Sterling 30RA010-055 manual CL-3

Page 95

OPERATING DATA:

RECORD THE FOLLOWING INFORMATION FROM THE PRESSURES AND TEMPERATURES MODES WHEN MACHINE IS IN A STABLE OPERATING CONDITION:

PRESSURE/TEMPERATURE

 

 

 

 

 

 

 

 

 

 

CIRCUIT A

 

 

 

 

CIRCUIT B

DISCHARGE PRESSURE

DP.A

 

 

 

DP.B

SUCTION PRESSURE

SP.A

 

 

 

SP.B

SATURATED CONDENSING TEMP

SCT.A

 

 

 

SCT.B

SATURATED SUCTION TEMP

SST.A

 

 

 

SST.B

LIQUID LINE TEMPERATURE*

 

 

 

 

 

 

 

 

 

DISCHARGE LINE TEMPERATURE*

 

 

 

 

 

 

 

 

 

RETURN GAS TEMPERATURE*

 

 

 

 

 

 

 

 

 

*Readings taken with a digital thermometer.

 

 

 

 

 

 

 

 

 

COOLER EWT

EWT

 

 

 

 

 

 

COOLER LWT

LWT

 

 

 

 

 

 

OUTDOOR-AIR TEMPERATURE

OAT

 

 

 

 

 

 

CONTROL POINT

CTPT

 

 

 

 

 

 

PERCENT TOTAL CAPACITY

CAP

 

 

 

 

 

 

LEAD/LAG LEAVING FLUID

DLWT

 

 

 

(Dual Chiller Control Only)

Compressor Running Current — All readings taken at full load.

 

 

 

 

 

 

COMPRESSOR MOTOR CURRENT

L1

L2

 

 

 

L3

COMPRESSOR A1

 

 

 

 

 

 

 

 

 

COMPRESSOR A2

 

 

 

 

 

 

 

 

 

COMPRESSOR B1

 

 

 

 

 

 

 

 

 

COMPRESSOR B2

 

 

 

 

 

 

 

 

 

CONDENSER FAN MOTOR CURRENT

L1

L2

 

 

 

L3

FAN MOTOR 1

 

 

 

 

 

 

 

 

 

FAN MOTOR 2

 

 

 

 

 

 

 

 

 

FAN MOTOR 3

 

 

 

 

 

 

 

 

 

FAN MOTOR 4

 

 

 

 

 

 

 

 

 

COOLER PUMP MOTOR CURRENT

L1

L2

 

 

 

L3

COOLER PUMP 1

 

 

 

 

 

 

 

 

 

COOLER PUMP 2

 

 

 

 

 

 

 

 

 

