C.Trouble shooting problems where a hard lockout code is displayed. When a hard lockout occurs, the boiler
will shut down and the display will flash the letter “E” followed by a two digit service code. Once the condition that caused the lockout is corrected, the boiler will need to be manually reset using the RESET button on the display.
TABLE 14.4: HARD LOCKOUT CODES DISPLAYED
CODE | CONDITION | POSSIBLE CAUSES | |
E 00 | A flame signal was present when there should | • Defective gas valve - make sure inlet pressure is below maximum on rating plate | |
be no flame. | before replacing valve. | ||
| |||
|
| • No gas pressure | |
|
| • Gas pressure under minimum value shown on rating plate | |
|
| • Gas line not completely purged of air | |
|
| • Defective Electrode | |
E 02 | Flame failure after 5 tries to restart | • Loose burner ground connection | |
|
| • Defective Ignition Cable | |
|
| • Defective gas valve (check for 24 VDC at harness during trial for ignition before | |
|
| replacing valve) | |
|
| • | |
|
|
| |
|
| • Loose or defective gas valve harness. Check electrical connections. | |
E 03 | Gas valve error | • Defective gas valve (check for 24 VDC at harness during trial for ignition before | |
|
| replacing valve) | |
E 04 | Power failure occurred after lockout | • Some other error on this list occurred and power to the boiler was then | |
interrupted. Reset control and see if hard lockout reoccurs. | |||
|
| ||
E 05 |
|
| |
E 06 | Internal control failure | • Reset the control. If problem reoccurs, replace the MCBA. | |
E 07 | |||
|
| ||
E 11 |
|
| |
|
|
| |
|
| • If yellow light on LWCO is on, system is low on water | |
E 12 | Low water | • If neither yellow nor green light is on, check LWCO harness and check for | |
|
| 24VAC across AT140 transformer | |
E 13 |
|
| |
E 14 |
|
| |
E 15 | Internal control failure | • Reset the control. If problem reoccurs, replace the MCBA. | |
E 16 |
|
| |
E 17 |
|
| |
E 18 | MCBA supply sensor detected temperatures in | • See possible causes for “b18” error. Also, check safety limit for proper operation. | |
excess of 200°F for an extended period of time | |||
|
| ||
E 19 | MCBA return sensor detected temperatures in | • See possible causes for “b19” error. | |
excess of 200°F for an extended period of time | |||
|
| ||
| Blower is not running when it should or fan speed | • Loose connection in 120 VAC fan wiring | |
E 28 | • Loose or miswired fan speed harness | ||
| signal not being detected by MCBA | • Defective fan | |
|
| ||
E 29 | Blower fan speed has not returned to zero rpm | • Miswired fan speed harness | |
• Defective fan | |||
|
| ||
E 31 | Shorted supply temperature sensor | • Shorted or miswired supply sensor wiring | |
• Defective supply sensor | |||
|
| ||
E 32 | Shorted return temperature sensor | • Shorted or miswired return sensor wiring | |
• Defective return sensor | |||
|
| ||
E 35 | Flue gas temperature sensor short circuit | • Shorted or miswired flue temp sensor wiring | |
• Defective flue temp sensor | |||
|
| ||
E 36 | Supply water temperature sensor circuit open | • Loose or miswired supply sensor wiring | |
• Defective supply sensor | |||
|
| ||
E 37 | Return water temperature sensor circuit open | • Loose or miswired return sensor wiring | |
• Defective return sensor | |||
|
| ||
E 40 | Flue gas temperature sensor circuit open | • Loose or miswired flue temp sensor wiring | |
• Defective flue temp sensor | |||
|
| ||
E 44 | Internal control failure | • Reset the control. If problem reoccurs, replace the MCBA. | |
|
|
| |
|
| • Heat exchanger needs to be cleaned | |
E 52 | Flue gas temperature over 230°F | • Boiler | |
|
| • | |
E 60 | Internal control failure | • Reset the control. If problem reoccurs, replace the MCBA. | |
|
|
|