System Operation
How to Transfer the UPS into Maintenance Bypass Operation
Select Help from the
Note procedure below.
When servicing the UPS, transfer the UPS into maintenance bypass operation. When the UPS is operating in maintenance bypass, input power flows directly to the PDU and out to the load equipment.
1. Command the UPS into static bypass operation through the UPS display interface:
a.Press the ESC key at the
b.Select Control on the
c.Select UPS Into Bypass on the Control menu and, press the ENTER key.
|
|
|
|
|
| Control | Logging |
|
| Status | Display |
|
| Setup | Diags |
|
| Accessories | Help |
|
|
|
|
Control Menu
UPS Into Bypass
Do Self Test
Simulate Power Fail
Graceful Reboot
Graceful Turn Off
Start Runtime Cal
Turn Load On
d.Confirm the selection on the next screen: select Yes, UPS into Bypass and press the ENTER key.
Confirmation Screen
Confirm
Yes, UPS into Bypass No, Abort
The UPS Bypass LED illuminates and the following screens appear:
UPS has been
commanded to go into Bypass...
UPS load is in Bypass
Press any key...
80kW InfraStruXure | 31 |