Sterling 30RA010-055 manual Options, Setpoint

Page 92
OPTIONS

DataPort, DataLink, BAClink Object Definition (cont)

SCN TABLE

DESCRIPTION

STATUS

UNITS

POINT

DataPort

DataLink

BAClink

NAME

 

 

 

 

 

 

 

 

FANS

 

 

 

 

 

 

 

Fan 1 Relay

Off/On

 

FAN_1

RO

RO

RO

 

Fan 2 Relay

Off/On

 

FAN_2

RO

RO

RO

 

Cooler/Pump Heater

Off/On

 

COOL_HTR

RO

RO

NA

 

UNIT ANALOG VALUES

 

 

 

 

 

 

 

Cooler Entering Fluid

snnn.n

°F (°C)

COOL_EWT

RO

RO

RO

 

Cooler Leaving Fluid

snnn.n

°F (°C)

COOL_LWT

RO

RO

RO

 

Lead/Lag Fluid

snnn.n

°F (°C)

DUAL_LWT

RO

RO

NA

 

TEMPERTURE RESET

 

 

 

 

 

 

 

4-20 mA Reset Signal

nn.n

ma

RST_MA

RO

RO

RO

OPTIONS

Outside Air Temperature

snnn.n

°F (°C)

OAT

RO

RW

NA

Space Temperature

snnn.n

°F (°C)

SPT

RO

RW

NA

 

 

DEMAND LIMIT

 

 

 

 

 

 

 

4-20 mA Demand Signal

nn.n

ma

LMT_MA

RO

RO

RO

 

Demand Limit Switch 1

Off/On

 

DMD_SW1

RO

RO

NA

 

Demand Limit Switch 2

Off/On

 

DMD_SW2

RO

RO

NA

 

SCN Loadshed Signal

0, 1, 2

 

DL_STAT

RO

RO

RO

 

MISCELLANEOUS

 

 

 

 

 

 

 

Heat Request

Off/On

 

HEAT_REQ

RO

RO

NA

 

Dual Setpoint Switch

Off/On

 

DUAL_IN

RO

RO

NA

 

Cooler LWT Setpoint

snnn.n

°F (°C)

LWT_SP

RO

RO

NA

 

Ice Done

Off/On

 

ICE_DONE

RO

RO

NA

 

COOLING

 

 

 

 

 

 

 

Cooling Setpoint 1

–20 to 70 (–28.8 to 21.1)

°F (°C)

CSP1

NA

RW

RW

 

Cooling Setpoint 2

–20 to 70 (–28.8 to 21.1)

°F (°C)

CSP2

NA

RW

NA

SETPOINT

Ice Setpoint

–20 to 32 (–28.8 to 0.0)

°F (°C)

CSP3

NA

RW

NA

RAMP LOADING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling Ramp Loading

0.2 to 2.0 (0.1 to 1.1)

dF (dC)

CRAMP

NA

RW

NA

 

Brine Freeze Point

–20 to 34 (–28.8 to 1.1)

°F (°C)

BRN_FRZ

NA

RW

NA

 

Timed Override Hours

0

Hours

OVR-EXT

NA

RW

RW

 

Period 1 DOW (MTWTFSSH)

00000000

 

DOW1

NA

RW

RW

 

Occupied Time

00:00

 

OCCTOD1

NA

RW

RW

 

Unoccupied Time

00:00

 

UNOCTOD1

NA

RW

RW

 

Period 2 DOW (MTWTFSSH)

00000000

 

DOW2

NA

RW

RW

 

Occupied Time

00:00

 

OCCTOD2

NA

RW

RW

 

Unoccupied Time

00:00

 

UNOCTOD2

NA

RW

RW

 

Period 3 DOW (MTWTFSSH)

00000000

 

DOW3

NA

RW

RW

 

Occupied Time

00:00

 

OCCTOD3

NA

RW

RW

 

Unoccupied Time

00:00

 

UNOCTOD3

NA

RW

RW

 

Period 4 DOW (MTWTFSSH)

00000000

 

DOW4

NA

RW

RW

OCCPC01S

Occupied Time

00:00

 

OCCTOD4

NA

RW

RW

Unoccupied Time

00:00

 

UNOCTOD4

NA

RW

RW

 

Period 5 DOW (MTWTFSSH)

00000000

 

DOW5

NA

RW

RW

 

Occupied Time

00:00

 

OCCTOD5

NA

RW

RW

 

