PDU Display Interface
Panel Configuration
Configure the branch metering settings for each breaker on the distribution panel. The panel position numbers on the screen correspond to the numbers on the distribution panel. (Odd numbers are on the left; even numbers are on the right.) Once you
have selected the correct range, configure the settings for each breaker in the range:
Pos: The panel positions in the selected range.
Breaker: Two configurable items:
•The breaker rating, in amps.
•The breaker tie
To configure the values on this screen:
1.From the first column, use the arrow keys to scroll up or down to the pole position you want to configure.
2.Press the ENTER key to move to the item you want to configure in the third column (the breaker rating or the breaker tie indicator).
3.Scroll again to select the value you want for the breaker rating or the breaker tie indicator. To associate one panel position with the next position in the list, choose the + character as the tie indicator immediately following the breaker rating. To indicate that the position is not tied to (associated with) the next panel position in the list, choose the ] character as the tie indicator immediately following the breaker rating. When you change the + or ] character that follows the breaker rating in one row, the + or [ character before the breaker rating in the next row also changes to indicate the changed association between the panel positions.
For example, this screen shows three,
breakers occupying positions 08, 10, and 12 on the top right |
| Pos | Breaker | ||
| 08 | [ | 20A | + | |
| |||||
distribution panel. | 10 | + | 20A | + | |
12 | + 20A ] |
| Circuit breakers with ratings above 60A are considered | |
| subfeed circuit breaker, select a value above 60A. The interface will display “SUB” | |
Note | after the rating you have selected. Only the bottom 12 positions on the distribution | |
panel can be configured as | ||
|
26 | 80kW InfraStruXure |