American Power Conversion PD80KF6FK1-M, PD80KG6FK1-M manual Overview, InfraStruXure PDU Components

Models: PD80KG6FK1-M PD80KF6FK1-M PD80KL6FK1-M

1 92
Download 92 pages 35.21 Kb
Page 13
Image 13

Overview

InfraStruXure PDU Components

The APC 80kW InfraStruXure PDU provides distribution and management of electrical power. The InfraStruXure PDU has the capacity of 80kW, accepts 208, 480, or 600V, 3-phase input, and distributes 208V, 3-phase power to equipment racks and Rack Distribution Panels (RDPs). The RDPs sit in the top 10U of specially-designed NetShelter VX enclosures and distribute power to equipment racks. The InfraStruXure PDU is housed in a specially-designed 23-inch NetShelter VX wide enclosure. Each 80kW InfraStruXure PDU has thirty pole positions available for feeding equipment racks and four, three-pole positions available for feeding RDPs. Each RDP has thirty-nine pole positions available for feeding equipment racks and one, three-pole position that back-feeds the RDP.

Rack Distribution Panel (RDP)

InfraStruXure PDU

39 pole positions available

Four circuit breakers sub-feeding the RDPs

One, 3-pole breaker back-feeding the RDP

30 pole positions available

NetShelter VX Enclosure

Power cables feeding equipment racks

42-position circuit breaker panel

Sub-feed power cable feeding the RDP

80kW InfraStruXure PDU—Operation and Configuration

5

Page 13
Image 13
American Power Conversion PD80KF6FK1-M, PD80KG6FK1-M, PD80KL6FK1-M manual Overview, InfraStruXure PDU Components