Sterling 30RA010-055 manual RUNTEST: Maintenance Display

Page 86

RUNTEST: Maintenance Display

DESCRIPTION

VALUE

UNITS

POINT NAME

Percent Total Capacity

nnn

%

CAPA_T

Percent Available Cap.

nnn

%

CAPA_A

Discharge Pressure

nnn.n

psig

DP_A

Suction Pressure

nnn.n

psig

SP_A

Calculated HP Setpoint A

nnn.n

°F

HSP_A

Saturated Condensing Tmp

nnn.n

°F

TMP_SCTA

Saturated Suction Temp

nnn.n

°F

TMP_SSTA

Compr Return Gas Temp

nnn.n

°F

TMP_RGTA

Suction Superheat Temp

nnn.n

^F

SH_A

Compressor A1 Relay

On/Off

 

K_A1_RLY

Compressor A2 Relay

On/Off

 

K_A2_RLY

Minimum Load Valve Relay

On/Off

 

MLV_RLY

Compressor A1 Feedback

On/Off

 

K_A1_FBK

Compressor A2 Feedback

On/Off

 

K_A2_FBK

Percent Total Capacity

nnn

%

CAPB_T

Percent Available Cap.

nnn

%

CAPB_A

Discharge Pressure

nnn.n

psig

DP_B

Suction Pressure

nnn.n

psig

SP_B

Calculated HP Setpoint B

nnn.n

°F

HSP_B

Saturated Condensing Tmp

nnn.n

°F

TMP_SCTB

Saturated Suction Temp

nnn.n

°F

TMP_SSTB

Compr Return Gas Temp

nnn.n

°F

TMP_RGTB

Suction Superheat Temp

nnn.n

^F

SH_B

Compressor B1 Relay

On/Off

 

K_B1_RLY

Compressor B2 Relay

On/Off

 

K_B2_RLY

Minimum Load Valve Relay

On/Off

 

MLV_RLY

 

 

 

 

Compressor B1 Feedback

On/Off

 

K_B1_FBK

Compressor B2 Feedback

On/Off

 

K_B2_FBK

Fan 1 Relay

On/Off

 

FAN_1

Fan 2 Relay

On/Off

 

FAN_2

 

 

 

 

Outside Air Temperature

nnn.n

°F

OAT

Space Temperature

nnn.n

°F

SPT

Cooler Pump Relay 1

On/Off

 

COOLPMP1

Cooler Pump Relay 2

On/Off

 

COOLPMP2

Cooler Pump 1 Interlock

Open/Closed

 

PMP1_FBK

Cooler Pump 2 Interlock

Open/Closed

 

PMP2_FBK

Cooler Entering Fluid

nnn.n

°F

COOL_EWT

Cooler Leaving Fluid

nnn.n

°F

COOL_LWT

Compressor A1 Size

nnn

tons

SIZE_A1

Compressor A2 Size

nnn

tons

SIZE_A2

Compressor B1 Size

nnn

tons

SIZE_B1

Compressor B2 Size

nnn

tons

SIZE_B2

Cooler Flow Switch

On/Off

 

