OPTIONS1 (Options 1 Configuration)

DESCRIPTION

 

VALUE

DEFAULT

UNITS

POINT NAME

Cooler Fluid

1

= Water

1

 

FLUIDTYP

 

2

= Med. Brine

 

 

 

Minimum Load Vlv Select

No/Yes

No

 

MLV_FLG

Return Gas Sensor Enable

Dsable/Enable

Dsable

 

RGT_ENA

Motormaster Select

No/Yes

No

 

MTR_TYPE

Cooler Pump Control

Off/On

Off

 

CPC

Cooler Pump 1 Enable

No/Yes

No

 

PMP1_ENA

Cooler Pump 2 Enable

Dsable/Enable

Dsable

 

PMP2_ENA

Cooler Pmp Periodic Strt

No/Yes

No

 

PUMP_PST

Cooler Pump Select

0

= Automatic

0

 

PMP_SLCT

 

1

= Pump 1

 

 

 

 

2

= Pump 2

 

 

 

Cooler Pump Shutdown Dly

0 to 10

1

minutes

PUMP_DLY

Pump Changeover Hours

10 to 2000

500

hours

PMP_DLTA

EMM Module Installed

No/Yes

No

 

EMM_BRD

OPTIONS2 (Options 2 Configuration)

DESCRIPTION

 

VALUE

DEFAULT

UNITS

POINT NAME

Control Method

0

= Switch

0

 

CONTROL

 

2

= Occupancy

 

 

 

 

3

= SCN

 

 

 

Loading Sequence Select

1

= Equal Loading

1

 

SEQ_TYP

 

2

= Staged Loading

 

 

 

Lead/Lag Circuit Select

0

= Automatic

0

 

LEAD_TYP

 

1

= Circuit A Leads

 

 

 

 

2

= Circuit B Leads

 

 

 

Cooling Setpoint Select

0

= Single

0

 

CLSP_TYP

 

1

= Dual, remote switch controlled

 

 

 

 

2

= Dual SCN occupancy

 

 

 

 

3

= 4-20 mA input

 

 

 

Ramp Load Select

Enable/Dsable

Enable

 

RAMP_EBL

Heat Cool Select

Cool/Heat

Cool

 

HEATCOOL

High LCW Alert Limit

2 to 60

60.0

F

LCW_LMT

Minutes off time

0 to 15

0

min

DELAY

Deadband Multiplier

1.0 to 4.0

2.0

 

Z_GAIN

Ice Mode Enable

Enable/Dsable

Dsable

 

ICE_CNFG

Close Control Select

Enable/Dsable

Dsable

 

CLS_CTRL

Low Sound Mode Select

0

= Disabled

1

 

LS_MODE

 

1

= Fan only

 

 

 

 

2

= Capacity/Fans

 

 

 

Low Sound Start Time

00:00 to 23:59

00:00

 

LS_START

Low Sound End Time

00:00 to 23:59

00:00

 

LS_END

Low Sound Capacity Limit

0 to 100

100

%

LS_LIMIT

Enable Short Loop Gain

Enable/Dsable

Enable

 

