Change during operation: N = impossible, Y* = possible (enabled by using
FUNC DATA
), Y= possible (enabled by using )
O: Optional Functions
Function |
|
|
|
|
|
|
| Min. | Factory | Change | User |
Name |
|
|
|
| Setting range | Unit | during | ||||
code No. |
|
|
|
| unit | setting | setting | ||||
|
|
|
|
|
|
| operation | ||||
|
|
|
|
|
|
|
|
|
|
| |
o00 | RTU Option | 0 | : Inactive 1 : Active | - | - | 0 | Y* |
| |||
o01 | Address | 1 to 247 (Max – 31 Drives) |
|
| 1 | Y* |
| ||||
o02 | Mode select on no response | 0 | : |
| Er8 by 8 times communiction/checksum |
|
| 0 | Y* |
| |
| error |
|
|
| errors |
|
|
|
|
|
|
|
| 1 | : |
| Er8 by 8 times communiction/checksum |
|
|
|
|
| |
|
|
|
|
| errors |
|
|
|
|
|
|
|
| 2 | : |
| Er8 with no communication more than |
|
|
|
|
| |
|
|
|
|
| timer (o03) |
|
|
|
|
| |
|
| 3 | : |
| Retry and keep running |
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| ||
o03 | Timer | 1 | to 60 s |
| s | 1 | 2 | Y* |
| ||
o04 | Baud rate | 1 | : 9600 | 2 : 4800 | - |
| 1 | Y* |
| ||
|
| 3: 2400 |
|
|
|
|
|
|
| ||
o05 | Data length | 0 | : 8 bits | (Fixed) |
| - |
| 0 | Y* |
| |
o06 | Parity check | 0 | : No checking |
| - |
| 0 | Y* |
| ||
|
| 1 : Even parity, | 2 : Odd parity |
|
|
|
|
| |||
o07 | Stop bits | 0 : 2bits | 1 : 1bit | - |
| 0 | Y* |
| |||
|
|
|
|
| (Automatically changed by o06 setting) |
|
|
|
|
| |
o08 | No response error detection | 0 | : (No detection) |
| s | 1 | 0 | Y* |
| ||
| time | 1 | to | 60 s |
|
|
|
|
|
| |
o09 | Response interval | 0.00 | to | 1.00 s |
| s | 0.1 | 0.01 | Y* |
| |
o10 | RTU Frequency Command | 0 | : F01 setting is active | - |
| 0 | N |
| |||
|
| 1 | : RTU setting is active |
|
|
|
|
| |||
o11 | RTU Operation Command | 0 | : F02 setting is active | - |
| 0 | N |
| |||
|
| 1 | : RTU setting is active |
|
|
|
|
|
Note: For details on “o01” to “o11”, refer to the instruction manual that came with the optional RS485 RTU