Table 13 — Pressure Mode and Sub-Mode Directory
KEYPAD | ITEM | DISPLAY | ITEM | COMMENT | ||||
ENTRY | EXPANSION | |||||||
|
|
|
| |||||
PRC.A |
|
|
|
|
| PRESSURES CIRCUIT A |
| |
|
|
|
| DP.A | XXX.X PSIG | DISCHARGE PRESSURE |
| |
|
| ENTER |
|
| ||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
| SP.A | XXX.X PSIG | SUCTION PRESSURE |
| |
|
|
|
|
|
|
|
| |
PRC.B |
|
|
|
|
| PRESSURES CIRCUIT B | See Note | |
|
|
| DP.B | XXX.X PSIG | DISCHARGE PRESSURE | See Note | ||
|
| ENTER |
| |||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
| SP.B | XXX.X PSIG | SUCTION PRESSURE | See Note | |
|
|
|
|
|
|
|
|
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
Table 14 — Set Point and Sub-Mode Directory
KEYPAD | ITEM | DISPLAY | ITEM | COMMENT | ||||
ENTRY | EXPANSION | |||||||
|
|
|
| |||||
COOL |
|
|
|
|
| COOLING SETPOINTS |
| |
|
|
|
| CSP.1 | XXX.X °F | COOLING SETPOINT 1 | Default: 44 F | |
|
| ENTER |
| |||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
| CSP.2 | XXX.X °F | COOLING SETPOINT 2 | Default: 44 F | |
|
|
|
|
|
|
|
| |
|
|
|
| CSP.3 | XXX.X °F | ICE SETPOINT | Default: 32 F | |
|
|
|
|
|
|
|
| |
HEAD |
|
|
|
|
| HEAD PRESSURE SETPOINTS |
| |
|
|
|
| HD.P.A | XXX.X °F | CALCULATED HP SETPOINT A | Default: 113 F | |
|
| ENTER |
| |||||
|
|
| (Read Only) | |||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
|
|
|
| HD.P.B | XXX.X °F | CALCULATED HP SETPOINT B | Default: 113 F | |
|
|
|
| (Read Only) | ||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
FRZ |
|
|
|
|
| BRINE FREEZE SETPOINT |
| |
|
|
| BR.FZ | XXX.X °F | BRINE FREEZE POINT | Default: 34 F | ||
|
| ENTER |
| |||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
Table 15 — Inputs Mode and Sub-Mode Directory
KEYPAD | ITEM | DISPLAY | ITEM | COMMENT | ||||
ENTRY | EXPANSION | |||||||
|
|
|
| |||||
GEN.I |
|
|
|
|
| GENERAL INPUTS |
| |
|
|
|
| STST | STRT/STOP | START/STOP SWITCH |
| |
|
| ENTER |
|
| ||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
| FLOW | ON/OFF | COOLER FLOW SWITCH |
| |
|
|
|
|
|
|
|
| |
|
|
|
| PM.F.1 | OPEN/CLSE | COOLER PUMP 1 INTERLOCK |
| |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
| 1 = Pump 1 | |
|
|
|
| LD.PM | X | Lead Pump | 2 = Pump 2 | |
|
|
|
|
|
|
| 3 = No Pump | |
|
|
|
|
|
|
|
| |
|
|
|
| PM.F.2 | OPEN/CLSE | COOLER PUMP 2 INTERLOCK |
| |
|
|
|
|
|
|
|
| |
|
|
|
| HT.RQ | ON/OFF | HEAT REQUEST |
| |
|
|
|
|
|
|
|
| |
|
|
|
| DLS1 | ON/OFF | DEMAND LIMIT SWITCH 1 |
| |
|
|
|
|
|
|
|
| |
|
|
|
| DLS2 | ON/OFF | DEMAND LIMIT SWITCH 2 |
| |
|
|
|
|
|
|
|
| |
|
|
|
| ICED | ON/OFF | ICE DONE |
| |
|
|
|
|
|
|
|
| |
|
|
|
| DUAL | ON/OFF | DUAL SETPOINT SWITCH |
| |
|
|
|
|
|
|
|
| |
CRCT |
|
|
|
|
| CIRCUITS INPUTS |
| |
|
|
| FKA1 | ON/OFF | COMPRESSOR A1 FEEDBACK |
| ||
|
| ENTER |
|
| ||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
| FKA2 | ON/OFF | COMPRESSOR A2 FEEDBACK |
| |
|
|
|
|
|
|
|
| |
|
|
|
| FKB1 | ON/OFF | COMPRESSOR B1 FEEDBACK | See Note | |
|
|
|
|
|
|
|
| |
|
|
|
| FKB2 | ON/OFF | COMPRESSOR B2 FEEDBACK | See Note | |
|
|
|
|
|
|
|
| |
|
|
|
|
|
| |||
|
|
| DMND | XX.X MA |
| |||
|
| ENTER |
|
| ||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
| RSET | XX.X MA |
| ||
|
|
|
|
|
|
|
| |
|
|
|
| CSP | XX.X MA |
| ||
|
|
|
|
|
|
|
|
30