Specifications |
|
|
|
| |
| Electrical |
|
| ||
|
|
|
|
|
|
| Power Cables to Enclosures/ Rack PDUs | 4W + G | 4W + G | 4W + G | |
| Power Cable Connections | ||||
| Power Cable Lengths | Various | Various | Various | |
| Power Cable Wiring (Top Exit) | Accommodates 10 + cables |
|
| |
| Power Cable Wiring (Bottom Exit) | Accommodates 10 + cables |
|
| |
| Subfeed |
|
|
|
|
| Subfeed Wiring (3 | 4W + G | 4W + G | 4W + G | |
| Subfeed Connector System | 100A, pin and sleeve |
|
| |
| Subfeed Voltage | 208:120V | 208:120V | 208:120V | |
| Subfeed Current | 80A | 80A | 80A | |
| Panels |
|
|
|
|
| Panel Style | ||||
| Number of Panels (per PDU) | 1 maximum | 1 maximum | 1 maximum | |
| Positions per Panel | 42 | 42 | 42 |
|
| 10 (with 4 subfeeds) |
|
| ||
| 4 maximum | 4 maximum | 4 maximum | ||
| 30 (with 4 subfeeds) |
|
| ||
| Panel Rating | 240V/400A per phase |
|
| |
| Panel Board Accessibility | Through rear of unit |
|
| |
|
|
|
|
|
|
| Relay Outputs |
|
|
|
|
|
|
|
|
|
|
| Nominal Switching Capacity | 1A at 30VDC |
|
|
|
| Maximum Switching Power | 30W |
|
|
|
| Maximum Switching Voltage | 60VDC |
|
|
|
| Maximum Switching Current | 2ADC |
|
|
|
| Maximum Carrying Current | 2ADC |
|
|
|
| Surge Ratings | 2kV per Bellcore |
|
| |
|
| 1.5kV per FCC part 68 |
|
| |
|
|
|
|
|
|
| Physical | ||||
|
|
|
|
|
|
| Dimensions (H × W × D) |
|
|
|
|
| PDU | 81 × 29 × 36 in (2057 × 737 × 914 mm) |
|
| |
| AC Power Trough | 7.5 × 4.0 × 29.0 in (190 ×100 × 740 mm) | |||
| Ramp (L × W) | 45 × 6 in (1143 × 150 mm) |
|
| |
| Weight |
|
|
|
|
| PDU with a Transformer | 2100 lb (953 kg) |
|
|
|
| PDU without a Transformer | 1284 lb (583 kg) |
|
|
|
|
|
|
|
|
|
68 | 80kW InfraStruXure |