Table 7 — Part Load Data Percent Displacement, Standard Units with Minimum Load Valve
30RA UNIT SIZE | CONTROL | LOADING SEQ A | LOADING SEQ B | |||
STEPS | % Displacement | Compressor | % Displacement | Compressor | ||
| ||||||
|
| |||||
010 (50/60 Hz) | 1 | 69/ 71 | A1* | — | — | |
2 | 100/100 | A1 | — | — | ||
| ||||||
015 (60 Hz) | 1 | 79 | A1* | — | — | |
2 | 100 | A1 | — | — | ||
| ||||||
015 (50 Hz) | 1 | 28 | A1* | — | — | |
2 | 50 | A1 | — | — | ||
| 3 | 100 | A1,A2 | — | — | |
018 (50/60 Hz) | 1 | 32/ 31 | A1* | — | — | |
2 | 50/ 50 | A1 | — | — | ||
| 3 | 100/100 | A1,A2 | — | — | |
022 (50/60 Hz) | 1 | 27/ 35 | A1* | — | — | |
2 | 42/ 50 | A1 | — | — | ||
| 3 | 100/100 | A1,A2 | — | — | |
025 (50/60 Hz) | 1 | 38/ 37 | A1* | — | — | |
2 | 50/ 50 | A1 | — | — | ||
| 3 | 100/100 | A1,A2 | — | — | |
030 | 1 | 39 | A1* | — | — | |
2 | 50 | A1 | — | — | ||
| 3 | 100 | A1,A2 | — | — | |
| 1 | 15 | A1* | 30 | B1* | |
032 | 2 | 25 | A1 | 40 | B1 | |
3 | 60 | A1,A2 | 65 | A1,B1 | ||
| ||||||
| 4 | 100 | A1,A2,B1 | 100 | A1,A2,B1 | |
| 1 | 16/25 | A1* | 32/25 | B1* | |
035 (50/60 Hz) | 2 | 25/33 | A1 | 40/33 | B1 | |
3 | 60/67 | A1,A2 | 65/67 | A1,B1 | ||
| ||||||
| 4 | 100 | A1,A2,B1 | 100 | A1,A2,B1 | |
| 1 | 24 | A1* | 29 | B1* | |
040 | 2 | 32 | A1 | 37 | B1 | |
3 | 63 | A1,A2 | 68 | A1,B1 | ||
| ||||||
| 4 | 100 | A1,A2,B1 | 100 | A1,A2,B1 | |
| 1 | 18 | A1* | 18 | B1* | |
042 | 2 | 25 | A1 | 25 | B1 | |
3 | 50 | A1,B1 | 50 | A1,B1 | ||
| 4 | 75 | A1,A2,B1 | 75 | A1,B1,B2 | |
| 5 | 100 | A1,A2,B1,B2 | 100 | A1,A2,B1,B2 | |
| 1 | 15 | A1* | 15 | B1* | |
045 (60 Hz) | 2 | 22 | A1 | 22 | B1 | |
3 | 44 | A1,B1 | 44 | A1,B1 | ||
| 4 | 72 | A1,A2,B1 | 72 | A1,B1,B2 | |
| 5 | 100 | A1,A2,B1,B2 | 100 | A1,A2,B1,B2 | |
| 1 | 19 | A1* | 19 | B1* | |
045 (50 Hz), 050 | 2 | 25 | A1 | 25 | B1 | |
3 | 50 | A1,B1 | 50 | A1,B1 | ||
| 4 | 77 | A1,A2,B1 | 77 | A1,B1,B2 | |
| 5 | 100 | A1,A2,B1,B2 | 100 | A1,A2,B1,B2 | |
| 1 | 20 | A1* | 20 | B1* | |
055 | 2 | 25 | A1 | 25 | B1 | |
3 | 50 | A1,B1 | 50 | A1,B1 | ||
| 4 | 75 | A1,A2,B1 | 75 | A1,B1,B2 | |
| 5 | 100 | A1,A2,B1,B2 | 100 | A1,A2,B1,B2 |
*Minimum Load Valve energized.
NOTE: These capacity steps may vary due to different capacity staging sequences.
19