44 TROUBLESHOOTING
Troubleshooting:
F8: HEAT LOW
|
|
|
|
|
|
| Are both blower motors moving air? |
| |
YES |
|
| ||
| Check in TEST MODE - see page 15. |
| ||
|
|
| ||
|
|
|
|
|
NO
Is the
YES
NO
Is the heater defective? Check in TEST MODE - see page 15.
YESNO
See page 39
to troubleshoot F1: BLOWER (Blower Running Status Bad)
Reset (page 34) and determine why it tripped – excess grease buildup, etc.
Replace defective heater. (page
Verify the solid state relay is not shorted across output.
Is the solid state relay defective or damaged?
YESNO
|
|
|
|
|
|
|
Replace the solid state relay |
| Is the wiring from the solid | ||||
(page |
| state relay to the control | ||||
|
|
| board OK? (See page 51 for | |||
|
| |||||
|
|
| schematic.) | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
YES
Replace the control board (page
NO
Correct wiring.