Specifications
68 80kW InfraStruXure PDU—Operation and Configuration
Power Cables to Enclosures/ Rack PDUs 4W + G 4W + G 4W + G
Power Cable Connections L21-20 L21-20 L21-20
Power Cable Lengths Various Various Various
Power Cable Wiring (Top Exit) Accommodates 10 + cables
Power Cable Wiring (Bottom Exit) Accommodates 10 + cables
Subfeed
Subfeed Wiring (3 -phase) 4W + G 4W + G 4W + G
Subfeed Connector System 100A, pin and sleeve
Subfeed Voltage 208:120V 208:120V 208:120V
Subfeed Current 80A 80A 80A
Panels
Panel Style 3-phase 3-phase 3-phase
Number of Panels (per PDU) 1 maximum 1 maximum 1 maximum
Positions per Panel 42 42 42
3-phase Breakers per Panel 10 (with 4 subfeeds)
3-phase Subfeeds per Panel 4 maximum 4 maximum 4 maximum
1-phase Breakers per Panel 30 (with 4 subfeeds)
Panel Rating 240V/400A per phase
Panel Board Accessibility Through rear of unit
Relay Outputs
Nominal Switching Capacity 1A at 30VDC
Maximum Switching Power 30W
Maximum Switching Voltage 60VDC
Maximum Switching Current 2 ADC
Maximum Carrying Current 2ADC
Surge Ratings 2 kV per Bellcore TA-NWT-001089
1.5kV per FCC part 68
Physical PD80F6FK1-M PD80G6FK1-M PD80L6FK1-M
Dimensions (H × W × D)
PDU 81 × 29 × 36 in (2057 × 737 × 914 mm)
AC Power Trough 7.5 × 4.0 × 29.0 in (190 ×100 × 740 mm)
Ramp (L × W) 45 × 6 in (1143 × 150 mm)
Weigh t
PDU with a Transformer 2100 lb (953 kg)
PDU without a Transformer 1284 lb (583 kg)
Electrical PD80F6FK1-M PD80G6FK1-M PD80L6FK1-M