(2) Run/stop command terminal (FWD, REV)
FWD terminal is
(3) Analog input terminal (13, 12, 11, C1)
Use these terminals to connect external input analog voltage and analog current and frequency setting device (POT). For connecting a contact to this circuit, use a twin contact for fine current sig- nal. Do not use a contact for terminal 11.
!WARNING
1.The STOP key is valid only when the function has been set. Prepare an- other switch for emergency stop. When the data of F02 is selecte “2” or “4”, the operation cannot be stopped using the STOP key on the keypad panel, otherwise accidents could occur.
*Note the following when wiring:
(1) Surge absorber connection
When the exciting coil of the magnetic contactor or relay in the control circuit or drive peripheral circuit is opened or closed, a surge voltage (noise) is generated with a sudden current change. Due to this surge voltage, the drive control circuit or peripheral equipment may malfunction. If so, directly connect a surge absorber to both ends of the coil. (See Fig- ure
(2)Control circuit wiring
1 Wires connected to control circuit terminals must be AWG 20 (0.5mm2) shielded wire or twisted vinyl wire. Remove the sheath as shown in Figure
2Keep the wiring of the main circuit, external relay se- quence circuit and control circuit as far away from each
AC relay | DC relay |
| |||||||||||||
|
|
|
|
|
|
| SK |
|
|
|
|
|
|
|
|
MC |
|
|
|
|
| + |
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
| Ry |
|
|
| D | ||||||
|
|
| |||||||||||||
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
| - |
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| ||||
SK: Surge absorber | D: Diode |
|
Figure 2-3-4 Surge absorber connection diagram
0.24” ± 0.04” (6±1mm)
other as possible. If they must be adjacent, cross them at right angles.
3Use a
(3)Shielding sheath connection
Connect one end of the shielding sheath of a shielded or
Figure 2-3-5 End treatment
Contact | Shielded wire | |
| FWD | |
| CM | |
| To ground terminal | |
Frequency | Shielded wire | |
setting POT | ||
| ||
| 13 | |
| 12 | |
| 11 | |
| To ground terminal |