Sterling 30RA010-055 Operating Mode and Sub-ModeDirectory, Alarms Mode and Sub-ModeDirectory

Page 37
Table 19 — Operating Mode and Sub-Mode Directory

Table 19 — Operating Mode and Sub-Mode Directory

 

SUB-MODE

 

KEYPAD

 

ITEM

DISPLAY

ITEM

COMMENT

 

 

ENTRY

 

EXPANSION

 

 

 

 

 

 

 

 

MODE

 

 

 

 

 

 

 

MODES CONTROLLING UNIT

 

 

 

 

 

 

 

 

MD01

ON/OFF

FSM CONTROLLING CHILLER

 

 

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD02

ON/OFF

WSM CONTROLLING CHILLER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD03

ON/OFF

MASTER/SLAVE CONTROL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD05

ON/OFF

RAMP LOAD LIMITED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD06

ON/OFF

TIMED OVERRIDE IN EFFECT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD07

ON/OFF

LOW COOLER SUCTION TEMPA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD08

ON/OFF

LOW COOLER SUCTION TEMPB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD09

ON/OFF

SLOW CHANGE OVERRIDE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD10

ON/OFF

MINIMUM OFF TIME ACTIVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD13

ON/OFF

DUAL SETPOINT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD14

ON/OFF

TEMPERATURE RESET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD15

ON/OFF

DEMAND/SOUND LIMITED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD16

ON/OFF

COOLER FREEZE PROTECTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD17

ON/OFF

LOW TEMPERATURE COOLING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD18

ON/OFF

HIGH TEMPERATURE COOLING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD19

ON/OFF

MAKING ICE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD20

ON/OFF

STORING ICE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD21

ON/OFF

HIGH SCT CIRCUIT A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD22

ON/OFF

HIGH SCT CIRCUIT B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD23

ON/OFF

MINIMUM COMP ON TIME

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD24

ON/OFF

PUMP OFF DELAY TIME

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD25

ON/OFF

LOW SOUND MODE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD26

ON/OFF

SHORT LOOP OVERRIDE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

FSM

Flotronic™ System Manager

 

 

 

 

SCT

Saturated Condensing Temperature

 

 

 

 

WSM

Water System Manager

 

 

 

 

Table 20 — Alarms Mode and Sub-Mode Directory

SUB-MODE

KEYPAD

ITEM

ITEM

COMMENT

ENTRY

EXPANSION

 

 

 

CRNT

 

 

 

AXXX OR TXXX

CURRENTLY ACTIVE ALARMS

Alarms are shown as AXXX.

 

ENTER

 

 

 

Alerts are shown as TXXX.

 

 

 

 

 

 

 

 

 

 

 

 

 

RCRN

 

 

YES/NO

RESET ALL CURRENT ALARMS

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIST

 

 

 

AXXX OR TXXX

ALARM HISTORY

Alarms are shown as AXXX.

 

ENTER

 

 

 

Alerts are shown as TXXX.

 

 

 

 

 

 

 

 

 

 

 

 

 

