Page 72

Table 38 — Motormaster® V Program Parameters for Operating Modes

PARAMETERS

DESCRIPTION

MODE

MODE

MODE

MODE

1

2

3

4

 

 

 

 

P01

Line Voltage: 01 = low line, 02 = high line

01

02

01

02

 

P02

Sterlco Freq: 01 = 4 kHz, 02 = 6 kHz, 03 = 8 kHz

01

01

01

01

 

P03

Startup mode: flying restart

06

06

06

06

 

P04

Stop mode: coast to stop

01

01

01

01

 

P05

Standard Speed source: 01= keypad,

05

05

05

05

 

04=4-20mA (NO PI), 05= R22, 06=R134a

 

 

 

 

 

 

 

P06

TB-14 output: 01 = none

01

01

01

01

 

P08

TB-30 output: 01 = none

01

01

01

01

 

P09

TB-31 Output: 01 = none

01

01

01

01

 

P10

TB-13A function sel: 01 = none

01

01

01

01

 

P11

TB-13B function sel: 01 = none

01

01

01

01

 

P12

TB-13C function sel: 01 = none

01

01

01

01

 

P13

TB-15 output: 01 = none

01

01

01

01

 

P14

Control: 01 = Terminal strip

01

01

01

01

 

P15

Serial link: 02 = enabled 9600,8,N,2 with timer

02

02

02

02

 

P16

Units editing: 02 = whole units

02

02

02

02

 

P17

Rotation: 01 = forward only, 03 = reverse only

01

01

01

01

 

P19

Acceleration time: 10 sec

10

10

10

10

 

P20

Deceleration time: 10 sec

10

10

10

10

 

P21

DC brake time: 0

0

0

0

0

 

P22

DC BRAKE VOLTAGE 0%

0

0

0

0

 

P23

Min freq = 8 Hz ~ 100 – 160 rpm

8

8

8

8

 

P24

Max freq

60

60

50

50

 

P25

Current limit: (%)

125

110

125

110

 

P26

Motor overload: 100

100

100

100

100

 

P27

Base freq: 60 or 50 Hz

60

60

50

50

 

P28

Fixed boost: 0.5% at low frequencies

0.5

0.5

0.5

0.5

 

P29

Accel boost: 0%

0

0

0

0

 

P30

Slip compensation: 0%

0

0

0

0

 

P31

Preset spd #1: speed if loss of control signal

57

57

47

47

 

P32

Preset spd #2: 0

0

0

0

0

 

P33

Preset spd #3: 0

0

0

0

0

 

P34

Preset spd 4 default — R22 set point.

18.0

18.0

18.0

18.0

 

TB12-2 open

 

 

 

 

 

 

 

P35

Preset spd 5 default — R134a set point.

12.6

12.6

12.6

12.6

 

TB12-2 closed

 

 

 

 

 

 

 

P36

Preset spd 6 default

0

0

0

0

 

P37

Preset spd 7 default

0

0

0

0

 

P38

Skip bandwidth

0

0

0

0

 

P39

Speed scaling

0

0

0

0

 

P40

Frequency scaling 50 or 60 Hz

60

60

50

50

 

P41

Load scaling: default (not used so NA)

200

200

200

200

 

P42

Accel/decel #2: default (not used so NA)

60

60

60

60

 

P43

Serial address

1

1

1

1

 

P44

Password:111

111

111

111

111

 

P45

Speed at min signal: 8 Hz; used when PID

8

8

8

8

 

mode is disabled and 4-20mA input is at 4 mA

 

 

 

 

 

 

 

P46

Speed at max feedback: 60 or 50 Hz. Used

60

60

50

50

 

when PID disabled and 4-20mA input is at 20 mA

 

 

 

 

 

 

 

P47

Clear history? 01 = maintain. (set to 02 to clear)

01

01

01

01

 

P48

Program selection: Program 1 – 12

01

02

03

04

 

P61

PI Mode: 05= reverse, 0-5V, 01 = no PID

05

05

05

05

 

P62

Min feedback = 0 (0V *10)

