Overview

Front view (door open)

Wraparound

maintenance bypass

 

 

panel—The

maintenance bypass

 

 

panel has three

 

 

circuit breakers that

 

 

allow the UPS to be

 

 

 

 

electrically isolated

 

 

from the main power

 

 

source, while

 

 

maintaining the

 

 

power panels. The

 

 

input circuit breaker

 

 

is labeled Q1, the

 

 

output circuit breaker

 

 

 

 

is labeled Q2, and the

 

 

maintenance bypass

 

 

circuit breaker is

 

 

labeled Q3. The label

 

 

on the maintenance

 

 

bypass panel of the

 

 

PDU illustrates the

 

 

power flow, and the

 

 

H2 and H3 LEDs

 

 

indicate when it is

 

 

safe to operate the Q2

 

 

and Q3 circuit

 

 

breakers.

 

 

Optional bottom-feed cable access—These knockouts are for bottom-feed power cables and RDP cables. If you ordered a PDU to accommodate under-floor wiring, your power cables for equipment racks and RDPs will exit the PDU from these cable access holes.

UPS input and output cables—The cables that connect the PDU to the UPS are shipped coiled on the floor of the PDU. The input cables consist of 5 wires: 3 phases, 1 neutral, and one ground. The output cable consist of 4 wires: 3 phases and 1 neutral. The bypass cables consist of 4-wires: 3 phases and one neutral. Each wire is labeled and corresponds to a lug on the Symmetra PX UPS bus bars. During installation, the Field Service Engineer will connect the PDU to the UPS.

User connection plate—The user connection plate is connected to the PDU monitoring unit, and provides easy access to the input contacts, relay outputs, network, and EPO connections. Make connections from inside the enclosure, and route wires through the knockout provided on the plate. See “User connection plate” on page 11 for a more detailed description.

8

80kW InfraStruXure PDU—Operation and Configuration

Page 16
Image 16
American Power Conversion PD80KF6FK1-M, PD80KG6FK1-M manual Front view door open,  Wraparound Maintenance bypass Panel