Specifications

Physical

PD80F6FK1-M PD80G6FK1-M PD80L6FK1-M

 

 

 

 

 

Shipping with a Transformer

2200 lb (1000 kg)

 

 

 

Shipping without a Transformer

1384 lb (628 kg)

 

 

 

Service

 

 

 

 

Access

Front and rear

 

 

 

Clearance

208 V: Greater than or equal to 36 in (914mm)

 

480 V: Greater than or equal to 42 in (1067mm)

Transformer (if installed)

 

 

 

 

Type

Isolation

Isolation/Step-Down

Configuration

Delta to WYE

 

 

 

Maximum Power Rating

112.5 kVA

 

 

 

Maximum Current Rating

312A

135A

108A

Construction

Cu. windings, open core

 

 

Temperature Rating

180°C (Class H)

 

 

 

Maximum Temperature Rise

302°F (150°C)

 

 

 

Main AC Power Feeds

Top or bottom feed, lugs sized for 600 mcm

 

 

 

 

 

Environmental

 

 

 

 

 

 

 

Operating Environment

Indoor use only; protect from water and conductive

 

contaminates

 

 

 

Temperature

 

 

 

 

Operating

32 to 104° F (0 to 40°C)

 

 

Storage

5 to 113° F (–15 to 45°C)

 

 

Humidity

 

 

 

 

Operating

0–95%, non-condensing

 

 

Storage

0–95%, non-condensing

 

 

Acoustic Noise Emission

Less than or equal to 50 dBA

 

 

 

 

 

 

 

Compliance

 

 

 

 

 

 

 

 

 

Approvals

UL, cUL

 

 

 

 

 

 

 

 

80kW InfraStruXure PDU—Operation and Configuration

69

Page 77
Image 77
American Power Conversion PD80KL6FK1-M, PD80KG6FK1-M, PD80KF6FK1-M manual PD80F6FK1-M PD80G6FK1-M PD80L6FK1-M