Sterling 30RA010-055 manual Appendix A, SCN Tables A_UNIT General Unit Parameters

Page 77

APPENDIX A

SCN Tables

A_UNIT (General Unit Parameters)

DESCRIPTION

 

VALUE

UNITS

POINT NAME

FORCEABLE

Control Mode

0

= Test

 

STAT

N

 

1

= Local Off

 

 

 

 

2

= SCN Off

 

 

 

 

3

= Clock Off

 

 

 

 

4 = Emergency Stop

 

 

 

 

5

= Local On

 

 

 

 

6

= SCN On

 

 

 

 

7

= Clock On

 

 

 

 

8

= Heat Enabled

 

 

 

 

9

= Pump Delay

 

 

 

Occupied

No/Yes

 

OCC

N

SCN Chiller

Start/Stop

 

CHIL_S_S

Y

Low Sound Active

No/Yes

 

LSACTIVE

N

Alarm State

Normal/Alert/Alarm

 

ALM

N

Active Demand Limit

0 to 100

%

DEM_LIM

Y

Override Modes in Effect

No/Yes

 

MODE

N

Percent Total Capacity

0 to 100

%

CAP_T

N

Requested Stage

0 to 99

 

STAGE

N

Active Set Point

–20 to 70

°F

SP

N

Control Point

–20 to 70

°F

CTRL_PNT

Y

Entering Fluid Temp

snnn.n

°F

EWT

N

Leaving Fluid Temp

snnn.n

°F

LWT

N

Emergency Stop

Enable/Emstop

Enable

EMSTOP

Y

Minutes Left for Start

00:00 to 15:00

minutes

MIN_LEFT

N

PUMPS

 

 

 

 

 

Cooler Pump Relay 1

Off/On

 

COOLPMP1

N

Cooler Pump Relay 2

Off/On

 

COOLPMP2

N

Cooler Pump 1 Interlock

Open/Close

 

PMP1_FBK

N

Cooler Pump 2 Interlock

Open/Close

 

PMP2_FBK

N

Cooler Flow Switch

Open/Close

 

COOLFLOW

N

Rotate Cooler Pumps Now

No/Yes

 

ROT_PUMP

 

 

 

 

 

 

Heat/Cool Select

Heat/Cool

 

HC_SEL

N

CIRCADIO (Circuit A Discrete Inputs/Outputs)

DESCRIPTION

VALUE

UNITS

POINT NAME

FORCEABLE

CIRC. A DISCRETE OUTPUTS

 

 

 

 

Compressor A1 Relay

On/Off

 

K_A1_RLY

N

Compressor A2 Relay

On/Off

 

K_A2_RLY

N

Minimum Load Valve Relay

On/Off

 

MLV_RLY

N

 

 

 

 

 

CIRC. A DISCRETE INPUTS

 

 

 

 

Compressor A1 Feedback

On/Off

 

K_A1_FBK

N

Compressor A2 Feedback

On/Off

 

K_A2_FBK

N

CIRCA_AN (Circuit A Analog Parameters)

DESCRIPTION

VALUE

UNITS

POINT NAME

FORCEABLE

CIRCUIT A ANALOG VALUES

 

 

 

 

Percent Total Capacity

0-100

%

CAPA_T

N

Percent Available Cap.

