Sterling 30RA010-055 manual Pressure Mode and Sub-ModeDirectory, Set Point and Sub-ModeDirectory

Page 30
Table 13 — Pressure Mode and Sub-Mode Directory

Table 13 — Pressure Mode and Sub-Mode Directory

SUB-MODE

KEYPAD

ITEM

DISPLAY

ITEM

COMMENT

ENTRY

EXPANSION

 

 

 

 

PRC.A

 

 

 

 

 

PRESSURES CIRCUIT A

 

 

 

 

 

DP.A

XXX.X PSIG

DISCHARGE PRESSURE

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP.A

XXX.X PSIG

SUCTION PRESSURE

 

 

 

 

 

 

 

 

 

PRC.B

 

 

 

 

 

PRESSURES CIRCUIT B

See Note

 

 

 

DP.B

XXX.X PSIG

DISCHARGE PRESSURE

See Note

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP.B

XXX.X PSIG

SUCTION PRESSURE

See Note

 

 

 

 

 

 

 

 

NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.

Table 14 — Set Point and Sub-Mode Directory

SUB-MODE

KEYPAD

ITEM

DISPLAY

ITEM

COMMENT

ENTRY

EXPANSION

 

 

 

 

COOL

 

 

 

 

 

COOLING SETPOINTS

 

 

 

 

 

CSP.1

XXX.X °F

COOLING SETPOINT 1

Default: 44 F

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CSP.2

XXX.X °F

COOLING SETPOINT 2

Default: 44 F

 

 

 

 

 

 

 

 

 

 

 

 

CSP.3

XXX.X °F

ICE SETPOINT

Default: 32 F

 

 

 

 

 

 

 

 

HEAD

 

 

 

 

 

HEAD PRESSURE SETPOINTS

 

 

 

 

 

HD.P.A

XXX.X °F

CALCULATED HP SETPOINT A

Default: 113 F

 

 

ENTER

 

 

 

 

(Read Only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HD.P.B

XXX.X °F

CALCULATED HP SETPOINT B

Default: 113 F

 

 

 

 

(Read Only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FRZ

 

 

 

 

 

BRINE FREEZE SETPOINT

 

 

 

 

BR.FZ

XXX.X °F

BRINE FREEZE POINT

Default: 34 F

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 15 — Inputs Mode and Sub-Mode Directory

SUB-MODE

KEYPAD

ITEM

DISPLAY

ITEM

COMMENT

ENTRY

EXPANSION

 

 

 

 

GEN.I

 

 

 

 

 

GENERAL INPUTS

 

 

 

 

 

STST

STRT/STOP

START/STOP SWITCH

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLOW

ON/OFF

COOLER FLOW SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

 

PM.F.1

OPEN/CLSE

COOLER PUMP 1 INTERLOCK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 = Pump 1

 

 

 

 

LD.PM

X

Lead Pump

2 = Pump 2

 

 

 

 

 

 

 

3 = No Pump

 

 

 

 

 

 

 

 

 

 

 

 

PM.F.2

OPEN/CLSE

COOLER PUMP 2 INTERLOCK

 

 

 

 

 

 

 

 

 

 

 

 

 

HT.RQ

ON/OFF

HEAT REQUEST

 

 

 

 

 

 

 

 

 

 

 

 

 

DLS1

ON/OFF

DEMAND LIMIT SWITCH 1

 

 

 

 

 

 

 

 

 

 

 

 

 

DLS2

ON/OFF

DEMAND LIMIT SWITCH 2

 

 

 

 

 

 

 

 

 

 

 

 

 

ICED

ON/OFF

ICE DONE

 

 

 

 

 

 

 

 

 

 

 

 

 

DUAL

ON/OFF

DUAL SETPOINT SWITCH

 

 

 

 

 

 

 

 

 

CRCT

 

 

 

 

 

CIRCUITS INPUTS

 

 

 

 

FKA1

ON/OFF

COMPRESSOR A1 FEEDBACK

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FKA2

ON/OFF

COMPRESSOR A2 FEEDBACK

 

 

 

 

 

 

 

 

 

 

 

 

