Table 10 — Run Status Mode and Sub-Mode Directory

Table 10 — Run Status Mode and Sub-Mode Directory

SUB-MODE

KEYPAD

ITEM

DISPLAY

SUB-ITEM

DISPLAY

SUB-ITEM

DISPLAY

ITEM

 

COMMENT

 

ENTRY

 

 

 

 

 

 

EXPANSION

 

 

VIEW

 

 

 

EWT

XXX.X °F

 

 

 

 

ENTERING FLUID TEMP

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LWT

XXX.X °F

 

 

 

 

LEAVING FLUID TEMP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SETP

XXX.X °F

 

 

 

 

ACTIVE SETPOINT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CTPT

XXX.X °F

 

 

 

 

CONTROL POINT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOD.F

XXX

 

 

 

 

LOAD/UNLOAD FACTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STAT

X

 

 

 

 

CONTROL MODE

0

= Service Test

 

 

 

 

 

 

 

 

 

 

 

1

= Off Local

 

 

 

 

 

 

 

 

 

 

 

2

= Off SCN

 

 

 

 

 

 

 

 

 

 

 

3

= Off Time

 

 

 

 

 

 

 

 

 

 

 

4

= Off Emrgcy

 

 

 

 

 

 

 

 

 

 

 

5

= On Local

 

 

 

 

 

 

 

 

 

 

 

6

= On SCN

 

 

 

 

 

 

 

 

 

 

 

7

= On Time

 

 

 

 

 

 

 

 

 

 

 

8

= Ht Enabled

 

 

 

 

 

 

 

 

 

 

 

9

= Pump Delay

 

 

 

 

LD.PM

 

 

 

 

 

LEAD PUMP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OCC

YES/NO

 

 

 

 

OCCUPIED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LS.AC

YES/NO

 

 

 

 

LOW SOUND ACTIVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODE

YES/NO

 

 

 

 

OVERRIDE MODES IN EFFECT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAP

XXX %

 

 

 

 

PERCENT TOTAL CAPACITY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STGE

X

 

 

 

 

REQUESTED STAGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALRM

XXX

 

 

 

 

CURRENT ALARMS & ALERTS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TIME

XX.XX

 

 

 

 

TIME OF DAY

 

00.00-23.59

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MNTH

XX

 

 

 

 

MONTH OF YEAR

1 = January, 2 = February, etc.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DATE

XX

 

 

 

 

DAY OF MONTH

 

01-31

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YEAR

XX

 

 

 

 

YEAR OF THE CENTURY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RUN

 

 

HRS.U

XXXX HRS

 

 

 

 

MACHINE OPERATING HOURS

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STR.U

XXXX

 

 

 

 

MACHINE STARTS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HR.P1

XXXX.X

 

 

 

 

PUMP 1 RUN HOURS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HR.P2

XXXX.X

 

 

 

 

PUMP 2 RUN HOURS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HOUR

 

 

HRS.A

XXXX HRS

 

 

 

 

CIRCUIT A RUN HOURS

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HRS.B

XXXX HRS

 

 

 

 

CIRCUIT B RUN HOURS

 

See Note

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HR.A1

XXXX HRS

 

 

 

 

COMPRESSOR A1 RUN HOURS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HR.A2

XXXX HRS

 

 

 

 

COMPRESSOR A2 RUN HOURS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HR.B1

XXXX HRS

 

 

 

 

COMPRESSOR B1 RUN HOURS

 

See Note

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HR.B2

XXXX HRS

 

 

 

 

COMPRESSOR B2 RUN HOURS

 

See Note

 

 

 

 

 

 

 

 

 

 

 

 

 

STRT

 

 

ST.A1

XXXX

 

 

 

 

COMPRESSOR A1 STARTS

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ST.A2

XXXX

 

 

 

 

COMPRESSOR A2 STARTS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ST.B1

XXXX

 

 

 

 

COMPRESSOR B1 STARTS

 

See Note

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ST.B2

XXXX

 

 

 

 

COMPRESSOR B2 STARTS

 

See Note

 

 

 

