Sterling 30RA010-055 manual Condenser Section and Coils, Oil Charge

Page 60
Table 31 — Oil Charge

Check Oil Charge — Compressors are factory charged with oil as shown in Table 31.

Table 31 — Oil Charge

COMPRESSOR

AMOUNT

pints (liters)

 

SM110

5.7

(2.7)

SM115, SM125

6.7

(3.2)

SM160

7.0

(3.3)

SM185

11.6

(5.5)

If oil is visible in the compressor sight glass, check unit for operating readiness as described in Pre-Start-Up, System Check section (page 74), then start the unit. Observe oil level and add oil if required, to bring oil level in compressor crankcase up to between 1/4 and 3/4 of sight glass during steady operation.

To Add Oil:

1.Check the oil level with all compressors in the circuit run- ning in a stabilized condition or immediately after com-

pressor shutdown. The oil level should be at 1/3 of the oil sight glass immediately after shutdown.

2.Using a suitable pump, add oil while compressor(s) are running through the low side ¼ in. Schraeder fitting on the compressor. For SM110 models, this fitting is directly above the suction line connection. For all other compres- sor models, this fitting is near the oil equalization line fit- ting at the same height as the suction line connection.

3.Run all compressors on the circuit for at least 15 minutes and check the oil level.

Use only Sterling-approved compressor oil:

Totaline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PP680002 Penreco . . . . . . . . . . . . . . . . . . . . . . . . . . . .Sontex 160 LT-A

Do not reuse drained oil, and do not use any oil that has been exposed to the atmosphere.

Condenser Section and Coils

COIL CLEANING — For standard aluminum, copper and pre-coated aluminum fin coils, clean the coils with a vacuum cleaner, fresh water, compressed air, or a bristle brush (not wire). Units installed in corrosive environments should have coil cleaning as part of a planned maintenance schedule. In this type of application, all accumulations of dirt should be cleaned off the coil. When condenser cleaning is complete, enter “Yes” for coil cleaning maintenance done (CL.MN) value under Run Status.

Do not use high-pressure water or air to clean coils — fin damage may result.

CLEANING E-COATED COILS — Follow the outlined pro- cedure below for proper care, cleaning and maintenance of E-coated aluminum or copper fin coils:

Coil Maintenance and Cleaning Recommendations — Rou- tine cleaning of coil surfaces is essential to maintain proper operation of the unit. Elimination of contamination and removal of harmful residues will greatly increase the life of the coil and extend the life of the unit.

Remove Surface Loaded Fibers — Surface loaded fibers or dirt should be removed with a vacuum cleaner. If a vacuum cleaner is not available, a soft brush may be used. In either case, the tool should be applied in the direction of the fins. Coil

surfaces can be easily damaged (fin edges bent over) if the tool is applied across the fins.

NOTE: Use of a water stream, such as a garden hose, against a surface loaded coil will drive the fibers and dirt into the coil. This will make cleaning efforts more difficult. Surface loaded fibers must be completely removed prior to using low velocity clean water rinse.

Periodic Clean Water Rinse — A periodic clean water rinse is very beneficial for coils that are applied in coastal or industrial environments. However, it is very important that the water rinse is made with very low velocity water stream to avoid damaging the fin edges. Monthly cleaning as described below is recommended.

Routine Cleaning of Coil Surfaces — Monthly cleaning with Environmentally Sound Coil Cleaner is essential to extend the life of coils. It is recommended that all coils, including stan- dard aluminum, pre-coated, copper/copper or E-coated coils are cleaned with the Environmentally Sound Coil Cleaner as described below. Coil cleaning should be part of the units regu- larly scheduled maintenance procedures to ensure long life of the coil. Failure to clean the coils may result in reduced dura- bility in the environment.

Environmentally Sound Coil Cleaner is non-flammable, hypo allergenic, non-bacterial, USDA accepted biodegradable and 100% ecologically safe agent that will not harm the coil or surrounding components such as electrical wiring, painted metal surfaces or insulation. Use of non-recommended coil cleaners is strongly discouraged since coil and unit durability could be affected.

Environmentally Sound Coil Cleaner Application Equipment

21/2 Gallon Garden Sprayer

Water Rinse with Low Velocity Spray Nozzle

Environmentally Sound Coil Cleaner Application Instructions

Although Environmentally Sound Coil Cleaner is harm- less to humans, animals, and marine life, proper eye pro- tection such as safety glasses is recommended during mixing and application.

