30 OVEN SYSTEMS
NOTE: The terminals with the orange dot or the orange wire always go to Terminal 3 on US models.
To verify correct wiring (International), measure the voltage between the taps on FT1 and FT2. The voltage must be 220 VAC (Latin America), 200 VAC (Japan), or 230 VAC (International).
High-Voltage Transformers
Wiring the High-Voltage Transformers
DANGER: Never attempt to wire or measure the secondary voltage values of the
The proper reinstallation of a
As shown in the schematic, transformers are installed mirror opposite and wired 180º
With the microwave system energized, the volt meter will read the incoming voltage (different readings for different electrical installations). If the meter reads 0 VAC, the
The wiring issue must be corrected prior to return- ing the oven to service, as the voltages must be:
-NORTH AMERICA: 208 VAC between 1 & 2 and
240 between 1 & 3.
-LATIN AMERICA: 220 VAC
-JAPAN: 200 VAC
-INTERNATIONAL: 230 VAC
NOTE: The terminals with the orange dot/orange wire always go to terminal 3 on USA models.
Testing a Filament or HV Transformer
DANGER: Never attempt to measure the secondary voltage values of the transformers
when they are enabled. Lethal voltage will be present.
1.Disconnect the AC power source and discharge the
2.Disconnect all the wires in question going to the transformer.
3.Use an ohmmeter to check the impedance of the primary and secondary winding. Refer to the adjacent resistance table to determine if the transformer is OK. If the resistance is different then the table indicates, replace the transformer.
High-Voltage Diodes
The