Sterling 30RA010-055 manual Sub-Mode

Page 36
Manual background

Table 18 — Time Clock Mode and Sub-Mode Directory (cont)

SUB-MODE

KEYPAD

ITEM

DISPLAY

SUB-ITEM

DISPLAY

ITEM

COMMENT

ENTRY

EXPANSION

 

 

 

 

 

 

SCH.L (cont)

 

 

 

 

 

THU.6

YES/NO

THURSDAY IN PERIOD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FRI.6

YES/NO

FRIDAY IN PERIOD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SAT.6

YES/NO

SATURDAY IN PERIOD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SUN.6

YES/NO

SUNDAY IN PERIOD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HOL.6

YES/NO

HOLIDAY IN PERIOD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PER.7

 

 

 

OCCUPANCY PERIOD 7

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OCC.7

XX:XX

PERIOD OCCUPIED TIME

Military (00:00 – 23:59)

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNC.7

XX.XX

PERIOD UNOCCUPIED TIME

Military (00:00 – 23:59)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MON.7

YES/NO

MONDAY IN PERIOD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TUE.7

YES/NO

TUESDAY IN PERIOD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WED.7

YES/NO

WEDNESDAY IN PERIOD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THU.7

YES/NO

THURSDAY IN PERIOD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FRI.7

YES/NO

FRIDAY IN PERIOD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SAT.7

YES/NO

SATURDAY IN PERIOD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SUN.7

YES/NO

SUNDAY IN PERIOD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HOL.7

YES/NO

HOLIDAY IN PERIOD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PER.8

 

 

 

OCCUPANCY PERIOD 8

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OCC.8

XX:XX

PERIOD OCCUPIED TIME

Military (00:00 – 23:59)

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNC.8

XX.XX

PERIOD UNOCCUPIED TIME

Military (00:00 – 23:59)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MON.8

YES/NO

MONDAY IN PERIOD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TUE.8

YES/NO

TUESDAY IN PERIOD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WED.8

YES/NO

WEDNESDAY IN PERIOD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THU.8

YES/NO

THURSDAY IN PERIOD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FRI.8

YES/NO

FRIDAY IN PERIOD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SAT.8

YES/NO

SATURDAY IN PERIOD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SUN.8

YES/NO

SUNDAY IN PERIOD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HOL.8

YES/NO

HOLIDAY IN PERIOD

 

 

 

 

 

 

 

 

 

 

 

OVR

 

 

 

 

 

 

 

SCHEDULE OVERRIDE

 

 

 

 

OVR.T

X

 

 

TIMED OVERRIDE HOURS

Default: 0, Range 0-4 hours

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OVR.L

X

 

 

OVERRIDE TIME LIMIT

Default: 0, Range 0-4 hours

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T.OVR

YES/NO

 

 

TIMED OVERRIDE

User Entry

 

 

 

 

 

 

 

 

 

 