Remove all surface loaded fibers and dirt with a vacuum cleaner as described above.

Thoroughly wet finned surfaces with clean water and a low velocity garden hose being careful not to bend fins.

Mix Environmentally Sound Coil Cleaner in a 21/2 gallon garden sprayer according to the instructions included with the Enzyme Cleaner. The optimum solution tem- perature is 100 F.

NOTE: DO NOT USE water in excess of 130 F as the enzy- matic activity will be destroyed.

Thoroughly apply Environmentally Sound Coil Cleaner solution to all coil surfaces including finned area, tube sheets and coil headers.

Hold garden sprayer nozzle close to finned areas and apply cleaner with a vertical, up-and-down motion. Avoid spraying in horizontal pattern to minimize poten- tial for fin damage.

Ensure cleaner thoroughly penetrates deep into finned areas.

Interior and exterior finned areas must be thoroughly cleaned.

Finned surfaces should remain wet with cleaning solu- tion for 10 minutes.

Ensure surfaces are not allowed to dry before rinsing. Reapply cleaner as needed to ensure 10-minute satura- tion is achieved.

60

Image 60
Contents SAFETY CONSIDERATIONS CONTENTS GENERALMAJOR SYSTEM COMPONENTS Control Module CommunicationSterlco Comfort Network SCN Interface — Table 1 — Unit SizesTable 3 — Status Switches Table 5 - SCN Communication Bus WiringTable 2 — Thermistor Designations Table 4 - Output RelaysLEGEND FOR FIG. Page Page Fig. 3 — Wiring Schematic 30RA010-018 30RA010-018AQUA SNAPAQUA-SNAPLOW VOLTAGE CONTROL SCHEMATIC Fig. 3 - Wiring Schematic 30RA010-018contSEE NOTE SEE NOTE Fig. 4 - Wiring Schematic 30RA022-030 30RA022-030AQUA SNAPFig. 4 - Wiring Schematic 30RA022-030cont AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICFig. 5 — Wiring Schematic 30RA032-040 30RA032-040AQUA SNAPFig. 5 — Wiring Schematic 30RA032-040cont AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICFig. 6 — Wiring Schematic 30RA042-055 30RA042-055AQUA SNAPFig. 6 — Wiring Schematic 30RA042-055cont AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICFig. 7 — Main Base Board ESCAPEENTERREMOTE CONTACT SW1 OFF ENABLE OFF SW2 ON MODEFig. 9 — Typical Space Temperature Sensor Wiring Fig. 11 - Energy Management Module CEPL130351100/100 Fig. 12 — Deadband Multiplier Fig. 13 — Operating Envelope for R-22Maneurop CompressorFig. 14 — 30RA Condenser Fan Sequence Cooling Set Point Select Service Test See Table 11 — Both main power and control circuit power must be onTable 8 — Control Methods and Cooling Set Points Fig. 16 — Scrolling Marquee DisplayOptional Factory-InstalledHydronic Package — •Cooler Pump Control CPC Configuration, OPT1 ON Fig. 17 — Dual Chiller Thermistor Location Table 9 — Marquee Display Menu StructureTable 10 — Run Status Mode and Sub-ModeDirectory SUB-MODE Table 12 - Temperature Mode and Sub-ModeDirectory Table 13 — Pressure Mode and Sub-ModeDirectory Table 14 — Set Point and Sub-ModeDirectoryTable 15 — Inputs Mode and Sub-ModeDirectory Table 16 — Outputs Mode and Sub-ModeDirectory SUB-MODEKEYPAD DISPLAYSUB-MODE KEYPADITEM DISPLAYSUB-MODE KEYPADITEM DISPLAYTable 18 — Time Clock Mode and Sub-ModeDirectory PER.3 SUB-MODE Table 20 — Alarms Mode and Sub-ModeDirectory Table 19 — Operating Mode and Sub-ModeDirectorySUB-MODE ITEMKEYPAD ENTRY DISPLAYRSET DISP Table 23 — Operating Modes Table 24 — Example of Reading and Clearing Alarms Table 25A — 4-20mA ResetTable 26B — Configuring Return Temperature Reset Fig. 18 — Standard Chilled Fluid Temperature Control — No ResetFig. 