Table 17 — Configuration Mode and
KEYPAD | ITEM | DISPLAY | ITEM |
| COMMENT | |||
ENTRY | EXPANSION |
| ||||||
|
|
|
|
| ||||
OPT1 |
|
|
|
|
| UNIT OPTIONS 1 HARDWARE |
|
|
|
|
|
| FLUD | X | COOLER FLUID | Default: Water | |
|
| ENTER |
| |||||
|
|
|
|
|
| 1 | = Water | |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| 2 | = Medium Temperature Brine |
|
|
|
| MLV.S | YES/NO | MINIMUM LOAD VALVE SELECT |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| MMR.S | YES/NO | MOTORMASTER SELECT |
|
|
|
|
|
|
|
|
|
| |
|
|
|
| RG.EN | ENBL/DSBL | RETURN GAS SENSOR ENABLE | Default: DISABLED | |
|
|
|
|
|
|
|
| |
|
|
|
| CPC | ON/OFF | COOLER PUMP CONTROL | Default: On | |
|
|
|
|
|
|
|
|
|
|
|
|
| PM1E | YES/NO | COOLER PUMP 1 ENABLE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| PM2E | YES/NO | COOLER PUMP 2 ENABLE |
|
|
|
|
|
|
|
|
|
| |
|
|
|
| PM.P.S | YES/NO | COOLER PMP PERIODIC STRT | Default: No | |
|
|
|
|
|
|
|
| |
|
|
|
| PM.SL | X | COOLER PUMP SELECT | Default: Automatic | |
|
|
|
|
|
|
| 0 | = Automatic |
|
|
|
|
|
|
| 1 | = Pump 1 Starts first |
|
|
|
|
|
|
| 2 | = Pump 2 Starts first |
|
|
|
| PM.DY | XX MIN | COOLER PUMP SHUTDOWN DLY | 0 to 10 minutes, Default: 1 min. | |
|
|
|
|
|
|
|
| |
|
|
|
| PM.DT | XXXX HRS | PUMP CHANGEOVER HOURS | Default: 500 hours | |
|
|
|
|
|
|
|
| |
|
|
|
| ROT.P | YES/NO | ROTATE COOLER PUMPS NOW | User Entry | |
|
|
|
|
|
|
|
|
|
|
|
|
| EMM | YES/NO | EMM MODULE INSTALLED |
|
|
|
|
|
|
|
|
|
|
|
OPT2 |
|
|
|
|
| UNIT OPTIONS 2 CONTROLS |
|
|
|
|
|
| CTRL | X | CONTROL METHOD | Default: Switch | |
|
| ENTER |
| |||||
|
|
|
|
|
| 0 | = Enable/Off/Remote Switch | |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| 2 | = Occupancy |
|
|
|
|
|
|
| 3 | = SCN Control |
|
|
|
| SCNA | XXX | SCN ADDRESS | Default: 1 | |
|
|
|
| Range: 1 to 239 | ||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
|
|
|
| SCNB | XXX | SCN BUS NUMBER | Default: 0 | |
|
|
|
| Range: 0 to 239 | ||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
|
|
|
| BAUD | X | SCN BAUD RATE | Default: 9600 | |
|
|
|
|
|
|
| 1 | = 2400 |
|
|
|
|
|
|
| 2 | = 4800 |
|
|
|
|
|
|
| 3 | = 9600 |
|
|
|
|
|
|
| 4 | = 19,200 |
|
|
|
|
|
|
| 5 | = 38,400 |
|
|
|
| LOAD | X | LOADING SEQUENCE SELECT | Default: Equal | |
|
|
|
|
|
|
| 1 | = Equal |
|
|
|
|
|
|
| 2 | = Staged |
|
|
|
| LLCS | X | LEAD/LAG CIRCUIT SELECT | Default: Automatic | |
|
|
|
|
|
|
| 1 | = Automatic |
|
|
|
|
|
|
| 2 | = Circuit A Leads |
|
|
|
|
|
|
| 3 | = Circuit B Leads |
|
|
|
| LCWT | XX.X ∆F | HIGH LCW ALERT LIMIT | Default: 60 | |
|
|
|
| Range: 2 to 60 °F | ||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
|
|
|
| DELY | XX | MINUTES OFF TIME | Default: 0 Minutes | |
|
|
|
| Range: 0 to 15 Minutes | ||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
|
|
|
| ICE.M | ENBL/DSBL | ICE MODE ENABLE | Default: Disable | |
|
|
|
|
|
|
|
| |
|
|
|
| CLS.C | ENBL/DSBL | CLOSE CONTROL SELECT | Default: Disable | |
|
|
|
|
|
|
|
| |
|
|
|
| LS.MD | X | LOW SOUND MODE SELECT | Default: 0 | |
|
|
|
|
|
|
| 0 | = Mode Disable |
|
|
|
|
|
|
| 1 | = Fan Noise Only |
|
|
|
|
|
|
| 2 | = Fan/Compressor Noise |
|
|
|
|
|
|
|
| |
|
|
|
| LS.ST | 00:00 | LOW SOUND START TIME | Default: 00:00 | |
|
|
|
|
|
|
|
| |
|
|
|
| LS.ND | 00:00 | LOW SOUND END TIME | Default: 00:00 | |
|
|
|
|
|
|
|
| |
|
|
|
| LS.LT | XXX % | LOW SOUND CAPACITY LIMIT | Default: 100% | |
|
|
|
| Range: 0 to 100% | ||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
RSET |
|
|
|
|
| RESET COOL TEMP |
|
|
|
|
|
| CRST | X | COOLING RESET TYPE | Default: No Reset | |
|
| ENTER |
| |||||
|
|
|
|
|
| 0 | = No Reset | |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| 1 | = 4 to 20 mA Input |
|
|
|
|
|
|
| 2 | = Outdoor Air Temperature |
|
|
|
|
|
|
| 3 | = Return Fluid |
|
|
|
|
|
|
| 4 | = Space Temperature |
|
|
|
| MA.DG | XX.X ∆F | Default: 0.0 ∆F | ||
|
|
|
| Range: | ||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
|
|
|
| RM.NO | XXX.X °F | REMOTE - NO RESET TEMP | Default: 125 F (51.7 C) | |
|
|
|
| Range: 0° to 125 F | ||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|