TXV SENSOR
LOCATION
TXV SENSOR
LOCATION
Fig. 34 — Mounting Locations for TXV Sensing Bulb
The amount of capacity reduction achieved by the mini- mum load valve is not adjustable. The total unit capacity with the minimum load valve is shown in Table 7.
PRESSURE RELIEF DEVICES — All units have one pres- sure relief device per circuit located in the liquid line which re- lieves at 210 F (100 C).
Compressor and Unit Protective Devices
MANUAL STARTER — There is one manual starter per compressor in each unit. It protects the compressor(s) against overloading, locked rotor conditions, and primary single phas- ing. If the manual starter trips, determine the cause and correct it before resetting.
Manual starters are factory set; field adjustment should not be required. Manual starters are also factory installed for each condenser fan motor and
NOTE:
COMPRESSOR INTERNAL THERMAL PROTECTION — All models include internal compressor protection. Models using the SM110 compressor (015 50 Hz and 018 60 Hz) have internal line break overloads. All other compressor models have internal discharge temperature thermostats that are wired in series with the compressor high pressure switch in the com- pressor motor junction box. The thermostat opens and shuts off the compressor if the discharge gas temperature exceeds 275 F (135 C). The thermostat will automatically reset when the tem- perature drops below a preset level, however, the control mod- ule will keep the unit locked off until the alert condition is reset.
Check Unit Safeties
The
The
Table 32 — Factory Settings, High-Pressure
Switch (Fixed)
UNIT | CUTOUT | ||||
Psig | kPa | Psig | kPa | ||
| |||||
30RA | 426 ± 7 | 2937 ± 48 | 324 ± 20 | 2206 ± 138 |
Clear the alarm using the Scrolling Marquee display as de- scribed on page 42. The unit should restart after the compressor
PRESSURE TRANSDUCERS — Each refrigerant circuit is equipped with a suction and discharge pressure transducer. The transducers are NOT the same part number. The discharge pressure transducer is the universal pressure transducer while the suction pressure transducer is a discrete low pressure trans- ducer. These inputs to the MBB are not only used to monitor the status of the unit, but to also maintain operation of the chill- er within the compressor manufacturer's specified limits. The input to the MBB from the suction pressure transducer is also used to protect the compressor from operating at low pressure conditions. In some cases, the unit may not be able to run at full capacity. The control module will automatically reduce the ca- pacity of a circuit as needed to maintain specified maximum/ minimum operating pressures.
62