COOLFLOW

86

Image 86
Contents SAFETY CONSIDERATIONS CONTENTS GENERALSterlco Comfort Network SCN Interface — MAJOR SYSTEM COMPONENTSControl Module Communication Table 1 — Unit SizesTable 2 — Thermistor Designations Table 3 — Status SwitchesTable 5 - SCN Communication Bus Wiring Table 4 - Output RelaysLEGEND FOR FIG. Page Page Fig. 3 — Wiring Schematic 30RA010-018 30RA010-018AQUA SNAPSEE NOTE SEE NOTE AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICFig. 3 - Wiring Schematic 30RA010-018cont Fig. 4 - Wiring Schematic 30RA022-030 30RA022-030AQUA SNAPFig. 4 - Wiring Schematic 30RA022-030cont AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICFig. 5 — Wiring Schematic 30RA032-040 30RA032-040AQUA SNAPFig. 5 — Wiring Schematic 30RA032-040cont AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICFig. 6 — Wiring Schematic 30RA042-055 30RA042-055AQUA SNAPFig. 6 — Wiring Schematic 30RA042-055cont AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICREMOTE CONTACT SW1 OFF ENABLE OFF SW2 ON Fig. 7 — Main Base BoardESCAPEENTER MODEFig. 9 — Typical Space Temperature Sensor Wiring Fig. 11 - Energy Management Module CEPL130351100/100 Fig. 12 — Deadband Multiplier Fig. 14 — 30RA Condenser Fan Sequence Fig. 13 — Operating Envelope forR-22Maneurop Compressor Cooling Set Point Select Table 8 — Control Methods and Cooling Set Points Service Test See Table 11 — Both main powerand control circuit power must be on Fig. 16 — Scrolling Marquee DisplayOptional Factory-InstalledHydronic Package — •Cooler Pump Control CPC Configuration, OPT1 ON Fig. 17 — Dual Chiller Thermistor Location Table 9 — Marquee Display Menu StructureTable 10 — Run Status Mode and Sub-ModeDirectory SUB-MODE Table 12 - Temperature Mode and Sub-ModeDirectory Table 15 — Inputs Mode and Sub-ModeDirectory Table 13 — Pressure Mode and Sub-ModeDirectoryTable 14 — Set Point and Sub-ModeDirectory KEYPAD Table 16 — Outputs Mode and Sub-ModeDirectorySUB-MODE DISPLAYITEM SUB-MODEKEYPAD DISPLAYITEM SUB-MODEKEYPAD DISPLAYTable 18 — Time Clock Mode and Sub-ModeDirectory PER.3 SUB-MODE Table 20 — Alarms Mode and Sub-ModeDirectory Table 19 — Operating Mode and Sub-ModeDirectoryKEYPAD ENTRY SUB-MODEITEM DISPLAYRSET DISP Table 23 — Operating Modes Table 24 — Example of Reading and Clearing Alarms Table 25A — 4-20mA ResetTable 26B — Configuring Return Temperature Reset Fig. 19 — Outdoor-AirTemperature Reset Fig. 18 — Standard Chilled FluidTemperature Control — No Reset Fig. 20 — Space Temperature ResetFig. 21A — 4- to 20-mADemand Limiting Fig. 21B — Cooling Set Point 4 to 20 mATROUBLESHOOTING Table 27 — Configuring Demand Limitand fluid tubing Table 28 — TroubleshootingRecommended that system be filled with an appro Fig. 22 — Component Arrangement — 30RA010-030 FU — Fuse GND — GroundFig. 23 — Component Arrangement — 30RA032-040 FU — Fuse GND — GroundFig. 24 — Component Arrangement — 30RA042-055 FU — Fuse GND — GroundNOTES LEGEND Table 29 — Alarm and Alert Codes Table 29 - Alarm and Alert Codes cont Table 29 — Alarm and Alert Codes cont ALARMTable 29 — Alarm and Alert Codes cont ALARMTable 29 — Alarm and Alert Codes cont ALARMTable 30 - Unit Torque Specification SERVICECompressor Replacement Refer to Fig Electronic ComponentsFig. 29 — Compressor Location — 30RA010-030 Fig. 28 — Compressor WiringFig. 27 — Typical Compressor Mounting — All Sizes Fig. 30 — Compressor Location — 30RA032-055Condenser Section and Coils Table 31 - Oil ChargeFig. 32 — Condenser-FanMounting Fig. 31 — 30RA Access PanelsCheck Refrigerant Feed Components Fig. 33 — Condenser-FanPosition Standard FanCompressor and Unit Protective Devices Table 32 — Factory Settings, High-PressureSwitch Fixed Check Unit SafetiesCOOLER FREEZE-UPPROTECTION TEMP TEMP For Thermistor T10 For Thermistor T10 Fig. 36 — Thermistor Connections to Main Base Board, J8 ConnectorFig. 35 — Fluid-SideTemperature Sensors T1 and T2 PROGRAMMING Mode •P51: SOFTWARE version Table 37 - Fault Codes•P50: FAULT HISTORY — Last 8 faults PARAMETERS Table 39 — Replacement Modules PRE-START-UP MAINTENANCEMinimum Loop Volume System CheckOperating Limitations Standard 30RA Units OPERATION SEQUENCETable 41 — Temperature Limits for CIRCADIO Circuit A Discrete Inputs/Outputs APPENDIX ASCN Tables A_UNIT General Unit Parameters CIRCA_AN Circuit A Analog ParametersOPTIONS Unit Parameters CIRCBDIO Circuit B Discrete Inputs/OutputsCIRCB_AN Circuit B Analog Parameters DUALCHIL Dual Chiller Configuration Settings ALARMDEF Alarm Definition TableDISPLAY Marquee Display SETUP BRODEFS Broadcast POC Definition TableOPTIONS1 Options 1 Configuration OPTIONS2 Options 2 ConfigurationSETPOINT SCHEDOVR Timed Override SetupRESETCON Temperature Reset and Demand Limit MAINTENANCE ALARMS: Maintenance DisplayUNIT CURRMODS: Maintenance Display DUALCHIL: Maintenance DisplayLEARNFNS Maintenance Display LOADFACT: Maintenance DisplayPM-STRN Maintenance Display PM-COIL:Maintenance DisplayPM-PUMP:Maintenance Display RUNTEST: Maintenance Display VERSIONS: Maintenance Display STRTHOUR Maintenance DisplayTESTMODE: Maintenance Display WSMDEFME: Maintenance Display AND MANUAL STARTERS FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMPAPPENDIX B AND MANUAL STARTERS cont FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMPAPPENDIX C DataPort, DataLink, BAClink Object DefinitionOPTIONS SETPOINTII. Preliminary Equipment Check START-UPCHECKLIST FOR 30RA LIQUID CHILLERRemove and use for Job File I.Project Information Design InformationIII. Unit Start-Up Start and Operate Machine. Complete the FollowingCL-3 CL-4 Record Software Versions MODE — RUN STATUSCOMMENTS III.Unit Start-Upcont UNIT Configuration SettingsOPTIONS1 Options Configuration III.Unit Start-Upcont OPTIONS2 Options ConfigurationRSET Reset Configuration Settings CL-6SETPOINT SLCT Setpoint and Ramp Load ConfigurationIII.Unit Start-Upcont CL-7Service Test Mode and Sub-ModeDirectory III.Unit Start-Upcont