Sterling 30RA010-055 manual Programming

Page 69
PROGRAMMING

PROGRAMMING

It is strongly recommended that the user NOT change any programming without consulting Sterling service personnel. Unit damage may occur from improper programming.

Motormaster V control is completely configured according to the inputs provided. No additional programming is necessary.

The drive can display 71 program parameters. Parameters

50-60 are monitor functions and cannot be changed. The remainder of the parameters can be changed after entering a password.

To enter password and change program values:

1.Press Mode.

2.Upper right decimal point blinks.

3.Display reads “00” (see Fig. 37). To enter the PRO- GRAM mode to access the parameters, press the Mode button (see Fig. 37). This will activate the PASSWORD prompt (if the password has not been disabled). The dis- play will read “00” and the upper right-hand decimal point will be blinking.

4.Use the Manual backgroundManual backgroundManual background and Manual backgroundManual backgroundManual background buttons to scroll to the password value (the factory default password is “111”) and press the Mode button. Once the correct password value is en- tered, the display will read “P01”, which indicates that the PROGRAM mode has been accessed at the beginning of the parameter menu (P01 is the first parameter).

NOTE: If the display flashes “Er”, the password was incorrect, and the process to enter the password must be repeated.

5.Press Mode to display present parameter setting. Upper right decimal point blinks.

Use the Manual backgroundManual backgroundManual background and Manual backgroundManual backgroundManual background buttons to scroll to the desired parameter number.

Once the desired parameter number is found, press the Mode button to display the present parameter setting. The up- per right-hand decimal point will begin blinking, indicating that the present parameter setting is being displayed, and that it can be changed by using the up and down buttons. Use Manual background and Manual backgroundManual backgroundManual background to change setting. Press Mode to store new setting.

Pressing the Mode will store the new setting and also exit the PROGRAM mode. To change another parameter, press the Mode key again to re-enter the PROGRAM mode (the param- eter menu will be accessed at the parameter that was last viewed or changed before exiting). If the Mode key is pressed within two minutes of exiting the PROGRAM mode, the pass- word is not required access the parameters. After two minutes, the password must be entered in order to access the parameters again.

To change password: first enter the current password then change parameter P44 to the desired password.

To disable automatic control mode and enter manual speed control mode:

1.Change P05 to ‘01- keypad’.

2.Push UP and DOWN arrow key to set manual speed.

3.Set P05 to ‘05 - R22’ to restore automatic control. To provide manual start/stop control:

With power removed from VFD, remove start command jumper and install a switch between the appropriate start termi- nals as required in Fig 37.

EPM CHIP — The drive uses a electronic programming mod- ule (EPM) chip to store the program parameters. This is an EE- PROM memory chip and is accessible from the front of the VFD. It should not be removed with power applied to the VFD.

LIQUID LINE PRESSURE SET POINT ADJUST- MENT — Adjusting the set point is not recommended due to possible interaction with other head pressure software algo- rithms or controls. In situations where the set point must be changed, the set point for R-22 is found in P34. A higher value will result in a higher liquid line set point. Example: increasing the factory default (P34) set point from 18.0 to 19.0 will in- crease the liquid line pressure by approximately 10 psi.

LOSS OF SCN COMMUNICATIONS — Sterlco Comfort Network (SCN) communications with external control systems can be affected by high frequency electrical noise gen- erated by the Motormaster V control. Ensure unit is well grounded to eliminate ground currents along communication lines.

If communications are lost only while Motormaster V con- trol is in operation, order a signal isolator (CEAS420876-2) and power supplies (CEAS221045-01, 2 required) for the SCN communication line.

Fault Codes — The drive is programmed to automatically re- start after a fault and will attempt to restart three times after a fault (the drive will not restart after CF, cF, GF, F1, F2-F9, or Fo faults). If all three restart attempts are unsuccessful, the drive will trip into FAULT LOCKOUT (LC), which requires a manual reset.

NOTE: Since faults may be reset as incoming power is cycled, you may need to observe current fault code before the Sterling unit control turns off the VFD. Most recent faults can be accessed using parameter 50. If necessary, remove start jumper and energize condenser fan contactor using Service Test. This will allow programming and access to fault history.

