Sterling 30RA010-055 manual Disp

Page 40
Manual background

Table 22 — Dual Chiller Configuration (Slave Chiller Example)

SUB-MODE

ITEM

KEYPAD ENTRY

DISPLAY

ITEM EXPANSION

COMMENTS

DISP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OPT1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OPT2

 

 

 

 

 

CTRL

CONTROL METHOD

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CTRL

 

 

 

 

0

SWITCH

DEFAULT 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CTRL

 

 

 

 

 

ESCAPE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CTRL

 

 

 

 

SCNA

 

 

 

 

 

 

 

 

 

 

 

 

SCNA

 

 

1

SCN ADDRESS

SCROLLING STOPS

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

VALUE FLASHES

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

SELECT 2

 

 

 

 

 

 

 

(SEE NOTE 1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SCNA

 

 

2

SCN ADDRESS

CHANGE ACCEPTED

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SCNA

 

 

 

 

 

ESCAPE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SCNB

 

 

 

 

 

 

 

 

 

 

 

 

SCNB

 

 

 

 

0

SCN BUS NUMBER

DEFAULT 0

 

 

ENTER

 

 

 

 

 

(SEE NOTE 2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SCNB

 

 

 

 

 

ESCAPE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OPT2

 

 

 

 

 

ESCAPE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RSET

 

PROCEED TO

 

 

 

 

 

 

 

SUBMODE RSET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RSET

 

 

 

CRST

COOLING RESET TYPE

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LLEN

LEAD/LAG CHILLER ENABLE

15 ITEMS

 

 

 

 

 

 

 

 

 

 

LLEN

 

 

DSBL

 

SCROLLING STOPS

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DSBL

 

VALUE FLASHES

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ENBL

 

SELECT ENBL

 

 

 

 

 

 

 

 

 

 

LLEN

 

 

ENBL

LEAD/LAG CHILLER ENABLE

CHANGE ACCEPTED

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LLEN

 

 

 

 

 

ESCAPE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MSSL

MASTER /SLAVE SELECT

 

 

 

 

 

 

 

 

 

 

 

MSSL

 

 

MAST

 

SCROLLING STOPS

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAST

 

VALUE FLASHES

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SLVE

 

SELECT SLVE

 

 

 

 

 

 

 

 

 

 

MSSL

 

 

SLVE

MASTER /SLAVE SELECT

CHANGE ACCEPTED

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MSSL

 

 

 

 

 

ESCAPE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RSET

 

SLAVE COMPLETE

 

 

 

ESCAPE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

1.Slave Control Method (CTRL) must be configured for 0.

2.Slave SCN Address (SCNA) must be different than Master.

3.Slave SCN Bus Number (SCNB) must be the same as Master

4.Slave does not require SLVA, LLBL, LLBD, or LLDY to be configured.