 

FKB1

ON/OFF

COMPRESSOR B1 FEEDBACK

See Note

 

 

 

 

 

 

 

 

 

 

 

 

FKB2

ON/OFF

COMPRESSOR B2 FEEDBACK

See Note

 

 

 

 

 

 

 

 

4-20

 

 

 

 

 

4-20 MA INPUTS

 

 

 

 

DMND

XX.X MA

4-20 MA DEMAND SIGNAL

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RSET

XX.X MA

4-20 MA RESET SIGNAL

 

 

 

 

 

 

 

 

 

 

 

 

 

CSP

XX.X MA

4-20 MA COOLING SETPOINT

 

 

 

 

 

 

 

 

 

30

Image 30
Contents SAFETY CONSIDERATIONS CONTENTS GENERALSterlco Comfort Network SCN Interface — MAJOR SYSTEM COMPONENTSControl Module Communication Table 1 — Unit SizesTable 2 — Thermistor Designations Table 3 — Status SwitchesTable 5 - SCN Communication Bus Wiring Table 4 - Output RelaysLEGEND FOR FIG. Page Page Fig. 3 — Wiring Schematic 30RA010-018 30RA010-018AQUA SNAPAQUA-SNAPLOW VOLTAGE CONTROL SCHEMATIC Fig. 3 - Wiring Schematic 30RA010-018contSEE NOTE SEE NOTE Fig. 4 - Wiring Schematic 30RA022-030 30RA022-030AQUA SNAPFig. 4 - Wiring Schematic 30RA022-030cont AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICFig. 5 — Wiring Schematic 30RA032-040 30RA032-040AQUA SNAPFig. 5 — Wiring Schematic 30RA032-040cont AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICFig. 6 — Wiring Schematic 30RA042-055 30RA042-055AQUA SNAPFig. 6 — Wiring Schematic 30RA042-055cont AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICREMOTE CONTACT SW1 OFF ENABLE OFF SW2 ON Fig. 7 — Main Base BoardESCAPEENTER MODEFig. 9 — Typical Space Temperature Sensor Wiring Fig. 11 - Energy Management Module CEPL130351100/100 Fig. 12 — Deadband Multiplier Fig. 13 — Operating Envelope for R-22Maneurop CompressorFig. 14 — 30RA Condenser Fan Sequence Cooling Set Point Select Table 8 — Control Methods and Cooling Set Points Service Test See Table 11 — Both main powerand control circuit power must be on Fig. 16 — Scrolling Marquee DisplayOptional Factory-InstalledHydronic Package — •Cooler Pump Control CPC Configuration, OPT1 ON Fig. 17 — Dual Chiller Thermistor Location Table 9 — Marquee Display Menu StructureTable 10 — Run Status Mode and Sub-ModeDirectory SUB-MODE Table 12 - Temperature Mode and Sub-ModeDirectory Table 13 — Pressure Mode and Sub-ModeDirectory Table 14 — Set Point and Sub-ModeDirectoryTable 15 — Inputs Mode and Sub-ModeDirectory KEYPAD Table 16 — Outputs Mode and Sub-ModeDirectorySUB-MODE DISPLAYITEM SUB-MODEKEYPAD DISPLAYITEM SUB-MODEKEYPAD DISPLAYTable 18 — Time Clock Mode and Sub-ModeDirectory PER.3 SUB-MODE Table 20 — Alarms Mode and Sub-ModeDirectory Table 19 — Operating Mode and Sub-ModeDirectoryKEYPAD ENTRY SUB-MODEITEM DISPLAYRSET DISP Table 23 — Operating Modes Table 24 — Example of Reading and Clearing Alarms Table 25A — 4-20mA ResetTable 26B — Configuring Return Temperature Reset Fig. 19 — Outdoor-AirTemperature Reset Fig. 18 — Standard Chilled FluidTemperature Control — No Reset Fig. 20 — Space Temperature ResetFig. 21A — 4- to 20-mADemand Limiting Fig. 21B — Cooling Set Point 4 to 20 mATROUBLESHOOTING Table 27 — Configuring Demand LimitTable 28 — Troubleshooting Recommended that system be filled with an approand fluid tubing Fig. 22 — Component Arrangement — 30RA010-030 FU — Fuse GND — GroundFig. 