CL-3

Image 95
Contents SAFETY CONSIDERATIONS GENERAL CONTENTSTable 1 — Unit Sizes MAJOR SYSTEM COMPONENTSControl Module Communication Sterlco Comfort Network SCN Interface —Table 4 - Output Relays Table 3 — Status SwitchesTable 5 - SCN Communication Bus Wiring Table 2 — Thermistor DesignationsLEGEND FOR FIG. Page Page 30RA010-018AQUA SNAP Fig. 3 — Wiring Schematic 30RA010-018SEE NOTE SEE NOTE AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICFig. 3 - Wiring Schematic 30RA010-018cont 30RA022-030AQUA SNAP Fig. 4 - Wiring Schematic 30RA022-030AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATIC Fig. 4 - Wiring Schematic 30RA022-030cont30RA032-040AQUA SNAP Fig. 5 — Wiring Schematic 30RA032-040AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATIC Fig. 5 — Wiring Schematic 30RA032-040cont30RA042-055AQUA SNAP Fig. 6 — Wiring Schematic 30RA042-055AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATIC Fig. 6 — Wiring Schematic 30RA042-055contMODE Fig. 7 — Main Base BoardESCAPEENTER REMOTE CONTACT SW1 OFF ENABLE OFF SW2 ONFig. 9 — Typical Space Temperature Sensor Wiring CEPL130351 Fig. 11 - Energy Management Module100/100 Fig. 12 — Deadband Multiplier Fig. 14 — 30RA Condenser Fan Sequence Fig. 13 — Operating Envelope forR-22Maneurop Compressor Cooling Set Point Select Fig. 16 — Scrolling Marquee Display Service Test See Table 11 — Both main powerand control circuit power must be on Table 8 — Control Methods and Cooling Set PointsOptional Factory-InstalledHydronic Package — •Cooler Pump Control CPC Configuration, OPT1 ON Table 9 — Marquee Display Menu Structure Fig. 17 — Dual Chiller Thermistor LocationTable 10 — Run Status Mode and Sub-ModeDirectory SUB-MODE Table 12 - Temperature Mode and Sub-ModeDirectory Table 15 — Inputs Mode and Sub-ModeDirectory Table 13 — Pressure Mode and Sub-ModeDirectoryTable 14 — Set Point and Sub-ModeDirectory DISPLAY Table 16 — Outputs Mode and Sub-ModeDirectorySUB-MODE KEYPADDISPLAY SUB-MODEKEYPAD ITEMDISPLAY SUB-MODEKEYPAD ITEMTable 18 — Time Clock Mode and Sub-ModeDirectory PER.3 SUB-MODE Table 19 — Operating Mode and Sub-ModeDirectory Table 20 — Alarms Mode and Sub-ModeDirectoryDISPLAY SUB-MODEITEM KEYPAD ENTRYRSET DISP Table 23 — Operating Modes Table 25A — 4-20mA Reset Table 24 — Example of Reading and Clearing AlarmsTable 26B — Configuring Return Temperature Reset Fig. 20 — Space Temperature Reset Fig. 18 — Standard Chilled FluidTemperature Control — No Reset Fig. 19 — Outdoor-AirTemperature ResetFig. 21B — Cooling Set Point 4 to 20 mA Fig. 21A — 4- to 20-mADemand LimitingTable 27 — Configuring Demand Limit TROUBLESHOOTINGand fluid tubing Table 28 — TroubleshootingRecommended that system be filled with an appro FU — Fuse GND — Ground Fig. 22 — Component Arrangement — 30RA010-030FU — Fuse GND — Ground Fig. 23 — Component Arrangement — 30RA032-040FU — Fuse GND — Ground Fig. 24 — Component Arrangement — 30RA042-055NOTES LEGEND Table 29 — Alarm and Alert Codes Table 29 - Alarm and Alert Codes cont ALARM Table 29 — Alarm and Alert Codes contALARM Table 29 — Alarm and Alert Codes contALARM Table 29 — Alarm and Alert Codes contElectronic Components SERVICECompressor Replacement Refer to Fig Table 30 - Unit Torque SpecificationFig. 30 — Compressor Location — 30RA032-055 Fig. 28 — Compressor WiringFig. 27 — Typical Compressor Mounting — All Sizes Fig. 29 — Compressor Location — 30RA010-030Table 31 - Oil Charge Condenser Section and CoilsFig. 33 — Condenser-FanPosition Standard Fan Fig. 31 — 30RA Access PanelsCheck Refrigerant Feed Components Fig. 32 — Condenser-FanMountingCheck Unit Safeties Table 32 — Factory Settings, High-PressureSwitch Fixed Compressor and Unit Protective DevicesCOOLER FREEZE-UPPROTECTION TEMP TEMP For Thermistor T10 For Thermistor T10 Fig. 36 — Thermistor Connections to Main Base Board, J8 ConnectorFig. 35 — Fluid-SideTemperature Sensors T1 and T2 PROGRAMMING Mode •P51: SOFTWARE version Table 37 - Fault Codes•P50: FAULT HISTORY — Last 8 faults PARAMETERS Table 39 — Replacement Modules System Check MAINTENANCEMinimum Loop Volume PRE-START-UPOperating Limitations Standard 30RA Units OPERATION SEQUENCETable 41 — Temperature Limits for CIRCA_AN Circuit A Analog Parameters APPENDIX ASCN Tables A_UNIT General Unit Parameters CIRCADIO Circuit A Discrete Inputs/OutputsOPTIONS Unit Parameters CIRCBDIO Circuit B Discrete Inputs/OutputsCIRCB_AN Circuit B Analog Parameters BRODEFS Broadcast POC Definition Table ALARMDEF Alarm Definition TableDISPLAY Marquee Display SETUP DUALCHIL Dual Chiller Configuration SettingsOPTIONS2 Options 2 Configuration OPTIONS1 Options 1 ConfigurationSETPOINT SCHEDOVR Timed Override SetupRESETCON Temperature Reset and Demand Limit MAINTENANCE ALARMS: Maintenance DisplayUNIT DUALCHIL: Maintenance Display CURRMODS: Maintenance DisplayLOADFACT: Maintenance Display LEARNFNS Maintenance DisplayPM-STRN Maintenance Display PM-COIL:Maintenance DisplayPM-PUMP:Maintenance Display RUNTEST: Maintenance Display VERSIONS: Maintenance Display STRTHOUR Maintenance DisplayTESTMODE: Maintenance Display WSMDEFME: Maintenance Display AND MANUAL STARTERS FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMPAPPENDIX B FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMP AND MANUAL STARTERS contDataPort, DataLink, BAClink Object Definition APPENDIX CSETPOINT OPTIONSDesign Information START-UPCHECKLIST FOR 30RA LIQUID CHILLERRemove and use for Job File I.Project Information II. Preliminary Equipment CheckStart and Operate Machine. Complete the Following III. Unit Start-UpCL-3 CL-4 Record Software Versions MODE — RUN STATUSCOMMENTS III.Unit Start-Upcont UNIT Configuration SettingsOPTIONS1 Options Configuration CL-6 OPTIONS2 Options ConfigurationRSET Reset Configuration Settings III.Unit Start-UpcontCL-7 SLCT Setpoint and Ramp Load ConfigurationIII.Unit Start-Upcont SETPOINTIII.Unit Start-Upcont Service Test Mode and Sub-ModeDirectory