PDU Display Interface

Alarm Setup

Use this option of the Alarms screen to access the following options:

Loading Limits

Configure the following in amps and as a percentage of full load:

 

Out High: The upper limit for output current

 

Out Low: The lower limit for output current

 

Out Neut: The upper limit for current on the neutral wire for

 

 

the output phases

Voltage Limits

Configure the following as a percentage under or over the rated

 

voltage:

 

Input: The allowed range for input voltage

 

Output: The allowed range for output voltage

 

Bypass: The allowed range for bypass input voltage (only on

 

 

PDUs with dual-fed input)

Other Limits

Configure these limits:

Frequency: The frequency variation, in hertz, that is acceptable for the output current.

Global Alarm Config Set all the loading limits or all the voltage limits simultaneously as a percentage of full load:

Load Limits: Set the same percentage for the upper limit for output current, the lower limit for output current, and the upper limit for current on the neutral wire for the output phases. (Use the Loading Limits option to set these thresholds individually).

Volt Limits: Set the same percentage for the high and low thresholds for input and output voltage. (Use the Voltage Limits option to set these thresholds individually).

Select Apply Now and then YES to implement your changes.

Alarm Beeper

Use this option of the Alarms screen to turn the alarm beeper ON or OFF.