58 80kW InfraStruXure PDU—Operation and Configuration
How to Add Circuit Breakers and Power Cables

Add a circuit breaker on the PDU

1. Snap and bolt the new circuit breaker
into a position on the panel.
2. Remove the corresponding plastic
blanking plate on the front panel of the
PDU.

Add a power cable to the PDU or RDP

Before adding a power cable, add a circuit breaker.
1. Install a strain-relief connector in
any available knockout on the roof
of the PDU.
2. Slide enough of the power cable
through the strain-relief connector
to reach the new circuit breaker.
3. Tighten the strain-relief connector.
Note
If you are installing 20A or 30A power cables in a knockout designed for 50 A
power cables, you must use reducing washers (provided) to adjust the size of the
knockout.