Overview

InfraStruXure PDU Components

The APC 80kW InfraStruXure PDU provides distribution and management of electrical power. The InfraStruXure PDU has the capacity of 80kW, accepts 208, 480, or 600V, 3-phase input, and distributes 208V, 3-phase power to equipment racks and Rack Distribution Panels (RDPs). The RDPs sit in the top 10U of specially-designed NetShelter VX enclosures and distribute power to equipment racks. The InfraStruXure PDU is housed in a specially-designed 23-inch NetShelter VX wide enclosure. Each 80kW InfraStruXure PDU has thirty pole positions available for feeding equipment racks and four, three-pole positions available for feeding RDPs. Each RDP has thirty-nine pole positions available for feeding equipment racks and one, three-pole position that back-feeds the RDP.

Rack Distribution Panel (RDP)

InfraStruXure PDU

39 pole positions available

Four circuit breakers sub-feeding the RDPs

One, 3-pole breaker back-feeding the RDP

30 pole positions available

NetShelter VX Enclosure

Power cables feeding equipment racks

42-position circuit breaker panel

Sub-feed power cable feeding the RDP

80kW InfraStruXure PDU—Operation and Configuration

5

Page 13
Image 13
American Power Conversion PD80KF6FK1-M, PD80KG6FK1-M, PD80KL6FK1-M manual Overview, InfraStruXure PDU Components