23 — Component Arrangement — 30RA032-040 FU — Fuse GND — GroundFig. 24 — Component Arrangement — 30RA042-055 FU — Fuse GND — GroundNOTES LEGEND Table 29 — Alarm and Alert Codes Table 29 - Alarm and Alert Codes cont Table 29 — Alarm and Alert Codes cont ALARMTable 29 — Alarm and Alert Codes cont ALARMTable 29 — Alarm and Alert Codes cont ALARMTable 30 - Unit Torque Specification SERVICECompressor Replacement Refer to Fig Electronic ComponentsFig. 29 — Compressor Location — 30RA010-030 Fig. 28 — Compressor WiringFig. 27 — Typical Compressor Mounting — All Sizes Fig. 30 — Compressor Location — 30RA032-055Condenser Section and Coils Table 31 - Oil ChargeFig. 32 — Condenser-FanMounting Fig. 31 — 30RA Access PanelsCheck Refrigerant Feed Components Fig. 33 — Condenser-FanPosition Standard FanCompressor and Unit Protective Devices Table 32 — Factory Settings, High-PressureSwitch Fixed Check Unit SafetiesCOOLER FREEZE-UPPROTECTION TEMP TEMP For Thermistor T10 For Thermistor T10 Main Base Board, J8 Connector Fig. 35 — Fluid-SideTemperature Sensors T1 and T2Fig. 36 — Thermistor Connections to PROGRAMMING Mode Table 37 - Fault Codes •P50: FAULT HISTORY — Last 8 faults•P51: SOFTWARE version PARAMETERS Table 39 — Replacement Modules PRE-START-UP MAINTENANCEMinimum Loop Volume System CheckOperating Limitations OPERATION SEQUENCE Table 41 — Temperature Limits forStandard 30RA Units CIRCADIO Circuit A Discrete Inputs/Outputs APPENDIX ASCN Tables A_UNIT General Unit Parameters CIRCA_AN Circuit A Analog ParametersCIRCBDIO Circuit B Discrete Inputs/Outputs CIRCB_AN Circuit B Analog ParametersOPTIONS Unit Parameters DUALCHIL Dual Chiller Configuration Settings ALARMDEF Alarm Definition TableDISPLAY Marquee Display SETUP BRODEFS Broadcast POC Definition TableOPTIONS1 Options 1 Configuration OPTIONS2 Options 2 ConfigurationSCHEDOVR Timed Override Setup RESETCON Temperature Reset and Demand LimitSETPOINT ALARMS: Maintenance Display UNITMAINTENANCE CURRMODS: Maintenance Display DUALCHIL: Maintenance DisplayLEARNFNS Maintenance Display LOADFACT: Maintenance DisplayPM-COIL:Maintenance Display PM-PUMP:Maintenance DisplayPM-STRN Maintenance Display RUNTEST: Maintenance Display STRTHOUR Maintenance Display TESTMODE: Maintenance DisplayVERSIONS: Maintenance Display WSMDEFME: Maintenance Display FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMP APPENDIX BAND MANUAL STARTERS AND MANUAL STARTERS cont FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMPAPPENDIX C DataPort, DataLink, BAClink Object DefinitionOPTIONS SETPOINTII. Preliminary Equipment Check START-UPCHECKLIST FOR 30RA LIQUID CHILLERRemove and use for Job File I.Project Information Design InformationIII. Unit Start-Up Start and Operate Machine. Complete the FollowingCL-3 Record Software Versions MODE — RUN STATUS COMMENTSCL-4 UNIT Configuration Settings OPTIONS1 Options ConfigurationIII.Unit Start-Upcont III.Unit Start-Upcont OPTIONS2 Options ConfigurationRSET Reset Configuration Settings CL-6SETPOINT SLCT Setpoint and Ramp Load ConfigurationIII.Unit Start-Upcont CL-7Service Test Mode and Sub-ModeDirectory III.Unit Start-Upcont