NOTES:

1.Factory wiring is in accordance with UL 1995 standards. Field modifications or additions must be in compliance with all applicable codes.

2.Wiring for main field supply must be rated 75 C minimum. Use copper for all units. Maximum incoming wire size for the terminal block is #2/0 AWG. Max- imum incoming wire size for 60 and 100 amp non-fused disconnect is #1 AWG. Maximum incoming wire size for 250 amp non-fused disconnect is 350 kcmil.

3.Terminals 9 and 10 of TB5 are for field external connections for remote on- off. The contacts must be rated for dry circuit application capable of handling a 24 vac load up to 50 mA.

4.Terminals 1 and 2 of TB5 are connected to the factory-installed chilled water flow switch (CWFS). To add chilled water pump interlock contacts, remove the orange harness wire from TB5-1 and wire contacts in series as shown. The contacts must be rated for dry circuit application capable of handling a 24 vac load up to 50 mA.

5.Terminals 11 and 13 of TB5 are for control of chilled water pump 1 (CWP1) starter. Terminals 13 and 15 of TB5 are for control of chilled water pump 2 (CWP2) starter. The maximum load allowed for the chilled water pump relay is 5 va sealed, 10 va inrush at 24 v. Field power supply is not required.

6.Terminals 12 and 13 of TB5 are for an alarm relay. The maximum load allowed for the alarm relay is 5 va sealed, 10 va inrush at 24 v. Field power supply is not required.

7.Make appropriate connections to TB6 as shown for energy management board options. The contacts for demand limit and ice done options must be rated for dry circuit application capable of handling a 24 vac load up to 50 mA.

8.Care should be taken when interfacing with other manufacturer’s control systems due to possible power supply differences: full wave bridge versus half wave rectification. The two different power supplies cannot be mixed. ComfortLink™ controls use half wave rectification. A signal isolation device should be utilized if a full wave bridge signal generating device is used.