0

0

0

0

 

P63

Max feedback = 50 (5V * 10)

50

50

50

50

 

P64

Proportional gain = 4%

4

4

4

4

 

P65

Integral gain = .2

.2

.2

.2

.2

 

P66

PI acell/decel (set point change filter) = 5

5

5

5

5

 

P67

Min alarm

0

0

0

0

 

P68

Max alarm

0

0

0

0

 

LEGEND

 

 

 

 

NA

Not Applicable

 

 

 

 

PID

Proportional Integral Derivative

 

 

 

 

TB

Terminal Block

 

 

 

 

72

Image 72
Contents SAFETY CONSIDERATIONS CONTENTS GENERALMAJOR SYSTEM COMPONENTS Control Module CommunicationSterlco Comfort Network SCN Interface — Table 1 — Unit SizesTable 3 — Status Switches Table 5 - SCN Communication Bus WiringTable 2 — Thermistor Designations Table 4 - Output RelaysLEGEND FOR FIG. Page Page Fig. 3 — Wiring Schematic 30RA010-018 30RA010-018AQUA SNAPAQUA-SNAPLOW VOLTAGE CONTROL SCHEMATIC Fig. 3 - Wiring Schematic 30RA010-018contSEE NOTE SEE NOTE Fig. 4 - Wiring Schematic 30RA022-030 30RA022-030AQUA SNAPFig. 4 - Wiring Schematic 30RA022-030cont AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICFig. 5 — Wiring Schematic 30RA032-040 30RA032-040AQUA SNAPFig. 5 — Wiring Schematic 30RA032-040cont AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICFig. 6 — Wiring Schematic 30RA042-055 30RA042-055AQUA SNAPFig. 6 — Wiring Schematic 30RA042-055cont AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICFig. 7 — Main Base Board ESCAPEENTERREMOTE CONTACT SW1 OFF ENABLE OFF SW2 ON MODEFig. 9 — Typical Space Temperature Sensor Wiring Fig. 11 - Energy Management Module CEPL130351100/100 Fig. 12 — Deadband Multiplier Fig. 13 — Operating Envelope for R-22Maneurop CompressorFig. 14 — 30RA Condenser Fan Sequence Cooling Set Point Select Service Test See Table 11 — Both main power and control circuit power must be onTable 8 — Control Methods and Cooling Set Points Fig. 16 — Scrolling Marquee DisplayOptional Factory-InstalledHydronic Package — •Cooler Pump Control CPC Configuration, OPT1 ON Fig. 17 — Dual Chiller Thermistor Location Table 9 — Marquee Display Menu StructureTable 10 — Run Status Mode and Sub-ModeDirectory SUB-MODE Table 12 - Temperature Mode and Sub-ModeDirectory Table 13 — Pressure Mode and Sub-ModeDirectory Table 14 — Set Point and Sub-ModeDirectoryTable 15 — Inputs Mode and Sub-ModeDirectory Table 16 — Outputs Mode and Sub-ModeDirectory SUB-MODEKEYPAD DISPLAYSUB-MODE KEYPADITEM DISPLAYSUB-MODE KEYPADITEM DISPLAYTable 18 — Time Clock Mode and Sub-ModeDirectory PER.3 SUB-MODE Table 20 — Alarms Mode and Sub-ModeDirectory Table 19 — Operating Mode and Sub-ModeDirectorySUB-MODE ITEMKEYPAD ENTRY DISPLAYRSET DISP Table 23 — Operating Modes Table 24 — Example of Reading and Clearing Alarms Table 25A — 4-20mA ResetTable 26B — Configuring Return Temperature Reset Fig. 18 — Standard Chilled Fluid Temperature Control — No ResetFig. 19 — Outdoor-AirTemperature Reset Fig. 20 — Space Temperature ResetFig. 21A — 4- to 20-mADemand Limiting Fig. 21B — Cooling Set Point 4 to 20 mATROUBLESHOOTING Table 27 — Configuring Demand LimitTable 28 — Troubleshooting Recommended that system be filled with an approand fluid tubing Fig. 22 — Component Arrangement — 30RA010-030 FU — Fuse GND — GroundFig. 