Panel Configuration Select Range: [01..41] [02..42]

PDU Display Interface

Panel Configuration

Configure the branch metering settings for each breaker on the distribution panel. The panel position numbers on the screen correspond to the numbers on the distribution panel. (Odd numbers are on the left; even numbers are on the right.) Once you

have selected the correct range, configure the settings for each breaker in the range:

Pos: The panel positions in the selected range.

Breaker: Two configurable items:

The breaker rating, in amps.

The breaker tie indicator—define the number of panel positions tied (i.e., associated). You can associate positions with breakers, which enables you to view status about each breaker and receive alarm notification when any of a breaker’s poles are above or below the configured branch circuit limit. You can also tie together panel positions that are logically associated. For example, you can tie together panel positions for three separate breakers that are connected to the same PDU power cord and that feed power to the same equipment enclosure.

To configure the values on this screen:

1.From the first column, use the arrow keys to scroll up or down to the pole position you want to configure.

2.Press the ENTER key to move to the item you want to configure in the third column (the breaker rating or the breaker tie indicator).

3.Scroll again to select the value you want for the breaker rating or the breaker tie indicator. To associate one panel position with the next position in the list, choose the + character as the tie indicator immediately following the breaker rating. To indicate that the position is not tied to (associated with) the next panel position in the list, choose the ] character as the tie indicator immediately following the breaker rating. When you change the + or ] character that follows the breaker rating in one row, the + or [ character before the breaker rating in the next row also changes to indicate the changed association between the panel positions.

For example, this screen shows three, single-pole, 20A, tied

breakers occupying positions 08, 10, and 12 on the top right

 

Pos

Breaker

 

08

[

20A

+

 

distribution panel.

10

+

20A

+

12

+ 20A ]

 

Circuit breakers with ratings above 60A are considered sub-feeds. To configure a

 

subfeed circuit breaker, select a value above 60A. The interface will display “SUB”

Note

after the rating you have selected. Only the bottom 12 positions on the distribution

panel can be configured as sub-feeds.

 

26

80kW InfraStruXure PDU—Operation and Configuration

Page 34
Image 34
American Power Conversion PD80KF6FK1-M, PD80KG6FK1-M, PD80KL6FK1-M manual Panel Configuration, Distribution panel