TABLE 9.7: FITTING EQUIVALENT LENGTHS

FITTING

PIPE SIZE

EQUIVALENT LENGTH (ft)

90 ELBOW

1

2.75

 

 

 

TURN IN TEE

1

5.50

 

 

 

RUN OF TEE

1

1.75

 

 

 

SWING CHECK

1

7.00

GATE VALVE

1

0.60

Method 2: Direct Connection to Heating System (Generally NOT Recommended)

The FCM can be connected directly to the heating system as is done with conventional boilers (Figure 9.8). If this is done, the flow rate through the boiler will equal the flow rate through the system. The flow rate through the system must therefore always remain within the limits shown in Table 9.1. For this reason, the pressure drop through the entire system must be known, added to the boiler pressure drop, and a circulator selected which will provide the required flow at the total calculated pressure drop.

This method is generally not recommended because it is often very difficult to accurately calculate the pressure drop through the system. In replacement installations, it may be impossible to get an accurate measurement of the amount of piping and number of fittings in the system. In addition, if the system is zoned, the system flow may drop well below the minimum required when only one zone is calling for heat.

The one advantage to this method is its installation simplicity. It may make sense to use this method when the boiler is to be installed with a new single zone system having a low-pressure drop. Pressure drop curves for the FCM Series boilers are shown in Figure 9.9. Calculation of the system pressure drop, and selection of the circulator, must be performed by someone having familiarity with pressure drop calculations, such as an HVAC engineer.

Figure 9.8: Piping Method #2 - Direct Connection of Boiler to Heating System

39

Image 39
Contents Freedom Table of Contents Maximum Vent Lengths SpecificationsProduct Description II SpecificationsIV Locating the Boiler III Before InstallingClearances To Combustible Or Non-combustible Material Clearances from Vent Piping to Combustible Construction Mounting The Boiler Wall MountingFloor Mounting Wall Mounting Hole Locations Boiler Mounting/Hardware VI Air for Ventilation Page Vent System Design VII VentingPage Or PVC Summary of Horizontal Venting OptionsHorizontal Concentric Venting Vent Option Size Vent U.S. Boiler Concentric Vent Components Vent Option6c Positioning Vent Terminal Under Overhangs VENT/ AIR Intake Fitting Equivalent Length Roof Summary of Vertical Venting OptionsNever Common Vent a FCM Boiler with Other Appliances Removing an Existing Boiler From a Common ChimneyAssembly of U.S. Boiler 60/100mm Concentric Venting 11 Dimension L 12 Cutting Outer Pipe 14 Preparing Terminal Section for Installation in the Wall 16 Installation of Stainless Steel Vent Collar Assembly of Stainless Steel Venting17a Star-34 Connection to Vent Collar 18 Z-Vent III Connection to Vent Collar 19 SAF-T Vent EZ Seal Connection to Vent Collar 20 FasNSeal Connection to Vent Collar Condensate Trap and Drain Line 21 Condensate Piping Arrangement Gas Connection To Boiler Viii Gas PipingFlow Requirements Through Boiler General System Piping PrecautionsIX System Piping System DesignMethod 1 Primary/Secondary Piping Piping Method #1 Heat Only Piping Method #1 Heat + Indirect Water Heater 4b Piping Method #1 Indirect Water Heater Loop Piping Shaded Pipe and Circulator Sizing for Indirect Water Heater Loop Pipe and Circulator Sizing for Boiler LoopFitting Equivalent Lengths Boiler Head Loss Standard Piping Installation RequirementsPiping for Special Situations 11 Chiller Piping Wiring Wiring Connections Diagram Ladder Diagram Page Never Attempt to Fill a HOT Empty Boiler XI Start-up and CheckoutWater Quality and Boiler Water Additives FCM Series Lighting and Operating Instructions SWT Typical CO2/O2 Combustion Readings Range Gas Valve DetailPage XII Operation Normal Display In Standby ModePage Basic Menu Tree First Digit Boiler Status Boiler StatusOutdoor Reset Curve XIII. Service and Maintenance Page No Error Code Displayed XIV. TroubleshootingCode Condition Possible Causes Soft Lockout Codes DisplayedHard Lockout Codes Displayed XV Parts Page KEY Description Parts ListPage Parts List Page Page Page DISP4D 150 151 152 153 154 155 156 157 158 159 160 161 162 Page Page Page Page Page Limited Warranty