Table 29 — Alarm and Alert Codes (cont)
ALARM/ | ALARM |
|
| WHY WAS THIS | ACTION TAKEN | RESET | PROBABLE |
ALERT | OR |
| DESCRIPTION | ALARM | |||
| BY CONTROL | METHOD | CAUSE | ||||
CODE | ALERT |
|
| GENERATED? | |||
|
|
|
|
| |||
|
|
|
|
|
|
|
|
T301 | Alert |
| Cooler Pump 2 | Pump 2 Service | None | Automatic | Routine pump |
|
|
| Scheduled | Countdown (P.2.DN) |
|
| maintenance |
|
|
| Maintenance Due | expired. Complete pump 2 |
|
| required |
|
|
|
| maintenance and |
|
|
|
|
|
|
| enter 'YES' for Pump 1 |
|
|
|
|
|
|
| Maintenance Done |
|
|
|
|
|
|
| (P.2.MN) item. |
|
|
|
|
|
|
|
|
|
|
|
T302 | Alert |
| Strainer Blowdown | Strainer Service | None | Automatic | Routine strainer |
|
|
| Scheduled | Countdown (S.T.DN) |
|
| maintenance |
|
|
| Maintenance Due | expired. Complete strainer |
|
| required |
|
|
|
| blowdown and enter 'YES' for |
|
|
|
|
|
|
| Strainer Maintenance Done |
|
|
|
|
|
|
| (S.T.MN) item. |
|
|
|
|
|
|
|
|
|
|
|
T303 | Alert |
| Condenser Coil | Coil Service Countdown | None | Automatic | Routine condenser |
|
|
| Maintenance Due | (C.L.DN) expired. |
|
| coil maintenance |
|
|
|
| Complete condenser coil |
|
| required |
|
|
|
| cleaning and enter 'YES' |
|
|
|
|
|
|
| for Coil Maintenance Done |
|
|
|
|
|
|
| (C.L.MN) item. |
|
|
|
T950 | Alert |
| Loss of Communication | No communications have | WSM forces removed. | Automatic | Failed module, wiring |
|
|
| with Water System | been received by the MBB | Chiller runs under own |
| error, failed |
|
|
| Manager | within 5 minutes of last | control |
| transformer, loose |
|
|
|
| transmission |
|
| connection plug, |
|
|
|
|
|
|
| wrong address |
T951 | Alert |
| Loss of Communication | No communications have | FSM forces removed. | Automatic | Failed module, wiring |
|
|
| with Flotronic™ System | been received by the MBB | Chiller runs under own |
| error, failed |
|
|
| Manager | within 5 minutes of last | control |
| transformer, loose |
|
|
|
| transmission |
|
| connection plug, |
|
|
|
|
|
|
| wrong address |
T952 | Alert |
| Loss of Communication | No communications have | HSM forces removed. | Automatic | Failed module, wiring |
|
|
| with Hydronic System | been received by the MBB | Chiller runs under own |
| error, failed |
|
|
| Manager | within 5 minutes of last | control |
| transformer, loose |
|
|
|
| transmission |
|
| connection plug, |
|
|
|
|
|
|
| wrong address |
| LEGEND |
|
|
|
|
| |
SCN — Sterlco Comfort Network |
|
|
|
| |||
EMM — Energy Management Module |
|
|
|
| |||
EWT — Entering Fluid Temperature |
|
|
|
| |||
FSM — Flotronic™ System Manager |
|
|
|
| |||
HSM — Hydronic System Manager |
|
|
|
| |||
LCW — Leaving Chilled Water |
|
|
|
| |||
LWT — Leaving Fluid Temperature |
|
|
|
| |||
MBB — Main Base Board |
|
|
|
|
| ||
OAT — |
|
|
|
| |||
SCT — Saturated Condensing Temperature |
|
|
|
| |||
TXV — Thermostatic Expansion Valve |
|
|
|
| |||
WSM — Water System Manager |
|
|
|
|