 

 

 

 

 

 

 

 

 

 

PM

 

 

PUMP

 

 

 

 

 

PUMP MAINTENANCE

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SI.PM

XXXX HRS

 

 

PUMP SERVICE INTERVAL

 

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P.1.DN

XXXX HRS

 

 

PUMP 1 SERVICE COUNTDOWN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P.2.DN

XXXX HRS

 

 

PUMP 2 SERVICE COUNTDOWN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P.1.MN

YES/NO

 

 

PUMP 1 MAINTENANCE DONE

 

User Entry

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P.2.MN

YES/NO

 

 

PUMP 2 MAINTENANCE DONE

 

User Entry

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.

27

Image 27
Contents SAFETY CONSIDERATIONS GENERAL CONTENTSTable 1 — Unit Sizes MAJOR SYSTEM COMPONENTSControl Module Communication Sterlco Comfort Network SCN Interface —Table 4 - Output Relays Table 3 — Status SwitchesTable 5 - SCN Communication Bus Wiring Table 2 — Thermistor DesignationsLEGEND FOR FIG. Page Page 30RA010-018AQUA SNAP Fig. 3 — Wiring Schematic 30RA010-018AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATIC Fig. 3 - Wiring Schematic 30RA010-018contSEE NOTE SEE NOTE 30RA022-030AQUA SNAP Fig. 4 - Wiring Schematic 30RA022-030AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATIC Fig. 4 - Wiring Schematic 30RA022-030cont30RA032-040AQUA SNAP Fig. 5 — Wiring Schematic 30RA032-040AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATIC Fig. 5 — Wiring Schematic 30RA032-040cont30RA042-055AQUA SNAP Fig. 6 — Wiring Schematic 30RA042-055AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATIC Fig. 6 — Wiring Schematic 30RA042-055contMODE Fig. 7 — Main Base BoardESCAPEENTER REMOTE CONTACT SW1 OFF ENABLE OFF SW2 ONFig. 9 — Typical Space Temperature Sensor Wiring CEPL130351 Fig. 11 - Energy Management Module100/100 Fig. 12 — Deadband Multiplier Fig. 13 — Operating Envelope for R-22Maneurop CompressorFig. 14 — 30RA Condenser Fan Sequence Cooling Set Point Select Fig. 16 — Scrolling Marquee Display Service Test See Table 11 — Both main powerand control circuit power must be on Table 8 — Control Methods and Cooling Set PointsOptional Factory-InstalledHydronic Package — •Cooler Pump Control CPC Configuration, OPT1 ON Table 9 — Marquee Display Menu Structure Fig. 17 — Dual Chiller Thermistor LocationTable 10 — Run Status Mode and Sub-ModeDirectory SUB-MODE Table 12 - Temperature Mode and Sub-ModeDirectory Table 13 — Pressure Mode and Sub-ModeDirectory Table 14 — Set Point and Sub-ModeDirectoryTable 15 — Inputs Mode and Sub-ModeDirectory DISPLAY Table 16 — Outputs Mode and Sub-ModeDirectorySUB-MODE KEYPADDISPLAY SUB-MODEKEYPAD ITEMDISPLAY SUB-MODEKEYPAD ITEMTable 18 — Time Clock Mode and Sub-ModeDirectory PER.3 SUB-MODE Table 19 — Operating Mode and Sub-ModeDirectory Table 20 — Alarms Mode and Sub-ModeDirectoryDISPLAY SUB-MODEITEM KEYPAD ENTRYRSET DISP Table 23 — Operating Modes Table 25A — 4-20mA Reset Table 24 — Example of Reading and Clearing AlarmsTable 26B — Configuring Return Temperature Reset Fig. 20 — Space Temperature Reset Fig. 18 — Standard Chilled FluidTemperature Control — No Reset Fig. 19 — Outdoor-AirTemperature ResetFig. 