40

Image 40
Contents SAFETY CONSIDERATIONS CONTENTS GENERALMAJOR SYSTEM COMPONENTS Control Module CommunicationSterlco Comfort Network SCN Interface — Table 1 — Unit SizesTable 3 — Status Switches Table 5 - SCN Communication Bus WiringTable 2 — Thermistor Designations Table 4 - Output RelaysLEGEND FOR FIG. Page Page Fig. 3 — Wiring Schematic 30RA010-018 30RA010-018AQUA SNAPFig. 3 - Wiring Schematic 30RA010-018cont AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICSEE NOTE SEE NOTE Fig. 4 - Wiring Schematic 30RA022-030 30RA022-030AQUA SNAPFig. 4 - Wiring Schematic 30RA022-030cont AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICFig. 5 — Wiring Schematic 30RA032-040 30RA032-040AQUA SNAPFig. 5 — Wiring Schematic 30RA032-040cont AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICFig. 6 — Wiring Schematic 30RA042-055 30RA042-055AQUA SNAPFig. 6 — Wiring Schematic 30RA042-055cont AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICFig. 7 — Main Base Board ESCAPEENTERREMOTE CONTACT SW1 OFF ENABLE OFF SW2 ON MODEFig. 9 — Typical Space Temperature Sensor Wiring Fig. 11 - Energy Management Module CEPL130351100/100 Fig. 12 — Deadband Multiplier R-22Maneurop Compressor Fig. 13 — Operating Envelope forFig. 14 — 30RA Condenser Fan Sequence Cooling Set Point Select Service Test See Table 11 — Both main power and control circuit power must be onTable 8 — Control Methods and Cooling Set Points Fig. 16 — Scrolling Marquee DisplayOptional Factory-InstalledHydronic Package — •Cooler Pump Control CPC Configuration, OPT1 ON Fig. 17 — Dual Chiller Thermistor Location Table 9 — Marquee Display Menu StructureTable 10 — Run Status Mode and Sub-ModeDirectory SUB-MODE Table 12 - Temperature Mode and Sub-ModeDirectory Table 14 — Set Point and Sub-ModeDirectory Table 13 — Pressure Mode and Sub-ModeDirectoryTable 15 — Inputs Mode and Sub-ModeDirectory Table 16 — Outputs Mode and Sub-ModeDirectory SUB-MODEKEYPAD DISPLAYSUB-MODE KEYPADITEM DISPLAYSUB-MODE KEYPADITEM DISPLAYTable 18 — Time Clock Mode and Sub-ModeDirectory PER.3 SUB-MODE Table 20 — Alarms Mode and Sub-ModeDirectory Table 19 — Operating Mode and Sub-ModeDirectorySUB-MODE ITEMKEYPAD ENTRY DISPLAYRSET DISP Table 23 — Operating Modes Table 24 — Example of Reading and Clearing Alarms Table 25A — 4-20mA ResetTable 26B — Configuring Return Temperature Reset Fig. 18 — Standard Chilled Fluid Temperature Control — No ResetFig. 19 — Outdoor-AirTemperature Reset Fig. 20 — Space Temperature ResetFig. 21A — 4- to 20-mADemand Limiting Fig. 21B — Cooling Set Point 4 to 20 mATROUBLESHOOTING Table 27 — Configuring Demand LimitRecommended that system be filled with an appro Table 28 — Troubleshootingand fluid tubing Fig. 22 — Component Arrangement — 30RA010-030 FU — Fuse GND — GroundFig. 23 — Component Arrangement — 30RA032-040 FU — Fuse GND — GroundFig. 24 — Component Arrangement — 30RA042-055 FU — Fuse GND — GroundNOTES LEGEND Table 29 — Alarm and Alert Codes Table 29 - Alarm and Alert Codes cont Table 29 — Alarm and Alert Codes cont ALARMTable 29 — Alarm and Alert Codes cont ALARMTable 29 — Alarm and Alert Codes cont ALARMSERVICE Compressor Replacement Refer to FigTable 30 - Unit Torque Specification Electronic ComponentsFig. 28 — Compressor Wiring Fig. 27 — Typical Compressor Mounting — All SizesFig. 29 — Compressor Location — 30RA010-030 Fig. 30 — Compressor Location — 30RA032-055Condenser Section and Coils Table 31 - Oil ChargeFig. 31 — 30RA Access Panels Check Refrigerant Feed ComponentsFig. 32 — Condenser-FanMounting Fig. 33 — Condenser-FanPosition Standard FanTable 32 — Factory Settings, High-Pressure Switch FixedCompressor and Unit Protective Devices Check Unit SafetiesCOOLER FREEZE-UPPROTECTION TEMP TEMP For Thermistor T10 For Thermistor T10 Fig. 35 — Fluid-SideTemperature Sensors T1 and T2 Main Base Board, J8 ConnectorFig. 36 — Thermistor Connections to PROGRAMMING Mode •P50: FAULT HISTORY — Last 8 faults Table 37 - Fault Codes•P51: SOFTWARE version PARAMETERS Table 39 — Replacement Modules MAINTENANCE Minimum Loop VolumePRE-START-UP System CheckOperating Limitations Table 41 — Temperature Limits for OPERATION SEQUENCEStandard 30RA Units APPENDIX A SCN Tables A_UNIT General Unit ParametersCIRCADIO Circuit A Discrete Inputs/Outputs CIRCA_AN Circuit A Analog ParametersCIRCB_AN Circuit B Analog Parameters CIRCBDIO Circuit B Discrete Inputs/OutputsOPTIONS Unit Parameters ALARMDEF Alarm Definition Table DISPLAY Marquee Display SETUPDUALCHIL Dual Chiller Configuration Settings BRODEFS Broadcast POC Definition TableOPTIONS1 Options 1 Configuration OPTIONS2 Options 2 ConfigurationRESETCON Temperature Reset and Demand Limit SCHEDOVR Timed Override SetupSETPOINT UNIT ALARMS: Maintenance DisplayMAINTENANCE CURRMODS: Maintenance Display DUALCHIL: Maintenance DisplayLEARNFNS Maintenance Display LOADFACT: Maintenance DisplayPM-PUMP:Maintenance Display PM-COIL:Maintenance DisplayPM-STRN Maintenance Display RUNTEST: Maintenance Display TESTMODE: Maintenance Display STRTHOUR Maintenance DisplayVERSIONS: Maintenance Display WSMDEFME: Maintenance Display APPENDIX B FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMPAND MANUAL STARTERS AND MANUAL STARTERS cont FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMPAPPENDIX C DataPort, DataLink, BAClink Object DefinitionOPTIONS SETPOINTSTART-UPCHECKLIST FOR 30RA LIQUID CHILLER Remove and use for Job File I.Project InformationII. Preliminary Equipment Check Design InformationIII. Unit Start-Up Start and Operate Machine. Complete the FollowingCL-3 COMMENTS Record Software Versions MODE — RUN STATUSCL-4 OPTIONS1 Options Configuration UNIT Configuration SettingsIII.Unit Start-Upcont OPTIONS2 Options Configuration RSET Reset Configuration SettingsIII.Unit Start-Upcont CL-6SLCT Setpoint and Ramp Load Configuration III.Unit Start-UpcontSETPOINT CL-7Service Test Mode and Sub-ModeDirectory III.Unit Start-Upcont