51

LEGEND

AAlarm

CWPI — Chilled Water Pump Interlock

CWP — Chilled Water Pump

EMM — Energy Management

FIOP — Factory-Installed Option

NEC — National Electrical Code

SPT — Space Temperature

TB — Terminal Block

Field Power Wiring

Field Control Wiring

Factory-Installed Wiring

Fig. 25 — Control and Field Power Wiring Diagram — 30RA010-030

Image 51 Sterling 30RA010-055 manual Notes
Contents SAFETY CONSIDERATIONS GENERAL CONTENTSTable 1 — Unit Sizes MAJOR SYSTEM COMPONENTSControl Module Communication Sterlco Comfort Network SCN Interface —Table 4 - Output Relays Table 3 — Status SwitchesTable 5 - SCN Communication Bus Wiring Table 2 — Thermistor DesignationsLEGEND FOR FIG. Page Page 30RA010-018AQUA SNAP Fig. 3 — Wiring Schematic 30RA010-018AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATIC Fig. 3 - Wiring Schematic 30RA010-018contSEE NOTE SEE NOTE 30RA022-030AQUA SNAP Fig. 4 - Wiring Schematic 30RA022-030AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATIC Fig. 4 - Wiring Schematic 30RA022-030cont30RA032-040AQUA SNAP Fig. 5 — Wiring Schematic 30RA032-040AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATIC Fig. 5 — Wiring Schematic 30RA032-040cont30RA042-055AQUA SNAP Fig. 6 — Wiring Schematic 30RA042-055AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATIC Fig. 6 — Wiring Schematic 30RA042-055contMODE Fig. 7 — Main Base BoardESCAPEENTER REMOTE CONTACT SW1 OFF ENABLE OFF SW2 ONFig. 9 — Typical Space Temperature Sensor Wiring CEPL130351 Fig. 11 - Energy Management Module100/100 Fig. 12 — Deadband Multiplier Fig. 13 — Operating Envelope for R-22Maneurop CompressorFig. 14 — 30RA Condenser Fan Sequence Cooling Set Point Select Fig. 16 — Scrolling Marquee Display Service Test See Table 11 — Both main powerand control circuit power must be on Table 8 — Control Methods and Cooling Set PointsOptional Factory-InstalledHydronic Package — •Cooler Pump Control CPC Configuration, OPT1 ON Table 9 — Marquee Display Menu Structure Fig. 17 — Dual Chiller Thermistor LocationTable 10 — Run Status Mode and Sub-ModeDirectory SUB-MODE Table 12 - Temperature Mode and Sub-ModeDirectory Table 13 — Pressure Mode and Sub-ModeDirectory Table 14 — Set Point and Sub-ModeDirectoryTable 15 — Inputs Mode and Sub-ModeDirectory DISPLAY Table 16 — Outputs Mode and Sub-ModeDirectorySUB-MODE KEYPADDISPLAY SUB-MODEKEYPAD ITEMDISPLAY SUB-MODEKEYPAD ITEMTable 18 — Time Clock Mode and Sub-ModeDirectory PER.3 SUB-MODE Table 19 — Operating Mode and Sub-ModeDirectory Table 20 — Alarms Mode and Sub-ModeDirectoryDISPLAY SUB-MODEITEM KEYPAD ENTRYRSET DISP Table 23 — Operating Modes Table 25A — 4-20mA Reset Table 24 — Example of Reading and Clearing AlarmsTable 26B — Configuring Return Temperature Reset Fig. 20 — Space Temperature Reset Fig. 18 — Standard Chilled FluidTemperature Control — No Reset Fig. 19 — Outdoor-AirTemperature ResetFig. 21B — Cooling Set Point 4 to 20 mA Fig. 21A — 4- to 20-mADemand LimitingTable 27 — Configuring Demand Limit TROUBLESHOOTINGTable 28 — Troubleshooting Recommended that system be filled with an approand fluid tubing FU — Fuse GND — Ground Fig. 22 — Component Arrangement — 30RA010-030FU — Fuse GND — Ground Fig. 23 — Component Arrangement — 30RA032-040FU — Fuse GND — Ground Fig. 24 — Component Arrangement — 30RA042-055NOTES LEGEND Table 29 — Alarm and Alert Codes Table 29 - Alarm and Alert Codes cont ALARM Table 29 — Alarm and Alert Codes contALARM Table 29 — Alarm and Alert Codes contALARM Table 29 — Alarm and Alert Codes contElectronic Components SERVICECompressor Replacement Refer to Fig Table 30 - Unit Torque SpecificationFig. 30 — Compressor Location — 30RA032-055 Fig. 28 — Compressor WiringFig. 27 — Typical Compressor Mounting — All Sizes Fig. 29 — Compressor Location — 30RA010-030Table 31 - Oil Charge Condenser Section and CoilsFig. 33 — Condenser-FanPosition Standard Fan Fig. 31 — 30RA Access PanelsCheck Refrigerant Feed Components Fig. 32 — Condenser-FanMountingCheck Unit Safeties Table 32 — Factory Settings, High-PressureSwitch Fixed Compressor and Unit Protective DevicesCOOLER FREEZE-UPPROTECTION TEMP TEMP For Thermistor T10 For Thermistor T10 Main Base Board, J8 Connector Fig. 35 — Fluid-SideTemperature Sensors T1 and T2Fig. 36 — Thermistor Connections to PROGRAMMING Mode Table 37 - Fault Codes •P50: FAULT HISTORY — Last 8 faults•P51: SOFTWARE version PARAMETERS Table 39 — Replacement Modules System Check MAINTENANCEMinimum Loop Volume PRE-START-UPOperating Limitations OPERATION SEQUENCE Table 41 — Temperature Limits forStandard 30RA Units CIRCA_AN Circuit A Analog Parameters APPENDIX ASCN Tables A_UNIT General Unit Parameters CIRCADIO Circuit A Discrete Inputs/OutputsCIRCBDIO Circuit B Discrete Inputs/Outputs CIRCB_AN Circuit B Analog ParametersOPTIONS Unit Parameters BRODEFS Broadcast POC Definition Table ALARMDEF Alarm Definition TableDISPLAY Marquee Display SETUP DUALCHIL Dual Chiller Configuration SettingsOPTIONS2 Options 2 Configuration OPTIONS1 Options 1 ConfigurationSCHEDOVR Timed Override Setup RESETCON Temperature Reset and Demand LimitSETPOINT ALARMS: Maintenance Display UNITMAINTENANCE DUALCHIL: Maintenance Display CURRMODS: Maintenance DisplayLOADFACT: Maintenance Display LEARNFNS Maintenance DisplayPM-COIL:Maintenance Display PM-PUMP:Maintenance DisplayPM-STRN Maintenance Display RUNTEST: Maintenance Display STRTHOUR Maintenance Display TESTMODE: Maintenance DisplayVERSIONS: Maintenance Display WSMDEFME: Maintenance Display FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMP APPENDIX BAND MANUAL STARTERS FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMP AND MANUAL STARTERS contDataPort, DataLink, BAClink Object Definition APPENDIX CSETPOINT OPTIONSDesign Information START-UPCHECKLIST FOR 30RA LIQUID CHILLERRemove and use for Job File I.Project Information II. Preliminary Equipment CheckStart and Operate Machine. Complete the Following III. Unit Start-UpCL-3 Record Software Versions MODE — RUN STATUS COMMENTSCL-4 UNIT Configuration Settings OPTIONS1 Options ConfigurationIII.Unit Start-Upcont CL-6 OPTIONS2 Options ConfigurationRSET Reset Configuration Settings III.Unit Start-UpcontCL-7 SLCT Setpoint and Ramp Load ConfigurationIII.Unit Start-Upcont SETPOINTIII.Unit Start-Upcont Service Test Mode and Sub-ModeDirectory