
MAINTENANCE
Recommended Maintenance Schedule — The fol- lowing are only recommended guidelines. Jobsite conditions may dictate that maintenance schedule is performed more often than recommended.
Routine:
For machines with
•Check condenser coils for debris, clean as necessary with Sterling approved coil cleaner.
•Periodic clean water rinse, especially in coastal and industrial applications.
Every month:
•Check condenser coils for debris, clean as necessary with Sterling approved coil cleaner.
•Check moisture indicating sight glass for possible refrig- erant loss and presence of moisture.
Every 3 months (for all machines):
•Check refrigerant charge.
•Check all refrigerant joints and valves for refrigerant leaks, repair as necessary.
•Check chilled water flow switch operation.
•Check condenser coils for debris, clean as necessary with Sterling approved coil cleaner.
•Check all condenser fans for proper operation.
•Check compressor oil level.
•Check crankcase heater operation.
Every 12 months (for all machines):
•Check all electrical connections, tighten as necessary.
•Inspect all contactors and relays, replace as necessary.
•Check accuracy of thermistors, replace if greater than
± 2° F (1.2° C) variance from calibrated thermometer.
•Obtain and test an oil sample. Change oil only if necessary.
•Check to be sure that the proper concentration of anti- freeze is present in the chilled water loop, if applicable.
•Verify that the chilled water loop is properly treated.
•Check refrigerant filter driers for excessive pressure drop, replace as necessary.
•Check chilled water strainers, clean as necessary.
•Check cooler heater operation, if equipped.
•Check condition of condenser fan blades and that they are securely fastened to the motor shaft.
•Perform Service Test to confirm operation of all components.
•Check for excessive cooler approach (Leaving Chilled Water Temperature — Saturated Suction Temperature) which may indicate fouling. Clean cooler vessel if necessary.
PRE-START-UP
IMPORTANT: Before beginning
Do not attempt to start the chiller until following checks have been completed.
System Check
1.Check all auxiliary components, such as chilled fluid pumps,
2.Use the Scrolling Marquee display to adjust the Cooling Set Point.
3.Fill chilled fluid circuit with clean water (with recom- mended inhibitor added) or other
4.Check tightness of all electrical connections.
5.Oil should be visible in the compressor sightglass(es). See Fig. 39. An acceptable oil level in the compressors is from ¼ to ¾ of sight glass. Adjust the oil level as re- quired. See Check Oil Charge section on page 60 for Sterling approved oils.
6.Electrical power source must agree with unit nameplate.
7.All condenser fan and factory installed hydronic package pump motors are three phase. Check for proper rotation of condenser fans first BEFORE attempting to start pumps or compressors. To reverse rotation, interchange any two of the main incoming power leads.
8.Be sure system is fully charged with refrigerant (see Check Refrigerant Charge section on page 75).
9.If unit is a brine unit, check to ensure proper brine con- centration is used to prevent freezing.
10.Verify proper operation of cooler and hydronic package heaters (if installed). Heaters operate at the same voltage as the main incoming power supply and are single phase. Heater current is approximately .4 amps for 380, 400, 460 and 575 v units. Heater current is approximately .8 amps for 230 v units.
Table 40 — Minimum Cooler Flow Rates and
Minimum Loop Volume
UNIT SIZE | COOLER MINIMUM | MINIMUM COOLER | |||
| FLOW | LOOP VOLUME | |||
30RA |
| ||||
Gpm |
| L/s | Gal. | L | |
|
| ||||
010 | 12 |
| .76 | 40 | 151.2 |
015 | 16 |
| 1.01 | 55 | 207.9 |
018 | 19 |
| 1.20 | 48 | 181.4 |
022 | 26 |
| 1.64 | 65 | 245.7 |
025 | 29 |
| 1.83 | 71 | 268.3 |
030 | 33 |
| 2.08 | 82 | 309.3 |
035 | 42 |
| 2.65 | 102 | 393.1 |
040 | 45 |
| 2.80 | 113 | 449.8 |
042 | 48 |
| 3.02 | 119 | 427.1 |
045 | 52 |
| 3.28 | 129 | 487.6 |
050 | 57 |
| 3.59 | 142 | 536.6 |
055 | 65 |
| 4.10 | 163 | 616.1 |
START-UP AND OPERATION
NOTE: Refer to
Actual
1.Be sure all service valves are open.
2.Using the Scrolling Marquee display, set
3.Start chilled fluid pump (if not configured for cooler pump control).
4.Turn ENABLE/OFF/REMOTE CONTACT switch to ENABLE position.
74