23 — Component Arrangement — 30RA032-040 FU — Fuse GND — GroundFig. 24 — Component Arrangement — 30RA042-055 FU — Fuse GND — GroundNOTES LEGEND Table 29 — Alarm and Alert Codes Table 29 - Alarm and Alert Codes cont Table 29 — Alarm and Alert Codes cont ALARMTable 29 — Alarm and Alert Codes cont ALARMTable 29 — Alarm and Alert Codes cont ALARMSERVICE Compressor Replacement Refer to FigTable 30 - Unit Torque Specification Electronic ComponentsFig. 28 — Compressor Wiring Fig. 27 — Typical Compressor Mounting — All SizesFig. 29 — Compressor Location — 30RA010-030 Fig. 30 — Compressor Location — 30RA032-055Condenser Section and Coils Table 31 - Oil ChargeFig. 31 — 30RA Access Panels Check Refrigerant Feed ComponentsFig. 32 — Condenser-FanMounting Fig. 33 — Condenser-FanPosition Standard FanTable 32 — Factory Settings, High-Pressure Switch FixedCompressor and Unit Protective Devices Check Unit SafetiesCOOLER FREEZE-UPPROTECTION TEMP TEMP For Thermistor T10 For Thermistor T10 Main Base Board, J8 Connector Fig. 35 — Fluid-SideTemperature Sensors T1 and T2Fig. 36 — Thermistor Connections to PROGRAMMING Mode Table 37 - Fault Codes •P50: FAULT HISTORY — Last 8 faults•P51: SOFTWARE version PARAMETERS Table 39 — Replacement Modules MAINTENANCE Minimum Loop VolumePRE-START-UP System CheckOperating Limitations OPERATION SEQUENCE Table 41 — Temperature Limits forStandard 30RA Units APPENDIX A SCN Tables A_UNIT General Unit ParametersCIRCADIO Circuit A Discrete Inputs/Outputs CIRCA_AN Circuit A Analog ParametersCIRCBDIO Circuit B Discrete Inputs/Outputs CIRCB_AN Circuit B Analog ParametersOPTIONS Unit Parameters ALARMDEF Alarm Definition Table DISPLAY Marquee Display SETUPDUALCHIL Dual Chiller Configuration Settings BRODEFS Broadcast POC Definition TableOPTIONS1 Options 1 Configuration OPTIONS2 Options 2 ConfigurationSCHEDOVR Timed Override Setup RESETCON Temperature Reset and Demand LimitSETPOINT ALARMS: Maintenance Display UNITMAINTENANCE CURRMODS: Maintenance Display DUALCHIL: Maintenance DisplayLEARNFNS Maintenance Display LOADFACT: Maintenance DisplayPM-COIL:Maintenance Display PM-PUMP:Maintenance DisplayPM-STRN Maintenance Display RUNTEST: Maintenance Display STRTHOUR Maintenance Display TESTMODE: Maintenance DisplayVERSIONS: Maintenance Display WSMDEFME: Maintenance Display FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMP APPENDIX BAND MANUAL STARTERS AND MANUAL STARTERS cont FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMPAPPENDIX C DataPort, DataLink, BAClink Object DefinitionOPTIONS SETPOINTSTART-UPCHECKLIST FOR 30RA LIQUID CHILLER Remove and use for Job File I.Project InformationII. Preliminary Equipment Check Design InformationIII. Unit Start-Up Start and Operate Machine. Complete the FollowingCL-3 Record Software Versions MODE — RUN STATUS COMMENTSCL-4 UNIT Configuration Settings OPTIONS1 Options ConfigurationIII.Unit Start-Upcont OPTIONS2 Options Configuration RSET Reset Configuration SettingsIII.Unit Start-Upcont CL-6SLCT Setpoint and Ramp Load Configuration III.Unit Start-UpcontSETPOINT CL-7Service Test Mode and Sub-ModeDirectory III.Unit Start-Upcont