Alarm Map: 01 of 04 [Vo, By, C4]
Map: Input Voltage Apply Now

PDU Display Interface

Alarm Relay Map Configure the relay outputs, using the Alarm Relay Map.

Each Alarm Map corresponds to an output relay. For

example, Alarm Map 01of04 corresponds to the first of four relay outputs. The second line, in brackets [ ], lists the items that you have selected to map to the selected relay. The third line allows you to select the alarms to which you want to map the relay:

Any Load (L)—Maps to over- or under-current alarms for circuit breaker panels and branch circuits.

Overload (O)—Maps to over-current alarms for circuit breaker panels, branch circuits, and SYSGND.

Input Voltage (Vi)—Maps to any input voltage alarm.

Output Voltage (Vo)—Maps to any output voltage alarm.

PDU in Bypass (By)—Mapping this option will cause the output relay to actuate when the Q3 breaker is closed.

Any Breaker (Br)—Mapping this option will cause the output relay to actuate when the input, bypass input (Q10), or cross-tie output breaker is not in its normal state.

Contacts 1–4(C1, C2, C3, C4)—Maps to the input contact alarms.

Before exiting the screen, to save your changes, select the Apply

Now option on the bottom line of the screen.

.

80kW InfraStruXure PDU—Operation and Configuration

19