37

Image 37
Contents SAFETY CONSIDERATIONS GENERAL CONTENTSControl Module Communication MAJOR SYSTEM COMPONENTSSterlco Comfort Network SCN Interface — Table 1 — Unit SizesTable 5 - SCN Communication Bus Wiring Table 3 — Status SwitchesTable 2 — Thermistor Designations Table 4 - Output RelaysLEGEND FOR FIG. Page Page 30RA010-018AQUA SNAP Fig. 3 — Wiring Schematic 30RA010-018Fig. 3 - Wiring Schematic 30RA010-018cont AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATICSEE NOTE SEE NOTE 30RA022-030AQUA SNAP Fig. 4 - Wiring Schematic 30RA022-030AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATIC Fig. 4 - Wiring Schematic 30RA022-030cont30RA032-040AQUA SNAP Fig. 5 — Wiring Schematic 30RA032-040AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATIC Fig. 5 — Wiring Schematic 30RA032-040cont30RA042-055AQUA SNAP Fig. 6 — Wiring Schematic 30RA042-055AQUA-SNAPLOW VOLTAGE CONTROL SCHEMATIC Fig. 6 — Wiring Schematic 30RA042-055contESCAPEENTER Fig. 7 — Main Base BoardREMOTE CONTACT SW1 OFF ENABLE OFF SW2 ON MODEFig. 9 — Typical Space Temperature Sensor Wiring CEPL130351 Fig. 11 - Energy Management Module100/100 Fig. 12 — Deadband Multiplier R-22Maneurop Compressor Fig. 13 — Operating Envelope forFig. 14 — 30RA Condenser Fan Sequence Cooling Set Point Select and control circuit power must be on Service Test See Table 11 — Both main powerTable 8 — Control Methods and Cooling Set Points Fig. 16 — Scrolling Marquee DisplayOptional Factory-InstalledHydronic Package — •Cooler Pump Control CPC Configuration, OPT1 ON Table 9 — Marquee Display Menu Structure Fig. 17 — Dual Chiller Thermistor LocationTable 10 — Run Status Mode and Sub-ModeDirectory SUB-MODE Table 12 - Temperature Mode and Sub-ModeDirectory Table 14 — Set Point and Sub-ModeDirectory Table 13 — Pressure Mode and Sub-ModeDirectoryTable 15 — Inputs Mode and Sub-ModeDirectory SUB-MODE Table 16 — Outputs Mode and Sub-ModeDirectoryKEYPAD DISPLAYKEYPAD SUB-MODEITEM DISPLAYKEYPAD SUB-MODEITEM DISPLAYTable 18 — Time Clock Mode and Sub-ModeDirectory PER.3 SUB-MODE Table 19 — Operating Mode and Sub-ModeDirectory Table 20 — Alarms Mode and Sub-ModeDirectoryITEM SUB-MODEKEYPAD ENTRY DISPLAYRSET DISP Table 23 — Operating Modes Table 25A — 4-20mA Reset Table 24 — Example of Reading and Clearing AlarmsTable 26B — Configuring Return Temperature Reset Temperature Control — No Reset Fig. 18 — Standard Chilled FluidFig. 19 — Outdoor-AirTemperature Reset Fig. 20 — Space Temperature ResetFig. 21B — Cooling Set Point 4 to 20 mA Fig. 21A — 4- to 20-mADemand LimitingTable 27 — Configuring Demand Limit TROUBLESHOOTINGRecommended that system be filled with an appro Table 28 — Troubleshootingand fluid tubing FU — Fuse GND — Ground Fig. 22 — Component Arrangement — 30RA010-030FU — Fuse GND — Ground Fig. 23 — Component Arrangement — 30RA032-040FU — Fuse GND — Ground Fig. 24 — Component Arrangement — 30RA042-055NOTES LEGEND Table 29 — Alarm and Alert Codes Table 29 - Alarm and Alert Codes cont ALARM Table 29 — Alarm and Alert Codes contALARM Table 29 — Alarm and Alert Codes contALARM Table 29 — Alarm and Alert Codes contCompressor Replacement Refer to Fig SERVICETable 30 - Unit Torque Specification Electronic ComponentsFig. 27 — Typical Compressor Mounting — All Sizes Fig. 28 — Compressor WiringFig. 29 — Compressor Location — 30RA010-030 Fig. 30 — Compressor Location — 30RA032-055Table 31 - Oil Charge Condenser Section and CoilsCheck Refrigerant Feed Components Fig. 31 — 30RA Access PanelsFig. 32 — Condenser-FanMounting Fig. 33 — Condenser-FanPosition Standard FanSwitch Fixed Table 32 — Factory Settings, High-PressureCompressor and Unit Protective Devices Check Unit SafetiesCOOLER FREEZE-UPPROTECTION TEMP TEMP For Thermistor T10 For Thermistor T10 Fig. 35 — Fluid-SideTemperature Sensors T1 and T2 Main Base Board, J8 ConnectorFig. 36 — Thermistor Connections to PROGRAMMING Mode •P50: FAULT HISTORY — Last 8 faults Table 37 - Fault Codes•P51: SOFTWARE version PARAMETERS Table 39 — Replacement Modules Minimum Loop Volume MAINTENANCEPRE-START-UP System CheckOperating Limitations Table 41 — Temperature Limits for OPERATION SEQUENCEStandard 30RA Units SCN Tables A_UNIT General Unit Parameters APPENDIX ACIRCADIO Circuit A Discrete Inputs/Outputs CIRCA_AN Circuit A Analog ParametersCIRCB_AN Circuit B Analog Parameters CIRCBDIO Circuit B Discrete Inputs/OutputsOPTIONS Unit Parameters DISPLAY Marquee Display SETUP ALARMDEF Alarm Definition TableDUALCHIL Dual Chiller Configuration Settings BRODEFS Broadcast POC Definition TableOPTIONS2 Options 2 Configuration OPTIONS1 Options 1 ConfigurationRESETCON Temperature Reset and Demand Limit SCHEDOVR Timed Override SetupSETPOINT UNIT ALARMS: Maintenance DisplayMAINTENANCE DUALCHIL: Maintenance Display CURRMODS: Maintenance DisplayLOADFACT: Maintenance Display LEARNFNS Maintenance DisplayPM-PUMP:Maintenance Display PM-COIL:Maintenance DisplayPM-STRN Maintenance Display RUNTEST: Maintenance Display TESTMODE: Maintenance Display STRTHOUR Maintenance DisplayVERSIONS: Maintenance Display WSMDEFME: Maintenance Display APPENDIX B FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMPAND MANUAL STARTERS FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMP AND MANUAL STARTERS contDataPort, DataLink, BAClink Object Definition APPENDIX CSETPOINT OPTIONSRemove and use for Job File I.Project Information START-UPCHECKLIST FOR 30RA LIQUID CHILLERII. Preliminary Equipment Check Design InformationStart and Operate Machine. Complete the Following III. Unit Start-UpCL-3 COMMENTS Record Software Versions MODE — RUN STATUSCL-4 OPTIONS1 Options Configuration UNIT Configuration SettingsIII.Unit Start-Upcont RSET Reset Configuration Settings OPTIONS2 Options ConfigurationIII.Unit Start-Upcont CL-6III.Unit Start-Upcont SLCT Setpoint and Ramp Load ConfigurationSETPOINT CL-7III.Unit Start-Upcont Service Test Mode and Sub-ModeDirectory