TABLE 9.5: PIPE AND CIRCULATOR SIZING FOR BOILER LOOP
| (a) | (b) | (c) | (d) | (e) | |
BOILER | PIPE |
| TEMP |
| BOILER LOOP | |
FLOW | CIRCULATOR | MAX EQUIVALENT | ||||
MODEL | SIZE | RISE | ||||
| MODEL | LENGTH | ||||
|
|
|
| |||
| (in NPT) | (GPM) | (F) |
| (ft) | |
|
|
|
|
|
| |
FCM070 | 1 | 6.0 | 22 | Taco 007 | 55 | |
|
|
|
|
|
| |
FCM070 | 1 | 6.0 | 22 | Taco 008 | 145 | |
|
|
|
|
|
| |
FCM090 | 1 | 8.0 | 21 | Taco 0014 | 90 | |
|
|
|
|
|
| |
FCM090 | 1 | 8.0 | 21 | Taco 0013 (Note #1) | 230 | |
|
|
|
|
|
| |
FCM120 | 1 | 8.0 | 29 | Taco 0014 | 111 | |
|
|
|
|
|
| |
FCM120 | 1 | 9.0 | 25 | Taco 0014 | 61 | |
|
|
|
|
|
| |
FCM120 | 1 | 12.0 | 19 | Taco 0013 (Note #1) | 28 | |
|
|
|
|
|
|
NOTE: 1) Use isolation relay between Taco 0013 and FCM - see Figure 10.3
TABLE 9.6: PIPE AND CIRCULATOR SIZING FOR INDIRECT WATER HEATER LOOP
| (a) | (b) | (c) | (d) |
| (e) | (f) | |
BOILER | PIPE |
| MAX. I.W.H. | ALLIANCE™ |
| I.W.H. LOOP MAX | ||
FLOW | PRESSURE | CIRCULATOR | EQUIVALENT | |||||
MODEL | SIZE | INDIRECT WATER | ||||||
| DROP | MODEL | LENGTH | |||||
|
|
| HEATERS | |||||
| (in NPT) | (GPM) | (ft HEAD) |
| (ft) | |||
|
|
|
| |||||
|
|
|
| AL27SL | (*) |
|
| |
FCM070 | 1 | 6.0 | 1.7 | AL35SL | (*) | Taco 008 | 102 | |
AL70SL | (*) | |||||||
|
|
|
|
|
| |||
|
|
|
| AL119SL (*) |
|
| ||
|
|
|
| AL27SL, AL35SL |
|
| ||
FCM090 | 1 | 8.0 | 3.0 | AL50SL | (*) | Taco 0014 | 50 | |
AL70SL | (*) | |||||||
|
|
|
|
|
| |||
|
|
|
| AL119SL (*) |
|
| ||
|
|
|
|
|
|
| ||
|
|
|
| AL27SL, AL35SL |
|
| ||
FCM090 | 1 | 8.0 | 3.0 | AL50SL | (*) | Taco 0013 (Note #3) | 190 | |
AL70SL | (*) | |||||||
|
|
|
|
|
| |||
|
|
|
| AL119SL (*) |
|
| ||
|
|
|
| AL27SL |
|
| ||
|
|
|
| AL35SL |
|
| ||
FCM120 | 1 | 8.0 | 3.0 | AL50SL | Taco 0014 | 71 | ||
|
|
|
| AL70SL |
|
| ||
|
|
|
| AL119SL |
|
| ||
|
|
|
| AL27SL, AL35SL |
|
| ||
FCM120 | 1 | 8.0 | 5.0 | AL50SL, AL70SL | Taco 0014 | 45 | ||
AL119SL | ||||||||
|
|
|
|
|
| |||
|
|
|
| (Note #2) |
|
| ||
|
|
|
| AL27SL, AL35SL |
|
| ||
FCM120 | 1 | 8.0 | 5.0 | AL50SL , AL70SL | Taco 0013 (Note #3) | 185 | ||
AL119SL | ||||||||
|
|
|
|
|
| |||
|
|
|
| (Note #2) |
|
| ||
|
|
|
|
|
|
|
|
NOTES:
1)Indirect water heaters with an asterisk (*) will not achieve their catalog rating due to inadequate boiler water flow and/or inadequate boiler output.
2)When used with an indirect heater having a pressure drop less than 3.0 ft of head, the Taco 0013 can be installed with up to 211 equivalent ft of 1” pipe.
3)Use isolation relay between Taco 0013 and FCM - see Figure 10.3
38