Burnham 101008-01R1-2/07 manual XII Operation, Normal Display In Standby Mode

Page 53

XII Operation

1)The FCM boiler uses a microprocessor based control, known as a “MCBA”, to manage all boiler functions including flame supervision and modulation. Two set point or “target” boiler supply temperatures are stored in the MCBA’s memory; one for space heating and one for domestic water production. If an outdoor temperature sensor is connected to the boiler, the space heating supply set point will automatically adjust downwards as the outdoor temperature increases. For more information on this feature see the discussion on boiler water reset below.

The MCBA modulates the boiler input by varying the fan speed. As the fan speed increases, so does the amount of gas drawn into the blower. As a result, a fairly constant air-fuel ratio is maintained across all inputs.

The MCBA determines the input needed by looking at both current and recent differences between the supply temperature and the set point temperature. As the supply temperature approaches the set point temperature, the fan will slow down and the input drop. Depending on the model boiler, the minimum input is between ¼ and 1/5 of maximum input.

The MCBA also monitors boiler return and flue temperatures. In addition, all other safety controls, including the low water cut-off and safety limit, are connected into the MCBA. The MCBA uses input from all of these controls to either shut down the boiler when an unsafe condition exists or, in some cases, to correct the problem.

2)The display panel has three primary modes of operation. These are:

Standby Mode – Displays boiler’s current status. This is the default operating mode.

Parameter Mode – Used to change control settings

Information Mode – Displays boiler operating temperatures

Under normal conditions, the boiler is in standby mode and the display looks like that shown in Figure 12.1. The three digits to the right of the decimal point are the boiler’s supply temperature. The digit to the left of the decimal point is the boiler’s status code. A list of status codes, and their meanings, is shown in Table 12.3.

Figure 12.2 is a map of the menu structure for the control panel. Push the mode key to move from one mode to the next. As you change modes, the mode you are entering is shown on the display:

a)PArA” for Parameter Mode

b)Info” for Information Mode

c)Stby” for Standby Mode. Upon entering standby mode, “Stby” will briefly appear on the display and then the

display will show the boiler’s status along with the supply temperature (Figure 12.1).

The control will return to standby mode from any other mode if no key is pressed for 20 minutes.

Figure 12.1: Normal Display In Standby Mode

53

Image 53
Contents Freedom Table of Contents Product Description SpecificationsII Specifications Maximum Vent LengthsIV Locating the Boiler III Before InstallingClearances To Combustible Or Non-combustible Material Clearances from Vent Piping to Combustible Construction Floor Mounting Mounting The BoilerWall Mounting Wall Mounting Hole Locations Boiler Mounting/Hardware VI Air for Ventilation Page Vent System Design VII VentingPage Or PVC Summary of Horizontal Venting OptionsHorizontal Concentric Venting Vent Option Size Vent U.S. Boiler Concentric Vent Components Vent Option6c Positioning Vent Terminal Under Overhangs VENT/ AIR Intake Fitting Equivalent Length Roof Summary of Vertical Venting OptionsNever Common Vent a FCM Boiler with Other Appliances Removing an Existing Boiler From a Common ChimneyAssembly of U.S. Boiler 60/100mm Concentric Venting 11 Dimension L 12 Cutting Outer Pipe 14 Preparing Terminal Section for Installation in the Wall 16 Installation of Stainless Steel Vent Collar Assembly of Stainless Steel Venting17a Star-34 Connection to Vent Collar 18 Z-Vent III Connection to Vent Collar 19 SAF-T Vent EZ Seal Connection to Vent Collar 20 FasNSeal Connection to Vent Collar Condensate Trap and Drain Line 21 Condensate Piping Arrangement Gas Connection To Boiler Viii Gas PipingIX System Piping General System Piping PrecautionsSystem Design Flow Requirements Through BoilerMethod 1 Primary/Secondary Piping Piping Method #1 Heat Only Piping Method #1 Heat + Indirect Water Heater 4b Piping Method #1 Indirect Water Heater Loop Piping Shaded Pipe and Circulator Sizing for Indirect Water Heater Loop Pipe and Circulator Sizing for Boiler LoopFitting Equivalent Lengths Boiler Head Loss Standard Piping Installation RequirementsPiping for Special Situations 11 Chiller Piping Wiring Wiring Connections Diagram Ladder Diagram Page Never Attempt to Fill a HOT Empty Boiler XI Start-up and CheckoutWater Quality and Boiler Water Additives FCM Series Lighting and Operating Instructions SWT Typical CO2/O2 Combustion Readings Range Gas Valve DetailPage XII Operation Normal Display In Standby ModePage Basic Menu Tree First Digit Boiler Status Boiler StatusOutdoor Reset Curve XIII. Service and Maintenance Page No Error Code Displayed XIV. TroubleshootingCode Condition Possible Causes Soft Lockout Codes DisplayedHard Lockout Codes Displayed XV Parts Page KEY Description Parts ListPage Parts List Page Page Page DISP4D 150 151 152 153 154 155 156 157 158 159 160 161 162 Page Page Page Page Page Limited Warranty