Specifications
80kW InfraStruXure PDU
Performance
Transformer Efficiency (if installed) | 97% |
|
|
|
System Full Load Output Rating | 80kW |
|
|
|
System Monitoring |
|
|
|
|
Of Current | Distribution branch monitoring (optional), subfeed | |||
Of Voltage | AC main input, bypass input, output at distribution panels, | |||
| output of fuses |
|
|
|
Of Bypass | Bypass breaker positions, bypass lamp cue/feedback | |||
Switches/ Breakers Status | Bypass breaker positions, input switch positions, cross tie | |||
| output switch position |
|
| |
Transformer Temperature Sensor | 180°C (triggers a warning through the PDU monitoring unit) | |||
Branch Current Monitoring |
|
|
|
|
Parameters | Maximum current (RMS): 95A |
|
| |
| Maximum current (peak): 135A |
|
| |
| Maximum crest factor: 3 |
|
| |
| Minimum current: 0.5A |
|
| |
| Measurement accuracy: ± 0.5A or 5% of reading | |||
| (whichever is greater) |
|
| |
| Maximum wire size: 0.35in (8.89mm) |
|
| |
|
|
|
|
|
Electrical |
|
|
| |
|
|
|
|
|
Input |
|
|
|
|
Nominal Voltage | 208V Delta | 480V Delta | 600 V Delta | |
Nominal Bypass Voltage | 208V WYE |
|
|
|
Nominal Current | 251A | 109A | 87A | |
Max. Current | 350A | 150A | 125A | |
Output |
|
|
|
|
Nominal Voltage | 208:120V WYE |
|
|
|
Frequency |
|
|
| |
Max. Continuous Nominal Current | 277.5A |
|
|
|
Nominal Current | 222A |
|
|
|
Wiring |
|
|
|
|
PDU to UPS | 4W + G (AC mains input) 4W (Bypass input) | |||
UPS to PDU | 4W | 4W | 4W | |
PDU to Distribution Panels | 4W + G | 4W + G | 4W + G | |
|
|
|
|
|
80kW InfraStruXure | 67 |