Change during operation: N = impossible, Y* = possible (enabled by using
FUNC DATA
), Y= possible (enabled by using )
F09 Torque boost
Factory | Change during |
setting | operation |
13 | Y |
This function can choose between 32 types of boost according to the load type and motor characteris- | ||||||||||||
tics. |
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
| ||||||
|
|
|
|
| 0 |
| For square law torque loads |
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |||
| to |
| Output | Higher | ||||||||
|
| |||||||||||
|
|
|
|
| 1 |
|
| (fan, pump) | ||||
|
|
|
|
|
|
| voltage |
|
| |||
|
|
|
|
|
|
| Lower |
|
| |||
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
| 2 |
|
|
| ||||
|
|
|
|
|
| Lower | ||||||
| to |
|
|
|
|
|
|
| ||||
|
|
|
|
|
| Square law torque | ||||||
|
|
| 3 |
| 1 |
| Higher |
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Output frequency
F10
F11
| Electronic thermal O/L relay (Select) |
|
|
|
|
| Factory | Change during |
| ||||||||||||||||||||||
|
|
|
|
|
| setting | operation |
| |||||||||||||||||||||||
|
|
|
| ||||||||||||||||||||||||||||
|
|
|
| ||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1 |
|
| Y* |
| |
|
|
|
| ||||||||||||||||||||||||||||
|
|
|
|
|
| ||||||||||||||||||||||||||
This function is used to select between the following three values: |
|
|
| ||||||||||||||||||||||||||||
|
|
|
|
|
|
| 0 | Inactive |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| · | · | · | · | · | · | · | · | · | · | · |
|
|
| ||||||||
|
|
|
|
|
|
| 1 | Active· |
|
|
| ||||||||||||||||||||
|
|
|
|
|
|
|
|
|
| · | · | · | · | · | · | · | · | · | · | · |
|
|
| ||||||||
|
|
|
|
|
|
| 2 | Active· |
|
|
| ||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Factory setting | Change during | |||
| Electronic thermal O/L relay(Level) |
|
|
|
|
|
|
|
|
| operation | ||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||||||||
|
|
|
|
|
|
| Motor rated | Y* | |||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 0. |
| 1 | 4 |
|
| This function sets the operation level of an electronic thermal O/L relay by using an | ||||||||||||||||||||||||
|
| to |
|
|
|
|
|
|
| ||||||||||||||||||||||
|
|
|
|
|
|
|
|
| ampere value according to the motor rated current. |
|
|
| |||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||||||||
| 2 | 2. | 3 |
|
| 20 to 135% of the drive rated current can be set. |
|
|
| ||||||||||||||||||||||
|
|
|
|
|
|
| |||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
| Values less than 9.99A can be set in 0.01A step and values more than 10.0A can be set | ||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
| in 0.1A step. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Set the value obtained by multiplying the motor rated current by coefficient K in the table below ac- cording to the wiring length between the drive and motor.
Drive HP |
|
| Wiring length | ||
| 0’ | 132’ 165’ | Max. 330’ | ||
1/8 | K=1.2 |
| External | thermal is | |
|
|
| recommended. | ||
1/4 | K=1 |
|
| K=1.1 | |
1/ 2 to 5 |
|
|
| K=1 |
|