical measurements in the Main Circuit 1 Meter for measuring the main circuitInput series Case of 3-phase input series+ + Motor SupplyInquiries about Products and Product Warranty Warranty Coverage 6Warranty ServiceIN-WARRANTY Failure Checklist Standard Specifications SpecificationsDrive output capacity kVA at RUN Stop Common specificationsPage Page Page Dimensions 00.2 2 68 17.2 D 00.2 Terminal Terminal 1 M2.5 00.2 2 Options Built-in OptionsExternal Options 1 External Options Connection method Applicable DC reactorsCompliance with standards PrecautionsGeneral L1/L L2/N L1/R L2/S L3/T P1 + N- U THR CMGeneral Electromagnetic Compatibility EMC GeneralRFI Filters Ferrite Ring Dimensions 1 RFI filters DimensionsPage 1 Recommended Installation 2 Recommended installation detail inside the enclosure GE Fuji Drives USA, Inc Roanoke Blvd. Suite