Specifications

80kW InfraStruXure PDU

Performance

Transformer Efficiency (if installed)

97%

 

 

 

System Full Load Output Rating

80kW

 

 

 

System Monitoring

 

 

 

 

Of Current

Distribution branch monitoring (optional), subfeed

Of Voltage

AC main input, bypass input, output at distribution panels,

 

output of fuses

 

 

 

Of Bypass

Bypass breaker positions, bypass lamp cue/feedback

Switches/ Breakers Status

Bypass breaker positions, input switch positions, cross tie

 

output switch position

 

 

Transformer Temperature Sensor

180°C (triggers a warning through the PDU monitoring unit)

Branch Current Monitoring

 

 

 

 

Parameters

Maximum current (RMS): 95A

 

 

 

Maximum current (peak): 135A

 

 

 

Maximum crest factor: 3

 

 

 

Minimum current: 0.5A

 

 

 

Measurement accuracy: ± 0.5A or 5% of reading

 

(whichever is greater)

 

 

 

Maximum wire size: 0.35in (8.89mm)

 

 

 

 

 

 

 

Electrical

PD80F6FK1-M

PD80G6FK1-M

PD80L6FK1-M

 

 

 

 

 

Input

 

 

 

 

Nominal Voltage

208V Delta

480V Delta

600 V Delta

Nominal Bypass Voltage

208V WYE

 

 

 

Nominal Current

251A

109A

87A

Max. Current

350A

150A

125A

Output

 

 

 

 

Nominal Voltage

208:120V WYE

 

 

 

Frequency

57–63 Hz

 

 

 

Max. Continuous Nominal Current

277.5A

 

 

 

Nominal Current

222A

 

 

 

Wiring

 

 

 

 

PDU to UPS

4W + G (AC mains input) 4W (Bypass input)

UPS to PDU

4W

4W

4W

PDU to Distribution Panels

4W + G

4W + G

4W + G

 

 

 

 

 

80kW InfraStruXure PDU—Operation and Configuration

67

Page 75
Image 75
American Power Conversion PD80KG6FK1-M, PD80KF6FK1-M, PD80KL6FK1-M manual Specifications, 80kW InfraStruXure PDU