III.Unit
COMPONENT TEST
USE ESCAPE/ARROW KEYS TO ILLUMINATE CONFIGURATION LED. PRESS ENTER TO DISPLAY ‘DISP’. PRESS ENTER AGAIN TO DISPLAY ‘TEST’ FOLLOWED BY ‘OFF’. PRESS ENTER TO STOP DISPLAY AT ‘OFF’ AND ENTER AGAIN SO ‘OFF’ DISPLAY FLASHES. ‘PASS’ AND ‘WORD’ WILL FLASH IF PASSWORD NEEDS TO BE ENTERED. PRESS ENTER TO DISPLAY PASSWORD FIELD AND USE THE ENTER KEY FOR EACH OF THE FOUR PASSWORD DIGITS. USE ARROW KEYS IF PASSWORD IS OTHER THAN STANDARD. AT FLASHING ‘OFF’ DISPLAY, PRESS THE UP ARROW KEY TO DISPLAY ‘ON’ AND PRESS ENTER. ALL LED SEGMENTS AND MODE LEDS WILL LIGHT UP. PRESS ESCAPE TO STOP THE TEST. PRESS ESCAPE TO RETURN TO THE ‘DISP’ DISPLAY. PRESS THE ESCAPE KEY AGAIN AND USE THE ARROW KEYS TO ILLU- MINATE THE SERVICE TEST LED. PRESS ENTER TO DISPLAY ‘TEST’. PRESS ENTER TO STOP DISPLAY AT ‘OFF’ AND ENTER AGAIN SO ‘OFF’ FLASHES. PRESS THE UP ARROW KEY AND ENTER TO ENABLE THE MANUAL MODE. PRESS ESCAPE AND DISPLAY NOW SAYS ‘TEST’ ‘ON’. REFER TO THE TABLE BELOW.
Service Test Mode and Sub-Mode Directory
KEYPAD | ITEM | DISPLAY | ITEM | COMMENT | Completed | ||||
ENTRY | EXPANSION | (Yes/No) | |||||||
|
|
|
| ||||||
|
|
|
|
| ON/OFF | SERVICE TEST MODE | To Enable Service Test Mode, |
| |
|
| ENTER |
|
|
| ||||
|
|
|
|
|
| move Enable/Off/Remote |
| ||
TEST |
|
|
|
|
|
|
| ||
|
|
|
|
|
| Contact switch to OFF. Change |
| ||
|
|
|
|
|
|
| TEST to ON. Move switch to |
| |
|
|
|
|
|
|
| ENABLE. |
| |
|
|
|
|
|
| OUTPUTS AND PUMPS |
|
| |
|
|
|
|
|
|
| SIZES |
| |
|
|
|
|
|
|
| Condenser fan at low speed |
| |
|
|
|
| FAN1 | ON/OFF | FAN 1 RELAY | SIZES |
| |
|
| ENTER |
|
| |||||
|
|
| Condenser fan A1 energized |
| |||||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| SIZES |
| |
|
|
|
|
|
|
| Condenser fan A2 energized |
| |
|
|
|
|
|
|
| SIZES |
| |
|
|
|
|
|
|
| Condenser fan A2 energized |
| |
|
|
|
| FAN2 | ON/OFF | FAN 2 RELAY | SIZES |
| |
OUTS |
|
|
| Condenser fan B1 at high speed |
| ||||
|
|
|
|
|
|
| |||
|
|
|
|
|
|
| SIZES |
| |
|
|
|
|
|
|
| Condenser fan B2 energized |
| |
|
|
|
| CLP.1 | ON/OFF | COOLER PUMP 1 RELAY |
|
| |
|
|
|
|
|
|
|
|
| |
|
|
|
| CLP.2 | ON/OFF | COOLER PUMP 2 RELAY |
|
| |
|
|
|
|
|
|
|
|
| |
|
|
|
| CL.HT | ON/OFF | COOLER/PUMP HEATER |
|
| |
|
|
|
|
|
|
|
|
| |
|
|
|
| RMT.A | ON/OFF | REMOTE ALARM RELAY |
|
| |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| CIRCUIT A COMPRESSOR TEST |
|
| |
|
| ENTER |
| CC.A1 | ON/OFF | COMPRESSOR A1 RELAY |
|
| |
CMPA |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| ||
|
|
| CC.A2 | ON/OFF | COMPRESSOR A2 RELAY |
|
| ||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
| |
|
|
|
| MLV | ON/OFF | MINIMUM LOAD VALVE RELAY |
|
| |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| CIRCUIT B COMPRESSOR TEST |
|
| |
|
| ENTER |
| CC.B1 | ON/OFF | COMPRESSOR B1 RELAY | See Note |
| |
CMPB |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| ||
|
|
| CC.B2 | ON/OFF | COMPRESSOR B2 RELAY | See Note |
| ||
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
| |
|
|
|
| MLV | ON/OFF | MINIMUM LOAD VALVE RELAY | See Note |
| |
|
|
|
|
|
|
|
|
|
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.