Unoccupied Time

00:00

 

UNOCTOD5

NA

RW

RW

 

Period 6 DOW (MTWTFSSH)

00000000

 

DOW6

NA

RW

RW

 

Occupied Time

00:00

 

OCCTOD6

NA

RW

RW

 

Unoccupied Time

00:00

 

UNOCTOD6

NA

RW

RW

 

Period 7 DOW (MTWTFSSH)

00000000

 

DOW7

NA

RW

RW

 

Occupied Time

00:00

 

OCCTOD7

NA

RW

RW

 

Unoccupied Time

00:00

 

UNOCTOD7

NA

RW

RW

 

Period 8 DOW (MTWTFSSH)

00000000

 

DOW8

NA

RW

RW

 

Occupied Time

00:00

 

OCCTOD8

NA

RW

RW

 

Unoccupied Time

00:00

 

UNOCTOD8

NA

RW

RW

LEGEND

NA — Not Available

RO — Read Only

RW — Read/Write

NOTE: In order to write to any point with DataLink or BAClink con- trols, the machine must be configured for SCN control. CTRL Control Method (Configuration mode, sub-mode OPT2) must be set to 3 = SCN Control.

Copyright 2003 Sterling

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book

2

PC 903

Catalog No. 533-00047

Printed in U.S.A.

