System Operation
80kW InfraStruXure PDU—Operation and Configuration 33
The UPS is now in maintenance bypass operation.
5. Open (turn OFF) the XR Battery Enclosure DC
Disconnect circuit breaker.
6. Open (turn OFF) the Q1 circuit breaker on the
PDU.
7. If applicable, open (turn OFF) the PDU Q10
Bypass Input (B) switch.