DataPort, DataLink, BAClink Object Definition (cont)
SCN TABLE | DESCRIPTION | STATUS | UNITS | POINT | DataPort | DataLink | BAClink | |
NAME | ||||||||
|
|
|
|
|
|
| ||
| FANS |
|
|
|
|
|
| |
| Fan 1 Relay | Off/On |
| FAN_1 | RO | RO | RO | |
| Fan 2 Relay | Off/On |
| FAN_2 | RO | RO | RO | |
| Cooler/Pump Heater | Off/On |
| COOL_HTR | RO | RO | NA | |
| UNIT ANALOG VALUES |
|
|
|
|
|
| |
| Cooler Entering Fluid | snnn.n | °F (°C) | COOL_EWT | RO | RO | RO | |
| Cooler Leaving Fluid | snnn.n | °F (°C) | COOL_LWT | RO | RO | RO | |
| Lead/Lag Fluid | snnn.n | °F (°C) | DUAL_LWT | RO | RO | NA | |
| TEMPERTURE RESET |
|
|
|
|
|
| |
| nn.n | ma | RST_MA | RO | RO | RO | ||
OPTIONS | Outside Air Temperature | snnn.n | °F (°C) | OAT | RO | RW | NA | |
Space Temperature | snnn.n | °F (°C) | SPT | RO | RW | NA | ||
| ||||||||
| DEMAND LIMIT |
|
|
|
|
|
| |
| nn.n | ma | LMT_MA | RO | RO | RO | ||
| Demand Limit Switch 1 | Off/On |
| DMD_SW1 | RO | RO | NA | |
| Demand Limit Switch 2 | Off/On |
| DMD_SW2 | RO | RO | NA | |
| SCN Loadshed Signal | 0, 1, 2 |
| DL_STAT | RO | RO | RO | |
| MISCELLANEOUS |
|
|
|
|
|
| |
| Heat Request | Off/On |
| HEAT_REQ | RO | RO | NA | |
| Dual Setpoint Switch | Off/On |
| DUAL_IN | RO | RO | NA | |
| Cooler LWT Setpoint | snnn.n | °F (°C) | LWT_SP | RO | RO | NA | |
| Ice Done | Off/On |
| ICE_DONE | RO | RO | NA | |
| COOLING |
|
|
|
|
|
| |
| Cooling Setpoint 1 | °F (°C) | CSP1 | NA | RW | RW | ||
| Cooling Setpoint 2 | °F (°C) | CSP2 | NA | RW | NA | ||
SETPOINT | Ice Setpoint | °F (°C) | CSP3 | NA | RW | NA | ||
RAMP LOADING |
|
|
|
|
|
| ||
|
|
|
|
|
|
| ||
| Cooling Ramp Loading | 0.2 to 2.0 (0.1 to 1.1) | dF (dC) | CRAMP | NA | RW | NA | |
| Brine Freeze Point | °F (°C) | BRN_FRZ | NA | RW | NA | ||
| Timed Override Hours | 0 | Hours | NA | RW | RW | ||
| Period 1 DOW (MTWTFSSH) | 00000000 |
| DOW1 | NA | RW | RW | |
| Occupied Time | 00:00 |
| OCCTOD1 | NA | RW | RW | |
| Unoccupied Time | 00:00 |
| UNOCTOD1 | NA | RW | RW | |
| Period 2 DOW (MTWTFSSH) | 00000000 |
| DOW2 | NA | RW | RW | |
| Occupied Time | 00:00 |
| OCCTOD2 | NA | RW | RW | |
| Unoccupied Time | 00:00 |
| UNOCTOD2 | NA | RW | RW | |
| Period 3 DOW (MTWTFSSH) | 00000000 |
| DOW3 | NA | RW | RW | |
| Occupied Time | 00:00 |
| OCCTOD3 | NA | RW | RW | |
| Unoccupied Time | 00:00 |
| UNOCTOD3 | NA | RW | RW | |
| Period 4 DOW (MTWTFSSH) | 00000000 |
| DOW4 | NA | RW | RW | |
OCCPC01S | Occupied Time | 00:00 |
| OCCTOD4 | NA | RW | RW | |
Unoccupied Time | 00:00 |
| UNOCTOD4 | NA | RW | RW | ||
| Period 5 DOW (MTWTFSSH) | 00000000 |
| DOW5 | NA | RW | RW | |
| Occupied Time | 00:00 |
| OCCTOD5 | NA | RW | RW | |
| Unoccupied Time | 00:00 |
| UNOCTOD5 | NA | RW | RW | |
| Period 6 DOW (MTWTFSSH) | 00000000 |
| DOW6 | NA | RW | RW | |
| Occupied Time | 00:00 |
| OCCTOD6 | NA | RW | RW | |
| Unoccupied Time | 00:00 |
| UNOCTOD6 | NA | RW | RW | |
| Period 7 DOW (MTWTFSSH) | 00000000 |
| DOW7 | NA | RW | RW | |
| Occupied Time | 00:00 |
| OCCTOD7 | NA | RW | RW | |
| Unoccupied Time | 00:00 |
| UNOCTOD7 | NA | RW | RW | |
| Period 8 DOW (MTWTFSSH) | 00000000 |
| DOW8 | NA | RW | RW | |
| Occupied Time | 00:00 |
| OCCTOD8 | NA | RW | RW | |
| Unoccupied Time | 00:00 |
| UNOCTOD8 | NA | RW | RW |
LEGEND
NA — Not Available
RO — Read Only
RW — Read/Write
NOTE: In order to write to any point with DataLink or BAClink con- trols, the machine must be configured for SCN control. CTRL Control Method (Configuration mode,