36

Image 36
Contents SAFETY CONSIDERATIONS CONTENTS GENERALMAJOR SYSTEM COMPONENTS Control Module CommunicationSterlco Comfort Network SCN Interface — Table 1 — Unit SizesTable 3 — Status Switches Table 5 - SCN Communication Bus WiringTable 2 — Thermistor Designations Table 4 - Output RelaysLEGEND FOR FIG. Page Page Fig. 3 — Wiring Schematic 30RA010-018 30RA010-018AQUA SNAPAQUA-SNAPLOW VOLTAGE CONTROL SCHEMATIC Fig. 3 - Wiring Schematic 30RA010-018contSEE NOTE SEE NOTE Fig. 4 - Wiring Schematic 30RA022-030 30RA022-030AQUA SNAPFig. 4 - Wiring Schematic 30RA022-030cont AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICFig. 5 — Wiring Schematic 30RA032-040 30RA032-040AQUA SNAPFig. 5 — Wiring Schematic 30RA032-040cont AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICFig. 6 — Wiring Schematic 30RA042-055 30RA042-055AQUA SNAPFig. 6 — Wiring Schematic 30RA042-055cont AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICFig. 7 — Main Base Board ESCAPEENTERREMOTE CONTACT SW1 OFF ENABLE OFF SW2 ON MODEFig. 9 — Typical Space Temperature Sensor Wiring Fig. 11 - Energy Management Module CEPL130351100/100 Fig. 12 — Deadband Multiplier Fig. 13 — Operating Envelope for R-22Maneurop CompressorFig. 14 — 30RA Condenser Fan Sequence Cooling Set Point Select Service Test See Table 11 — Both main power and control circuit power must be onTable 8 — Control Methods and Cooling Set Points Fig. 16 — Scrolling Marquee DisplayOptional Factory-InstalledHydronic Package — •Cooler Pump Control CPC Configuration, OPT1 ON Fig. 17 — Dual Chiller Thermistor Location Table 9 — Marquee Display Menu StructureTable 10 — Run Status Mode and Sub-ModeDirectory SUB-MODE Table 12 - Temperature Mode and Sub-ModeDirectory Table 13 — Pressure Mode and Sub-ModeDirectory Table 14 — Set Point and Sub-ModeDirectoryTable 15 — Inputs Mode and Sub-ModeDirectory Table 16 — Outputs Mode and Sub-ModeDirectory SUB-MODEKEYPAD DISPLAYSUB-MODE KEYPADITEM DISPLAYSUB-MODE KEYPADITEM DISPLAYTable 18 — Time Clock Mode and Sub-ModeDirectory PER.3 SUB-MODE Table 20 — Alarms Mode and Sub-ModeDirectory Table 19 — Operating Mode and Sub-ModeDirectorySUB-MODE ITEMKEYPAD ENTRY DISPLAYRSET DISP Table 23 — Operating Modes Table 24 — Example of Reading and Clearing Alarms Table 25A — 4-20mA ResetTable 26B — Configuring Return Temperature Reset Fig. 18 — Standard Chilled Fluid Temperature Control — No ResetFig. 19 — Outdoor-AirTemperature Reset Fig. 20 — Space Temperature ResetFig. 21A — 4- to 20-mADemand Limiting Fig. 21B — Cooling Set Point 4 to 20 mATROUBLESHOOTING Table 27 — Configuring Demand LimitTable 28 — Troubleshooting Recommended that system be filled with an approand fluid tubing Fig. 22 — Component Arrangement — 30RA010-030 FU — Fuse GND — GroundFig. 23 — Component Arrangement — 30RA032-040 FU — Fuse GND — GroundFig. 24 — Component Arrangement — 30RA042-055 FU — Fuse GND — GroundNOTES LEGEND Table 29 — Alarm and Alert Codes Table 29 - Alarm and Alert Codes cont Table 29 — Alarm and Alert Codes cont ALARMTable 29 — Alarm and Alert Codes cont ALARMTable 29 — Alarm and Alert Codes cont ALARMSERVICE Compressor Replacement Refer to FigTable 30 - Unit Torque Specification Electronic ComponentsFig. 28 — Compressor Wiring Fig. 27 — Typical Compressor Mounting — All SizesFig. 29 — Compressor Location — 30RA010-030 Fig. 30 — Compressor Location — 30RA032-055Condenser Section and Coils Table 31 - Oil ChargeFig. 31 — 30RA Access Panels Check Refrigerant Feed ComponentsFig. 32 — Condenser-FanMounting Fig. 33 — Condenser-FanPosition Standard FanTable 32 — Factory Settings, High-Pressure Switch FixedCompressor and Unit Protective Devices Check Unit SafetiesCOOLER FREEZE-UPPROTECTION TEMP TEMP For Thermistor T10 For Thermistor T10 Main Base Board, J8 Connector Fig. 35 — Fluid-SideTemperature Sensors T1 and T2Fig. 36 — Thermistor Connections to PROGRAMMING Mode Table 37 - Fault Codes •P50: FAULT HISTORY — Last 8 faults•P51: SOFTWARE version PARAMETERS Table 39 — Replacement Modules MAINTENANCE Minimum Loop VolumePRE-START-UP System CheckOperating Limitations OPERATION SEQUENCE Table 41 — Temperature Limits forStandard 30RA Units APPENDIX A SCN Tables A_UNIT General Unit ParametersCIRCADIO Circuit A Discrete Inputs/Outputs CIRCA_AN Circuit A Analog ParametersCIRCBDIO Circuit B Discrete Inputs/Outputs CIRCB_AN Circuit B Analog ParametersOPTIONS Unit Parameters ALARMDEF Alarm Definition Table DISPLAY Marquee Display SETUPDUALCHIL Dual Chiller Configuration Settings BRODEFS Broadcast POC Definition TableOPTIONS1 Options 1 Configuration OPTIONS2 Options 2 ConfigurationSCHEDOVR Timed Override Setup RESETCON Temperature Reset and Demand LimitSETPOINT ALARMS: Maintenance Display UNITMAINTENANCE CURRMODS: Maintenance Display DUALCHIL: Maintenance DisplayLEARNFNS Maintenance Display LOADFACT: Maintenance DisplayPM-COIL:Maintenance Display PM-PUMP:Maintenance DisplayPM-STRN Maintenance Display RUNTEST: Maintenance Display STRTHOUR Maintenance Display TESTMODE: Maintenance DisplayVERSIONS: Maintenance Display WSMDEFME: Maintenance Display FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMP APPENDIX BAND MANUAL STARTERS AND MANUAL STARTERS cont FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMPAPPENDIX C DataPort, DataLink, BAClink Object DefinitionOPTIONS SETPOINTSTART-UPCHECKLIST FOR 30RA LIQUID CHILLER Remove and use for Job File I.Project InformationII. Preliminary Equipment Check Design InformationIII. Unit Start-Up Start and Operate Machine. Complete the FollowingCL-3 Record Software Versions MODE — RUN STATUS COMMENTSCL-4 UNIT Configuration Settings OPTIONS1 Options ConfigurationIII.Unit Start-Upcont OPTIONS2 Options Configuration RSET Reset Configuration SettingsIII.Unit Start-Upcont CL-6SLCT Setpoint and Ramp Load Configuration III.Unit Start-UpcontSETPOINT CL-7Service Test Mode and Sub-ModeDirectory III.Unit Start-Upcont