Customizing and Updating the PDU

4.If the test was successful, place the Arm/Test rocker switch back to the Arm position. The PDU display interface will clear the EPO test mode alarm. If the test was not successful, see the troubleshooting chart:

Problem

Action

 

 

Neither state LED was red

• Check the wiring to your EPO switch

when the EPO switch was

• Check to make sure the EPO DIP

engaged

switch configuration is correct for

 

your switch (NO or NC).

 

 

Only one of the state LEDs

• Check to make sure the EPO DIP

was red when the EPO switch

switch configuration is correct for

was engaged

your switch (NO or NC) and test

 

again.

 

• If the switch is configured correctly

 

and both LEDs are not red after testing

 

again, contact customer support at a

 

number on the back cover of this

 

manual.

 

 

5.Repeat this test for each EPO switch installed.

6.Ensure that the Arm/Test rocker switch is in the Arm position on the monitoring unit.

Safety warnings

Hazardous voltage from the branch circuit must be isolated from the 24VAC, 24VDC, and contact closure. 24VAC and 24VDC are considered Class 2 circuits as defined in Article 725 of the National Electrical Code (NFPA 70) and Section 16 of the Canadian Electrical Code (C22.1).

A Class 2 circuit is a source having limited voltage and energy capacity as follows:

a.If an Inherently Limited Power Source, voltage and energy are limited to less than 30VAC, less than 30VDC, and 8A.

b.If not an Inherently Limited Power Source, voltage and energy are limited to less than 30VAC, less than 60VDC, 250VA, and the current is limited to 1000/Vmax. The fuse is limited to 5A if less than 20VAC or 20VDC, or 100/V maximum if less than 30VAC or 60VDC.

80kW InfraStruXure PDU—Operation and Configuration

61

Page 69
Image 69
American Power Conversion PD80KG6FK1-M, PD80KF6FK1-M, PD80KL6FK1-M manual Safety warnings