Form 30RA-2T

Pg 92

1-03

Replaces: 30RA-1T

Tab

5c

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Image 92
Contents SAFETY CONSIDERATIONS CONTENTS GENERALMAJOR SYSTEM COMPONENTS Control Module CommunicationSterlco Comfort Network SCN Interface — Table 1 — Unit SizesTable 3 — Status Switches Table 5 - SCN Communication Bus WiringTable 2 — Thermistor Designations Table 4 - Output RelaysLEGEND FOR FIG. Page Page Fig. 3 — Wiring Schematic 30RA010-018 30RA010-018AQUA SNAPSEE NOTE SEE NOTE AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICFig. 3 - Wiring Schematic 30RA010-018cont Fig. 4 - Wiring Schematic 30RA022-030 30RA022-030AQUA SNAPFig. 4 - Wiring Schematic 30RA022-030cont AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICFig. 5 — Wiring Schematic 30RA032-040 30RA032-040AQUA SNAPFig. 5 — Wiring Schematic 30RA032-040cont AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICFig. 6 — Wiring Schematic 30RA042-055 30RA042-055AQUA SNAPFig. 6 — Wiring Schematic 30RA042-055cont AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICFig. 7 — Main Base Board ESCAPEENTERREMOTE CONTACT SW1 OFF ENABLE OFF SW2 ON MODEFig. 9 — Typical Space Temperature Sensor Wiring Fig. 11 - Energy Management Module CEPL130351100/100 Fig. 12 — Deadband Multiplier Fig. 14 — 30RA Condenser Fan Sequence Fig. 13 — Operating Envelope forR-22Maneurop Compressor Cooling Set Point Select Service Test See Table 11 — Both main power and control circuit power must be onTable 8 — Control Methods and Cooling Set Points Fig. 16 — Scrolling Marquee DisplayOptional Factory-InstalledHydronic Package — •Cooler Pump Control CPC Configuration, OPT1 ON Fig. 17 — Dual Chiller Thermistor Location Table 9 — Marquee Display Menu StructureTable 10 — Run Status Mode and Sub-ModeDirectory SUB-MODE Table 12 - Temperature Mode and Sub-ModeDirectory Table 15 — Inputs Mode and Sub-ModeDirectory Table 13 — Pressure Mode and Sub-ModeDirectoryTable 14 — Set Point and Sub-ModeDirectory Table 16 — Outputs Mode and Sub-ModeDirectory SUB-MODEKEYPAD DISPLAYSUB-MODE KEYPADITEM DISPLAYSUB-MODE KEYPADITEM DISPLAYTable 18 — Time Clock Mode and Sub-ModeDirectory PER.3 SUB-MODE Table 20 — Alarms Mode and Sub-ModeDirectory Table 19 — Operating Mode and Sub-ModeDirectorySUB-MODE ITEMKEYPAD ENTRY DISPLAYRSET DISP Table 23 — Operating Modes Table 24 — Example of Reading and Clearing Alarms Table 25A — 4-20mA ResetTable 26B — Configuring Return Temperature Reset Fig. 18 — Standard Chilled Fluid Temperature Control — No ResetFig. 19 — Outdoor-AirTemperature Reset Fig. 20 — Space Temperature ResetFig. 21A — 4- to 20-mADemand Limiting Fig. 21B — Cooling Set Point 4 to 20 mATROUBLESHOOTING Table 27 — Configuring Demand Limitand fluid tubing Table 28 — TroubleshootingRecommended that system be filled with an appro Fig. 22 — Component Arrangement — 30RA010-030 FU — Fuse GND — GroundFig. 23 — Component Arrangement — 30RA032-040 FU — Fuse GND — GroundFig. 24 — Component Arrangement — 30RA042-055 FU — Fuse GND — GroundNOTES LEGEND Table 29 — Alarm and Alert Codes Table 29 - Alarm and Alert Codes cont Table 29 — Alarm and Alert Codes cont ALARMTable 29 — Alarm and Alert Codes cont ALARMTable 29 — Alarm and Alert Codes cont ALARMSERVICE Compressor Replacement Refer to FigTable 30 - Unit Torque Specification Electronic ComponentsFig. 28 — Compressor Wiring Fig. 27 — Typical Compressor Mounting — All SizesFig. 29 — Compressor Location — 30RA010-030 Fig. 30 — Compressor Location — 30RA032-055Condenser Section and Coils Table 31 - Oil ChargeFig. 31 — 30RA Access Panels Check Refrigerant Feed ComponentsFig. 32 — Condenser-FanMounting Fig. 33 — Condenser-FanPosition Standard FanTable 32 — Factory Settings, High-Pressure Switch FixedCompressor and Unit Protective Devices Check Unit SafetiesCOOLER FREEZE-UPPROTECTION TEMP TEMP For Thermistor T10 For Thermistor T10 Fig. 36 — Thermistor Connections to Main Base Board, J8 ConnectorFig. 35 — Fluid-SideTemperature Sensors T1 and T2 PROGRAMMING Mode •P51: SOFTWARE version Table 37 - Fault Codes•P50: FAULT HISTORY — Last 8 faults PARAMETERS Table 39 — Replacement Modules MAINTENANCE Minimum Loop VolumePRE-START-UP System CheckOperating Limitations Standard 30RA Units OPERATION SEQUENCETable 41 — Temperature Limits for APPENDIX A SCN Tables A_UNIT General Unit ParametersCIRCADIO Circuit A Discrete Inputs/Outputs CIRCA_AN Circuit A Analog ParametersOPTIONS Unit Parameters CIRCBDIO Circuit B Discrete Inputs/OutputsCIRCB_AN Circuit B Analog Parameters ALARMDEF Alarm Definition Table DISPLAY Marquee Display SETUPDUALCHIL Dual Chiller Configuration Settings BRODEFS Broadcast POC Definition TableOPTIONS1 Options 1 Configuration OPTIONS2 Options 2 ConfigurationSETPOINT SCHEDOVR Timed Override SetupRESETCON Temperature Reset and Demand Limit MAINTENANCE ALARMS: Maintenance DisplayUNIT CURRMODS: Maintenance Display DUALCHIL: Maintenance DisplayLEARNFNS Maintenance Display LOADFACT: Maintenance DisplayPM-STRN Maintenance Display PM-COIL:Maintenance DisplayPM-PUMP:Maintenance Display RUNTEST: Maintenance Display VERSIONS: Maintenance Display STRTHOUR Maintenance DisplayTESTMODE: Maintenance Display WSMDEFME: Maintenance Display AND MANUAL STARTERS FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMPAPPENDIX B AND MANUAL STARTERS cont FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMPAPPENDIX C DataPort, DataLink, BAClink Object DefinitionOPTIONS SETPOINTSTART-UPCHECKLIST FOR 30RA LIQUID CHILLER Remove and use for Job File I.Project InformationII. Preliminary Equipment Check Design InformationIII. Unit Start-Up Start and Operate Machine. Complete the FollowingCL-3 CL-4 Record Software Versions MODE — RUN STATUSCOMMENTS III.Unit Start-Upcont UNIT Configuration SettingsOPTIONS1 Options Configuration OPTIONS2 Options Configuration RSET Reset Configuration SettingsIII.Unit Start-Upcont CL-6SLCT Setpoint and Ramp Load Configuration III.Unit Start-UpcontSETPOINT CL-7Service Test Mode and Sub-ModeDirectory III.Unit Start-Upcont