21B — Cooling Set Point 4 to 20 mA Fig. 21A — 4- to 20-mADemand LimitingTable 27 — Configuring Demand Limit TROUBLESHOOTINGTable 28 — Troubleshooting Recommended that system be filled with an approand fluid tubing FU — Fuse GND — Ground Fig. 22 — Component Arrangement — 30RA010-030FU — Fuse GND — Ground Fig. 23 — Component Arrangement — 30RA032-040FU — Fuse GND — Ground Fig. 24 — Component Arrangement — 30RA042-055NOTES LEGEND Table 29 — Alarm and Alert Codes Table 29 - Alarm and Alert Codes cont ALARM Table 29 — Alarm and Alert Codes contALARM Table 29 — Alarm and Alert Codes contALARM Table 29 — Alarm and Alert Codes contElectronic Components SERVICECompressor Replacement Refer to Fig Table 30 - Unit Torque SpecificationFig. 30 — Compressor Location — 30RA032-055 Fig. 28 — Compressor WiringFig. 27 — Typical Compressor Mounting — All Sizes Fig. 29 — Compressor Location — 30RA010-030Table 31 - Oil Charge Condenser Section and CoilsFig. 33 — Condenser-FanPosition Standard Fan Fig. 31 — 30RA Access PanelsCheck Refrigerant Feed Components Fig. 32 — Condenser-FanMountingCheck Unit Safeties Table 32 — Factory Settings, High-PressureSwitch Fixed Compressor and Unit Protective DevicesCOOLER FREEZE-UPPROTECTION TEMP TEMP For Thermistor T10 For Thermistor T10 Main Base Board, J8 Connector Fig. 35 — Fluid-SideTemperature Sensors T1 and T2Fig. 36 — Thermistor Connections to PROGRAMMING Mode Table 37 - Fault Codes •P50: FAULT HISTORY — Last 8 faults•P51: SOFTWARE version PARAMETERS Table 39 — Replacement Modules System Check MAINTENANCEMinimum Loop Volume PRE-START-UPOperating Limitations OPERATION SEQUENCE Table 41 — Temperature Limits forStandard 30RA Units CIRCA_AN Circuit A Analog Parameters APPENDIX ASCN Tables A_UNIT General Unit Parameters CIRCADIO Circuit A Discrete Inputs/OutputsCIRCBDIO Circuit B Discrete Inputs/Outputs CIRCB_AN Circuit B Analog ParametersOPTIONS Unit Parameters BRODEFS Broadcast POC Definition Table ALARMDEF Alarm Definition TableDISPLAY Marquee Display SETUP DUALCHIL Dual Chiller Configuration SettingsOPTIONS2 Options 2 Configuration OPTIONS1 Options 1 ConfigurationSCHEDOVR Timed Override Setup RESETCON Temperature Reset and Demand LimitSETPOINT ALARMS: Maintenance Display UNITMAINTENANCE DUALCHIL: Maintenance Display CURRMODS: Maintenance DisplayLOADFACT: Maintenance Display LEARNFNS Maintenance DisplayPM-COIL:Maintenance Display PM-PUMP:Maintenance DisplayPM-STRN Maintenance Display RUNTEST: Maintenance Display STRTHOUR Maintenance Display TESTMODE: Maintenance DisplayVERSIONS: Maintenance Display WSMDEFME: Maintenance Display FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMP APPENDIX BAND MANUAL STARTERS FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMP AND MANUAL STARTERS contDataPort, DataLink, BAClink Object Definition APPENDIX CSETPOINT OPTIONSDesign Information START-UPCHECKLIST FOR 30RA LIQUID CHILLERRemove and use for Job File I.Project Information II. Preliminary Equipment CheckStart and Operate Machine. Complete the Following III. Unit Start-UpCL-3 Record Software Versions MODE — RUN STATUS COMMENTSCL-4 UNIT Configuration Settings OPTIONS1 Options ConfigurationIII.Unit Start-Upcont CL-6 OPTIONS2 Options ConfigurationRSET Reset Configuration Settings III.Unit Start-UpcontCL-7 SLCT Setpoint and Ramp Load ConfigurationIII.Unit Start-Upcont SETPOINTIII.Unit Start-Upcont Service Test Mode and Sub-ModeDirectory