Table 24 — Example of Reading and Clearing Alarms
KEYPAD | ITEM | ITEM EXPANSION | COMMENT | ||
ENTRY | |||||
|
|
|
| ||
CRNT | ENTER | AXXX or TXXX | CURRENTLY ACTIVE ALARMS | ACTIVE ALARMS (AXXX) OR | |
ALERTS (TXXX) DISPLAYED. | |||||
| |||||
|
|
|
| ||
CRNT | ESCAPE |
|
|
| |
|
| NO |
| Use to clear active alarms/alerts | |
RCRN | ENTER | NO |
| NO Flashes | |
| YES |
| Select YES | ||
|
|
| |||
| ENTER | NO |
| Alarms/alerts clear, YES changes to NO |
|
|
| Table 25A — |
|
| |
KEYPAD | ITEM | DISPLAY | ITEM |
| COMMENT | |
ENTRY | EXPANSION |
| ||||
|
|
|
|
| ||
RSET |
|
|
|
| 0 | = no reset |
|
|
|
| COOLING RESET | 1 | = 4 to 20 mA input |
| ENTER | CRST | 1 | 2 | = Outdoor air temp | |
|
| TYPE | ||||
|
|
|
| 3 | = Return Fluid | |
|
|
|
|
| ||
|
|
|
|
| 4 | = Space Temperature |
|
| CRT1 | 4.0 | NO COOL RESET | Default: 125 F (51.7 C) | |
|
| TEMP | Range: 0° to 125 F | |||
|
|
|
| |||
|
| CRT2 | 20.0 | FULL COOL | Default: 0° F | |
|
| RESET TEMP | Range: 0° to 125 F | |||
|
|
|
| |||
|
| DGRC | 5.0 F | DEGREES COOL | Default: 0° F (0° C) Reset at 20 mA | |
|
| (2.8 C) | RESET | Range: | ||
|
|
|
NOTE: The example above shows how to configure the chiller for
Table 25B — Menu Configuration of 4 to 20 mA Cooling Set Point Control
MODE | KEYPAD | KEYPAD | ITEM | DISPLAY | ITEM | COMMENT | |
(RED LED) | ENTRY |
| ENTRY |
|
| EXPANSION |
|
| ENTER | DISP |
|
|
|
|
|
|
| UNIT |
|
|
|
|
|
|
| OPT1 |
|
|
|
|
|
|
| OPT2 |
|
|
|
|
|
CONFIGURATION |
| RSET |
|
|
|
|
|
|
|
|
|
|
|
| |
|
| SLCT | ENTER | CLSP | 0 | COOLING SETPOINT SELECT |
|
|
|
|
| ||||
|
|
| ENTER |
| 0 |
| Scrolling Stops |
|
|
|
|
|
| ||
|
|
| ENTER |
| 0 |
| Flashing ‘0’ |
|
|
|
|
|
| ||
|
|
|
|
| 4 |
| Select ‘4’ |
|
|
| ENTER |
| 4 |
| Change Accepted |
|
|
|
|
|
|