SAGENABL

80

Image 80
Contents SAFETY CONSIDERATIONS CONTENTS GENERALMAJOR SYSTEM COMPONENTS Control Module CommunicationSterlco Comfort Network SCN Interface — Table 1 — Unit SizesTable 3 — Status Switches Table 5 - SCN Communication Bus WiringTable 2 — Thermistor Designations Table 4 - Output RelaysLEGEND FOR FIG. Page Page Fig. 3 — Wiring Schematic 30RA010-018 30RA010-018AQUA SNAPSEE NOTE SEE NOTE AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICFig. 3 - Wiring Schematic 30RA010-018cont Fig. 4 - Wiring Schematic 30RA022-030 30RA022-030AQUA SNAPFig. 4 - Wiring Schematic 30RA022-030cont AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICFig. 5 — Wiring Schematic 30RA032-040 30RA032-040AQUA SNAPFig. 5 — Wiring Schematic 30RA032-040cont AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICFig. 6 — Wiring Schematic 30RA042-055 30RA042-055AQUA SNAPFig. 6 — Wiring Schematic 30RA042-055cont AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICFig. 7 — Main Base Board ESCAPEENTERREMOTE CONTACT SW1 OFF ENABLE OFF SW2 ON MODEFig. 9 — Typical Space Temperature Sensor Wiring Fig. 11 - Energy Management Module CEPL130351100/100 Fig. 12 — Deadband Multiplier Fig. 14 — 30RA Condenser Fan Sequence Fig. 13 — Operating Envelope forR-22Maneurop Compressor Cooling Set Point Select Service Test See Table 11 — Both main power and control circuit power must be onTable 8 — Control Methods and Cooling Set Points Fig. 16 — Scrolling Marquee DisplayOptional Factory-InstalledHydronic Package — •Cooler Pump Control CPC Configuration, OPT1 ON Fig. 17 — Dual Chiller Thermistor Location Table 9 — Marquee Display Menu StructureTable 10 — Run Status Mode and Sub-ModeDirectory SUB-MODE Table 12 - Temperature Mode and Sub-ModeDirectory Table 15 — Inputs Mode and Sub-ModeDirectory Table 13 — Pressure Mode and Sub-ModeDirectoryTable 14 — Set Point and Sub-ModeDirectory Table 16 — Outputs Mode and Sub-ModeDirectory SUB-MODEKEYPAD DISPLAYSUB-MODE KEYPADITEM DISPLAYSUB-MODE KEYPADITEM DISPLAYTable 18 — Time Clock Mode and Sub-ModeDirectory PER.3 SUB-MODE Table 20 — Alarms Mode and Sub-ModeDirectory Table 19 — Operating Mode and Sub-ModeDirectorySUB-MODE ITEMKEYPAD ENTRY DISPLAYRSET DISP Table 23 — Operating Modes Table 24 — Example of Reading and Clearing Alarms Table 25A — 4-20mA ResetTable 26B — Configuring Return Temperature Reset Fig. 18 — Standard Chilled Fluid Temperature Control — No ResetFig. 19 — Outdoor-AirTemperature Reset Fig. 20 — Space Temperature ResetFig. 21A — 4- to 20-mADemand Limiting Fig. 21B — Cooling Set Point 4 to 20 mATROUBLESHOOTING Table 27 — Configuring Demand Limitand fluid tubing Table 28 — TroubleshootingRecommended that system be filled with an appro Fig. 22 — Component Arrangement — 30RA010-030 FU — Fuse GND — GroundFig. 23 — Component Arrangement — 30RA032-040 FU — Fuse GND — GroundFig. 24 — Component Arrangement — 30RA042-055 FU — Fuse GND — GroundNOTES LEGEND Table 29 — Alarm and Alert Codes Table 29 - Alarm and Alert Codes cont Table 29 — Alarm and Alert Codes cont ALARMTable 29 — Alarm and Alert Codes cont ALARMTable 29 — Alarm and Alert Codes cont ALARMSERVICE Compressor Replacement Refer to FigTable 30 - Unit Torque Specification Electronic ComponentsFig. 28 — Compressor Wiring Fig. 27 — Typical Compressor Mounting — All SizesFig. 29 — Compressor Location — 30RA010-030 Fig. 30 — Compressor Location — 30RA032-055Condenser Section and Coils Table 31 - Oil ChargeFig. 31 — 30RA Access Panels Check Refrigerant Feed ComponentsFig. 32 — Condenser-FanMounting Fig. 33 — Condenser-FanPosition Standard FanTable 32 — Factory Settings, High-Pressure Switch FixedCompressor and Unit Protective Devices Check Unit SafetiesCOOLER FREEZE-UPPROTECTION TEMP TEMP For Thermistor T10 For Thermistor T10 Fig. 36 — Thermistor Connections to Main Base Board, J8 ConnectorFig. 35 — Fluid-SideTemperature Sensors T1 and T2 PROGRAMMING Mode •P51: SOFTWARE version Table 37 - Fault Codes•P50: FAULT HISTORY — Last 8 faults PARAMETERS Table 39 — Replacement Modules MAINTENANCE Minimum Loop VolumePRE-START-UP System CheckOperating Limitations Standard 30RA Units OPERATION SEQUENCETable 41 — Temperature Limits for APPENDIX A SCN Tables A_UNIT General Unit ParametersCIRCADIO Circuit A Discrete Inputs/Outputs CIRCA_AN Circuit A Analog ParametersOPTIONS Unit Parameters CIRCBDIO Circuit B Discrete Inputs/OutputsCIRCB_AN Circuit B Analog Parameters ALARMDEF Alarm Definition Table DISPLAY Marquee Display SETUPDUALCHIL Dual Chiller Configuration Settings BRODEFS Broadcast POC Definition TableOPTIONS1 Options 1 Configuration OPTIONS2 Options 2 ConfigurationSETPOINT SCHEDOVR Timed Override SetupRESETCON Temperature Reset and Demand Limit MAINTENANCE ALARMS: Maintenance DisplayUNIT CURRMODS: Maintenance Display DUALCHIL: Maintenance DisplayLEARNFNS Maintenance Display LOADFACT: Maintenance DisplayPM-STRN Maintenance Display PM-COIL:Maintenance DisplayPM-PUMP:Maintenance Display RUNTEST: Maintenance Display VERSIONS: Maintenance Display STRTHOUR Maintenance DisplayTESTMODE: Maintenance Display WSMDEFME: Maintenance Display AND MANUAL STARTERS FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMPAPPENDIX B AND MANUAL STARTERS cont FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMPAPPENDIX C DataPort, DataLink, BAClink Object DefinitionOPTIONS SETPOINTSTART-UPCHECKLIST FOR 30RA LIQUID CHILLER Remove and use for Job File I.Project InformationII. Preliminary Equipment Check Design InformationIII. Unit Start-Up Start and Operate Machine. Complete the FollowingCL-3 CL-4 Record Software Versions MODE — RUN STATUSCOMMENTS III.Unit Start-Upcont UNIT Configuration SettingsOPTIONS1 Options Configuration OPTIONS2 Options Configuration RSET Reset Configuration SettingsIII.Unit Start-Upcont CL-6SLCT Setpoint and Ramp Load Configuration III.Unit Start-UpcontSETPOINT CL-7Service Test Mode and Sub-ModeDirectory III.Unit Start-Upcont