19 — Outdoor-AirTemperature Reset Fig. 20 — Space Temperature ResetFig. 21A — 4- to 20-mADemand Limiting Fig. 21B — Cooling Set Point 4 to 20 mATROUBLESHOOTING Table 27 — Configuring Demand LimitTable 28 — Troubleshooting Recommended that system be filled with an approand fluid tubing Fig. 22 — Component Arrangement — 30RA010-030 FU — Fuse GND — GroundFig. 23 — Component Arrangement — 30RA032-040 FU — Fuse GND — GroundFig. 24 — Component Arrangement — 30RA042-055 FU — Fuse GND — GroundNOTES LEGEND Table 29 — Alarm and Alert Codes Table 29 - Alarm and Alert Codes cont Table 29 — Alarm and Alert Codes cont ALARMTable 29 — Alarm and Alert Codes cont ALARMTable 29 — Alarm and Alert Codes cont ALARMSERVICE Compressor Replacement Refer to FigTable 30 - Unit Torque Specification Electronic ComponentsFig. 28 — Compressor Wiring Fig. 27 — Typical Compressor Mounting — All SizesFig. 29 — Compressor Location — 30RA010-030 Fig. 30 — Compressor Location — 30RA032-055Condenser Section and Coils Table 31 - Oil ChargeFig. 31 — 30RA Access Panels Check Refrigerant Feed ComponentsFig. 32 — Condenser-FanMounting Fig. 33 — Condenser-FanPosition Standard FanTable 32 — Factory Settings, High-Pressure Switch FixedCompressor and Unit Protective Devices Check Unit SafetiesCOOLER FREEZE-UPPROTECTION TEMP TEMP For Thermistor T10 For Thermistor T10 Main Base Board, J8 Connector Fig. 35 — Fluid-SideTemperature Sensors T1 and T2Fig. 36 — Thermistor Connections to PROGRAMMING Mode Table 37 - Fault Codes •P50: FAULT HISTORY — Last 8 faults•P51: SOFTWARE version PARAMETERS Table 39 — Replacement Modules MAINTENANCE Minimum Loop VolumePRE-START-UP System CheckOperating Limitations OPERATION SEQUENCE Table 41 — Temperature Limits forStandard 30RA Units APPENDIX A SCN Tables A_UNIT General Unit ParametersCIRCADIO Circuit A Discrete Inputs/Outputs CIRCA_AN Circuit A Analog ParametersCIRCBDIO Circuit B Discrete Inputs/Outputs CIRCB_AN Circuit B Analog ParametersOPTIONS Unit Parameters ALARMDEF Alarm Definition Table DISPLAY Marquee Display SETUPDUALCHIL Dual Chiller Configuration Settings BRODEFS Broadcast POC Definition TableOPTIONS1 Options 1 Configuration OPTIONS2 Options 2 ConfigurationSCHEDOVR Timed Override Setup RESETCON Temperature Reset and Demand LimitSETPOINT ALARMS: Maintenance Display UNITMAINTENANCE CURRMODS: Maintenance Display DUALCHIL: Maintenance DisplayLEARNFNS Maintenance Display LOADFACT: Maintenance DisplayPM-COIL:Maintenance Display PM-PUMP:Maintenance DisplayPM-STRN Maintenance Display RUNTEST: Maintenance Display STRTHOUR Maintenance Display TESTMODE: Maintenance DisplayVERSIONS: Maintenance Display WSMDEFME: Maintenance Display FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMP APPENDIX BAND MANUAL STARTERS AND MANUAL STARTERS cont FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMPAPPENDIX C DataPort, DataLink, BAClink Object DefinitionOPTIONS SETPOINTSTART-UPCHECKLIST FOR 30RA LIQUID CHILLER Remove and use for Job File I.Project InformationII. Preliminary Equipment Check Design InformationIII. Unit Start-Up Start and Operate Machine. Complete the FollowingCL-3 Record Software Versions MODE — RUN STATUS COMMENTSCL-4 UNIT Configuration Settings OPTIONS1 Options ConfigurationIII.Unit Start-Upcont OPTIONS2 Options Configuration RSET Reset Configuration SettingsIII.Unit Start-Upcont CL-6SLCT Setpoint and Ramp Load Configuration III.Unit Start-UpcontSETPOINT CL-7Service Test Mode and Sub-ModeDirectory III.Unit Start-Upcont