B.Trouble shooting problems where a soft lockout code is displayed. When a soft lockout occurs, the boiler will shut down and the display will alternate between the number “9” and the letter “b” followed by a two digit service code. The boiler will automatically restart once the condition that caused the lockout is corrected.
TABLE 14.3: SOFT LOCKOUT CODES DISPLAYED
CODE | CONDITION | POSSIBLE CAUSES | |
|
| • Blockage in intake or vent system. | |
|
| • Vent and/or intake system not constructed in accordance with Part VI. | |
b 08 | Pressure switch circuit open | • Blocked or leaking pressure switch tubing | |
• Heat exchanger or burner blockage | |||
|
| ||
|
| • Terminals exposed to high winds | |
|
| • Blockage in condensate trap above vent. | |
|
|
| |
|
| • Heating load at time of error was far below the minimum firing rate of the | |
| MCBA supply sensor detected temperatures in excess | boiler | |
b 18 | • Defective primary pump or no flow in primary loop (Piping Method 1) | ||
of 200°F | |||
| • Control system miswired so that boiler operation is permitted when no | ||
|
| ||
|
| zones are calling | |
|
|
| |
b 19 | MCBA return sensor detected temperatures in excess | • See possible causes for “b18” | |
of 200°F | • Flow through boiler reversed | ||
| |||
|
| • Sensor wiring reversed | |
|
|
| |
|
| • Flow through boiler reversed. Verify correct piping and pump orientation. | |
| MCBA is reading a return sensor temperature higher | • No boiler water flow. Verify that system is purged of air and that | |
b 24 | than the supply sensor temperature. Condition must be | appropriate valves are open. | |
| present for at least 75s for this error code to appear. | • Sensor wiring reversed. | |
|
| • Supply or return sensor defective. | |
|
|
| |
|
| • See possible causes for “b18” | |
b 25 | Supply water temperature has risen too quickly | • Inadequate boiler water flow. Verify that pump is operating and that pump | |
|
| and piping are sized per Part VIII of this manual | |
|
|
| |
b 26 | Boiler safety limit, or external limit wired across | • See possible causes for “b18” | |
terminals 3&4, is open. | • Defective supply sensor. | ||
| |||
|
|
| |
b 30 | Temperature rise between supply and return is too high. | • Inadequate boiler water flow. Verify that pump is operating and that pump | |
and piping are sized per Part VIII of this manual | |||
|
| ||
|
|
| |
|
| • Blockage in pressure switch hose | |
|
| • Pressure switch wires shorted together | |
b 61 | Pressure switch circuit closed with fan off | • Defective pressure switch | |
|
| • Loose or miswired fan speed harness (if “b61” error code is observed | |
|
| while fan is running) | |
|
|
| |
b 65 | Fan is not achieving set point speed | • Loose or incorrect fan speed control connection | |
• Defective fan | |||
|
| ||
|
|
|
61