Compliance with low voltage directive in EU [Continued]
!CAUTION
Use of wires specified in Appendix C of EN 60204 is recommended.
|
|
| Molded case circuit | Recommended wire size AWG (mm2) | ||||||
|
|
| Input circuit*2 |
|
|
| ||||
Power |
|
| breaker (MCCB) or |
|
|
| ||||
Nominal |
| earth leakage cir- |
| *2 |
| |||||
supply | applied |
| cuit breaker (ELCB) | [L1/R, L2/S, L3/T], | Output | Control | ||||
volt- | Drive type | DCR | ||||||||
motor | Rated current [A] | single phase 200V | circuit*2 | circuit | wiring | |||||
age |
| |||||||||
| [HP] |
|
|
| [L1/L, L2/N] | [U. V. W] | [P1] |
| ||
|
|
|
|
|
|
|
| [P(+)] |
| |
|
|
| With | Without | With | Without |
|
| ||
|
|
|
|
|
| |||||
|
|
| DCR | reactor*3 | DCR | reactor*3 |
|
|
| |
| 1/8 | 6KC1123F12X1** |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| |
| 1/4 | 6KC1123F25X1** | 5 | 5 |
|
|
|
|
| |
230V |
|
|
|
|
|
|
|
| ||
1/2 | 6KC1123F50X1** |
| 14 | 14 | 14 | 14 |
| |||
|
|
| ||||||||
|
|
|
| |||||||
|
|
|
| (2.5)*4 | (2.5)*4 | (2.5)*4 | (2.5)*4 |
| ||
1 | 6KC1123001X1** |
| 10 |
| ||||||
|
|
|
|
|
|
|
|
| ||
2 | 6KC1123002X1** |
| 15 |
|
|
|
|
| ||
| 10 |
|
|
|
|
| ||||
|
|
|
|
|
|
|
| |||
3 | 6KC1123003X1** |
| 20 |
|
|
|
|
| ||
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| |
| 5 | 6KC1123005X1** | 20 | 30 | 12 | 10 | 12 | 12 | 20 | |
|
| (4.0)*5 | (6.0)*5 | (4.0)*5 | (4.0)*5 | |||||
|
|
|
|
| (0.5) | |||||
| 1/8 | 6KC1121F12X1** |
|
|
|
|
|
|
| |
|
|
| 5 |
|
|
|
|
| ||
230V |
|
|
|
|
|
|
|
| ||
1/4 | 6KC1121F25X1** | 5 |
| 14 |
|
|
| |||
|
|
|
|
| ||||||
|
| 14 | 14 | 14 |
| |||||
|
|
|
| (2.5)*4 |
| |||||
1/2 | 6KC1121F50X1** |
| 10 |
| ||||||
phase |
|
| ||||||||
|
|
|
| (2.5)*4 |
| (2.5)*4 | (2.5)*4 |
| ||
1 | 6KC1121001X1** | 10 | 15 |
|
|
|
|
| ||
|
|
|
|
|
| |||||
Single |
|
|
|
|
|
|
|
|
| |
2 | 6KC1121002X1** | 15 | 20 |
| (4.0)*4 |
|
|
| ||
3 | 6KC1121003X1** | 20 | 30 | 12 | 10 | 14 | 12 |
| ||
|
| (4.0)*5 | (6.0)*5 | (2.5)*5 | (4.0)*5 |
| ||||
|
|
|
|
|
|
*1 The applicable frame and series of the molded case circuit breaker (MCCB) and earth leakage circuit breaker (ELCB) vary according to the capacity of the transformer of the equipment. For details of selection, refer to the concerning technical documents.
*2 The recommended wire size for the main circuit is the case for the low voltage directive at ambient temperature 40 °C.
*3 The power supply impedance without a reactor is considered to be the equivalent of 0.1% of the drive capacity, with 10% current imbalance accompanied by the voltage imbalance.
*4 Crimp terminals up to 0.29” (7.4 mm) in width (including tolerance) can be used.
*5 Crimp terminals up to 0.37” (9.5 mm) in width (including tolerance) can be used.
*6 Use the grounding cable of a size equal to or larger than that of the input power supply cable.