69

Image 69
Contents SAFETY CONSIDERATIONS GENERAL CONTENTSControl Module Communication MAJOR SYSTEM COMPONENTSSterlco Comfort Network SCN Interface — Table 1 — Unit SizesTable 5 - SCN Communication Bus Wiring Table 3 — Status SwitchesTable 2 — Thermistor Designations Table 4 - Output RelaysLEGEND FOR FIG. Page Page 30RA010-018AQUA SNAP Fig. 3 — Wiring Schematic 30RA010-018AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATIC Fig. 3 - Wiring Schematic 30RA010-018contSEE NOTE SEE NOTE 30RA022-030AQUA SNAP Fig. 4 - Wiring Schematic 30RA022-030AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATIC Fig. 4 - Wiring Schematic 30RA022-030cont30RA032-040AQUA SNAP Fig. 5 — Wiring Schematic 30RA032-040AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATIC Fig. 5 — Wiring Schematic 30RA032-040cont30RA042-055AQUA SNAP Fig. 6 — Wiring Schematic 30RA042-055AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATIC Fig. 6 — Wiring Schematic 30RA042-055contESCAPEENTER Fig. 7 — Main Base BoardREMOTE CONTACT SW1 OFF ENABLE OFF SW2 ON MODEFig. 9 — Typical Space Temperature Sensor Wiring CEPL130351 Fig. 11 - Energy Management Module100/100 Fig. 12 — Deadband Multiplier Fig. 13 — Operating Envelope for R-22Maneurop CompressorFig. 14 — 30RA Condenser Fan Sequence Cooling Set Point Select and control circuit power must be on Service Test See Table 11 — Both main powerTable 8 — Control Methods and Cooling Set Points Fig. 16 — Scrolling Marquee DisplayOptional Factory-InstalledHydronic Package — •Cooler Pump Control CPC Configuration, OPT1 ON Table 9 — Marquee Display Menu Structure Fig. 17 — Dual Chiller Thermistor LocationTable 10 — Run Status Mode and Sub-ModeDirectory SUB-MODE Table 12 - Temperature Mode and Sub-ModeDirectory Table 13 — Pressure Mode and Sub-ModeDirectory Table 14 — Set Point and Sub-ModeDirectoryTable 15 — Inputs Mode and Sub-ModeDirectory SUB-MODE Table 16 — Outputs Mode and Sub-ModeDirectoryKEYPAD DISPLAYKEYPAD SUB-MODEITEM DISPLAYKEYPAD SUB-MODEITEM DISPLAYTable 18 — Time Clock Mode and Sub-ModeDirectory PER.3 SUB-MODE Table 19 — Operating Mode and Sub-ModeDirectory Table 20 — Alarms Mode and Sub-ModeDirectoryITEM SUB-MODEKEYPAD ENTRY DISPLAYRSET DISP Table 23 — Operating Modes Table 25A — 4-20mA Reset Table 24 — Example of Reading and Clearing AlarmsTable 26B — Configuring Return Temperature Reset Temperature Control — No Reset Fig. 18 — Standard Chilled FluidFig. 19 — Outdoor-AirTemperature Reset Fig. 20 — Space Temperature ResetFig. 21B — Cooling Set Point 4 to 20 mA Fig. 21A — 4- to 20-mADemand LimitingTable 27 — Configuring Demand Limit TROUBLESHOOTINGTable 28 — Troubleshooting Recommended that system be filled with an approand fluid tubing FU — Fuse GND — Ground Fig. 22 — Component Arrangement — 30RA010-030FU — Fuse GND — Ground Fig. 23 — Component Arrangement — 30RA032-040FU — Fuse GND — Ground Fig. 24 — Component Arrangement — 30RA042-055NOTES LEGEND Table 29 — Alarm and Alert Codes Table 29 - Alarm and Alert Codes cont ALARM Table 29 — Alarm and Alert Codes contALARM Table 29 — Alarm and Alert Codes contALARM Table 29 — Alarm and Alert Codes contCompressor Replacement Refer to Fig SERVICETable 30 - Unit Torque Specification Electronic ComponentsFig. 27 — Typical Compressor Mounting — All Sizes Fig. 28 — Compressor WiringFig. 29 — Compressor Location — 30RA010-030 Fig. 30 — Compressor Location — 30RA032-055Table 31 - Oil Charge Condenser Section and CoilsCheck Refrigerant Feed Components Fig. 31 — 30RA Access PanelsFig. 32 — Condenser-FanMounting Fig. 33 — Condenser-FanPosition Standard FanSwitch Fixed Table 32 — Factory Settings, High-PressureCompressor and Unit Protective Devices Check Unit SafetiesCOOLER FREEZE-UPPROTECTION TEMP TEMP For Thermistor T10 For Thermistor T10 Main Base Board, J8 Connector Fig. 35 — Fluid-SideTemperature Sensors T1 and T2Fig. 36 — Thermistor Connections to PROGRAMMING Mode Table 37 - Fault Codes •P50: FAULT HISTORY — Last 8 faults•P51: SOFTWARE version PARAMETERS Table 39 — Replacement Modules Minimum Loop Volume MAINTENANCEPRE-START-UP System CheckOperating Limitations OPERATION SEQUENCE Table 41 — Temperature Limits forStandard 30RA Units SCN Tables A_UNIT General Unit Parameters APPENDIX ACIRCADIO Circuit A Discrete Inputs/Outputs CIRCA_AN Circuit A Analog ParametersCIRCBDIO Circuit B Discrete Inputs/Outputs CIRCB_AN Circuit B Analog ParametersOPTIONS Unit Parameters DISPLAY Marquee Display SETUP ALARMDEF Alarm Definition TableDUALCHIL Dual Chiller Configuration Settings BRODEFS Broadcast POC Definition TableOPTIONS2 Options 2 Configuration OPTIONS1 Options 1 ConfigurationSCHEDOVR Timed Override Setup RESETCON Temperature Reset and Demand LimitSETPOINT ALARMS: Maintenance Display UNITMAINTENANCE DUALCHIL: Maintenance Display CURRMODS: Maintenance DisplayLOADFACT: Maintenance Display LEARNFNS Maintenance DisplayPM-COIL:Maintenance Display PM-PUMP:Maintenance DisplayPM-STRN Maintenance Display RUNTEST: Maintenance Display STRTHOUR Maintenance Display TESTMODE: Maintenance DisplayVERSIONS: Maintenance Display WSMDEFME: Maintenance Display FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMP APPENDIX BAND MANUAL STARTERS FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMP AND MANUAL STARTERS contDataPort, DataLink, BAClink Object Definition APPENDIX CSETPOINT OPTIONSRemove and use for Job File I.Project Information START-UPCHECKLIST FOR 30RA LIQUID CHILLERII. Preliminary Equipment Check Design InformationStart and Operate Machine. Complete the Following III. Unit Start-UpCL-3 Record Software Versions MODE — RUN STATUS COMMENTSCL-4 UNIT Configuration Settings OPTIONS1 Options ConfigurationIII.Unit Start-Upcont RSET Reset Configuration Settings OPTIONS2 Options ConfigurationIII.Unit Start-Upcont CL-6III.Unit Start-Upcont SLCT Setpoint and Ramp Load ConfigurationSETPOINT CL-7III.Unit Start-Upcont Service Test Mode and Sub-ModeDirectory