0-100

%

CAPA_A

N

Discharge Pressure

nnn.n

PSIG

DP_A

N

Suction Pressure

nnn.n

PSIG

SP_A

N

Calculated HP Setpoint A

nnn.n

°F

HSP_A

N

Saturated Condensing Tmp

snnn.n

°F

TMP_SCTA

N

Saturated Suction Temp

snnn.n

°F

TMP_SSTA

N

Compr Return Gas Temp

snnn.n

°F

TMP_RGTA

N

Suction Superheat Temp

snnn.n

F

SH_A

N

77

Image 77
Contents SAFETY CONSIDERATIONS GENERAL CONTENTSControl Module Communication MAJOR SYSTEM COMPONENTSSterlco Comfort Network SCN Interface — Table 1 — Unit SizesTable 5 - SCN Communication Bus Wiring Table 3 — Status SwitchesTable 2 — Thermistor Designations Table 4 - Output RelaysLEGEND FOR FIG. Page Page 30RA010-018AQUA SNAP Fig. 3 — Wiring Schematic 30RA010-018SEE NOTE SEE NOTE AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICFig. 3 - Wiring Schematic 30RA010-018cont 30RA022-030AQUA SNAP Fig. 4 - Wiring Schematic 30RA022-030AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATIC Fig. 4 - Wiring Schematic 30RA022-030cont30RA032-040AQUA SNAP Fig. 5 — Wiring Schematic 30RA032-040AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATIC Fig. 5 — Wiring Schematic 30RA032-040cont30RA042-055AQUA SNAP Fig. 6 — Wiring Schematic 30RA042-055AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATIC Fig. 6 — Wiring Schematic 30RA042-055contESCAPEENTER Fig. 7 — Main Base BoardREMOTE CONTACT SW1 OFF ENABLE OFF SW2 ON MODEFig. 9 — Typical Space Temperature Sensor Wiring CEPL130351 Fig. 11 - Energy Management Module100/100 Fig. 12 — Deadband Multiplier Fig. 14 — 30RA Condenser Fan Sequence Fig. 13 — Operating Envelope forR-22Maneurop Compressor Cooling Set Point Select and control circuit power must be on Service Test See Table 11 — Both main powerTable 8 — Control Methods and Cooling Set Points Fig. 16 — Scrolling Marquee DisplayOptional Factory-InstalledHydronic Package — •Cooler Pump Control CPC Configuration, OPT1 ON Table 9 — Marquee Display Menu Structure Fig. 17 — Dual Chiller Thermistor LocationTable 10 — Run Status Mode and Sub-ModeDirectory SUB-MODE Table 12 - Temperature Mode and Sub-ModeDirectory Table 15 — Inputs Mode and Sub-ModeDirectory Table 13 — Pressure Mode and Sub-ModeDirectoryTable 14 — Set Point and Sub-ModeDirectory SUB-MODE Table 16 — Outputs Mode and Sub-ModeDirectoryKEYPAD DISPLAYKEYPAD SUB-MODEITEM DISPLAYKEYPAD SUB-MODEITEM DISPLAYTable 18 — Time Clock Mode and Sub-ModeDirectory PER.3 SUB-MODE Table 19 — Operating Mode and Sub-ModeDirectory Table 20 — Alarms Mode and Sub-ModeDirectoryITEM SUB-MODEKEYPAD ENTRY DISPLAYRSET DISP Table 23 — Operating Modes Table 25A — 4-20mA Reset Table 24 — Example of Reading and Clearing AlarmsTable 26B — Configuring Return Temperature Reset Temperature Control — No Reset Fig. 18 — Standard Chilled FluidFig. 19 — Outdoor-AirTemperature Reset Fig. 20 — Space Temperature ResetFig. 21B — Cooling Set Point 4 to 20 mA Fig. 21A — 4- to 20-mADemand LimitingTable 27 — Configuring Demand Limit TROUBLESHOOTINGand fluid tubing Table 28 — TroubleshootingRecommended that system be filled with an appro FU — Fuse GND — Ground Fig. 22 — Component Arrangement — 30RA010-030FU — Fuse GND — Ground Fig. 23 — Component Arrangement — 30RA032-040FU — Fuse GND — Ground Fig. 24 — Component Arrangement — 30RA042-055NOTES LEGEND Table 29 — Alarm and Alert Codes Table 29 - Alarm and Alert Codes cont ALARM Table 29 — Alarm and Alert Codes contALARM Table 29 — Alarm and Alert Codes contALARM Table 29 — Alarm and Alert Codes contCompressor Replacement Refer to Fig SERVICETable 30 - Unit Torque Specification Electronic ComponentsFig. 27 — Typical Compressor Mounting — All Sizes Fig. 28 — Compressor WiringFig. 29 — Compressor Location — 30RA010-030 Fig. 30 — Compressor Location — 30RA032-055Table 31 - Oil Charge Condenser Section and CoilsCheck Refrigerant Feed Components Fig. 31 — 30RA Access PanelsFig. 32 — Condenser-FanMounting Fig. 33 — Condenser-FanPosition Standard FanSwitch Fixed Table 32 — Factory Settings, High-PressureCompressor and Unit Protective Devices Check Unit SafetiesCOOLER FREEZE-UPPROTECTION TEMP TEMP For Thermistor T10 For Thermistor T10 Fig. 36 — Thermistor Connections to Main Base Board, J8 ConnectorFig. 35 — Fluid-SideTemperature Sensors T1 and T2 PROGRAMMING Mode •P51: SOFTWARE version Table 37 - Fault Codes•P50: FAULT HISTORY — Last 8 faults PARAMETERS Table 39 — Replacement Modules Minimum Loop Volume MAINTENANCEPRE-START-UP System CheckOperating Limitations Standard 30RA Units OPERATION SEQUENCETable 41 — Temperature Limits for SCN Tables A_UNIT General Unit Parameters APPENDIX ACIRCADIO Circuit A Discrete Inputs/Outputs CIRCA_AN Circuit A Analog ParametersOPTIONS Unit Parameters CIRCBDIO Circuit B Discrete Inputs/OutputsCIRCB_AN Circuit B Analog Parameters DISPLAY Marquee Display SETUP ALARMDEF Alarm Definition TableDUALCHIL Dual Chiller Configuration Settings BRODEFS Broadcast POC Definition TableOPTIONS2 Options 2 Configuration OPTIONS1 Options 1 ConfigurationSETPOINT SCHEDOVR Timed Override SetupRESETCON Temperature Reset and Demand Limit MAINTENANCE ALARMS: Maintenance DisplayUNIT DUALCHIL: Maintenance Display CURRMODS: Maintenance DisplayLOADFACT: Maintenance Display LEARNFNS Maintenance DisplayPM-STRN Maintenance Display PM-COIL:Maintenance DisplayPM-PUMP:Maintenance Display RUNTEST: Maintenance Display VERSIONS: Maintenance Display STRTHOUR Maintenance DisplayTESTMODE: Maintenance Display WSMDEFME: Maintenance Display AND MANUAL STARTERS FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMPAPPENDIX B FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMP AND MANUAL STARTERS contDataPort, DataLink, BAClink Object Definition APPENDIX CSETPOINT OPTIONSRemove and use for Job File I.Project Information START-UPCHECKLIST FOR 30RA LIQUID CHILLERII. Preliminary Equipment Check Design InformationStart and Operate Machine. Complete the Following III. Unit Start-UpCL-3 CL-4 Record Software Versions MODE — RUN STATUSCOMMENTS III.Unit Start-Upcont UNIT Configuration SettingsOPTIONS1 Options Configuration RSET Reset Configuration Settings OPTIONS2 Options ConfigurationIII.Unit Start-Upcont CL-6III.Unit Start-Upcont SLCT Setpoint and Ramp Load ConfigurationSETPOINT CL-7III.Unit Start-Upcont Service Test Mode and Sub-ModeDirectory