Table 38 — Motormaster® V Program Parameters for Operating Modes
PARAMETERS | DESCRIPTION | MODE | MODE | MODE | MODE | ||
1 | 2 | 3 | 4 | ||||
|
|
| |||||
| P01 | Line Voltage: 01 = low line, 02 = high line | 01 | 02 | 01 | 02 | |
| P02 | Sterlco Freq: 01 = 4 kHz, 02 = 6 kHz, 03 = 8 kHz | 01 | 01 | 01 | 01 | |
| P03 | Startup mode: flying restart | 06 | 06 | 06 | 06 | |
| P04 | Stop mode: coast to stop | 01 | 01 | 01 | 01 | |
| P05 | Standard Speed source: 01= keypad, | 05 | 05 | 05 | 05 | |
| |||||||
|
|
|
|
|
| ||
| P06 | 01 | 01 | 01 | 01 | ||
| P08 | 01 | 01 | 01 | 01 | ||
| P09 | 01 | 01 | 01 | 01 | ||
| P10 | 01 | 01 | 01 | 01 | ||
| P11 | 01 | 01 | 01 | 01 | ||
| P12 | 01 | 01 | 01 | 01 | ||
| P13 | 01 | 01 | 01 | 01 | ||
| P14 | Control: 01 = Terminal strip | 01 | 01 | 01 | 01 | |
| P15 | Serial link: 02 = enabled 9600,8,N,2 with timer | 02 | 02 | 02 | 02 | |
| P16 | Units editing: 02 = whole units | 02 | 02 | 02 | 02 | |
| P17 | Rotation: 01 = forward only, 03 = reverse only | 01 | 01 | 01 | 01 | |
| P19 | Acceleration time: 10 sec | 10 | 10 | 10 | 10 | |
| P20 | Deceleration time: 10 sec | 10 | 10 | 10 | 10 | |
| P21 | DC brake time: 0 | 0 | 0 | 0 | 0 | |
| P22 | DC BRAKE VOLTAGE 0% | 0 | 0 | 0 | 0 | |
| P23 | Min freq = 8 Hz ~ 100 – 160 rpm | 8 | 8 | 8 | 8 | |
| P24 | Max freq | 60 | 60 | 50 | 50 | |
| P25 | Current limit: (%) | 125 | 110 | 125 | 110 | |
| P26 | Motor overload: 100 | 100 | 100 | 100 | 100 | |
| P27 | Base freq: 60 or 50 Hz | 60 | 60 | 50 | 50 | |
| P28 | Fixed boost: 0.5% at low frequencies | 0.5 | 0.5 | 0.5 | 0.5 | |
| P29 | Accel boost: 0% | 0 | 0 | 0 | 0 | |
| P30 | Slip compensation: 0% | 0 | 0 | 0 | 0 | |
| P31 | Preset spd #1: speed if loss of control signal | 57 | 57 | 47 | 47 | |
| P32 | Preset spd #2: 0 | 0 | 0 | 0 | 0 | |
| P33 | Preset spd #3: 0 | 0 | 0 | 0 | 0 | |
| P34 | Preset spd 4 default — R22 set point. | 18.0 | 18.0 | 18.0 | 18.0 | |
| |||||||
|
|
|
|
|
| ||
| P35 | Preset spd 5 default — R134a set point. | 12.6 | 12.6 | 12.6 | 12.6 | |
| |||||||
|
|
|
|
|
| ||
| P36 | Preset spd 6 default | 0 | 0 | 0 | 0 | |
| P37 | Preset spd 7 default | 0 | 0 | 0 | 0 | |
| P38 | Skip bandwidth | 0 | 0 | 0 | 0 | |
| P39 | Speed scaling | 0 | 0 | 0 | 0 | |
| P40 | Frequency scaling 50 or 60 Hz | 60 | 60 | 50 | 50 | |
| P41 | Load scaling: default (not used so NA) | 200 | 200 | 200 | 200 | |
| P42 | Accel/decel #2: default (not used so NA) | 60 | 60 | 60 | 60 | |
| P43 | Serial address | 1 | 1 | 1 | 1 | |
| P44 | Password:111 | 111 | 111 | 111 | 111 | |
| P45 | Speed at min signal: 8 Hz; used when PID | 8 | 8 | 8 | 8 | |
| mode is disabled and | ||||||
|
|
|
|
|
| ||
| P46 | Speed at max feedback: 60 or 50 Hz. Used | 60 | 60 | 50 | 50 | |
| when PID disabled and | ||||||
|
|
|
|
|
| ||
| P47 | Clear history? 01 = maintain. (set to 02 to clear) | 01 | 01 | 01 | 01 | |
| P48 | Program selection: Program 1 – 12 | 01 | 02 | 03 | 04 | |
| P61 | PI Mode: 05= reverse, | 05 | 05 | 05 | 05 | |
| P62 | Min feedback = 0 (0V *10) | 0 | 0 | 0 | 0 | |
| P63 | Max feedback = 50 (5V * 10) | 50 | 50 | 50 | 50 | |
| P64 | Proportional gain = 4% | 4 | 4 | 4 | 4 | |
| P65 | Integral gain = .2 | .2 | .2 | .2 | .2 | |
| P66 | PI acell/decel (set point change filter) = 5 | 5 | 5 | 5 | 5 | |
| P67 | Min alarm | 0 | 0 | 0 | 0 | |
| P68 | Max alarm | 0 | 0 | 0 | 0 | |
| LEGEND |
|
|
|
| ||
NA | — Not Applicable |
|
|
|
| ||
PID | — Proportional Integral Derivative |
|
|
|
| ||
TB | — Terminal Block |
|
|
|
|
72