PDU Display Interface

Electrical Config

This option of the Config screen displays information about the electrical service that provides input to the InfraStruXure PDU. All of the values displayed on this screen are set at the factory. Use this information when viewing and setting alarms.

Input Config

Configure the following items:

 

Main Input: The voltage from the building’s electrical

 

 

service coming into the PDU Main Input switch.

 

 

• 3W: 3-phase Delta, measured line-to-line

 

 

• 4W: 3-phase wye, measured line-to-neutral

 

Transformer: Indicates whether the InfraStruXure PDU has

 

 

a transformer.

 

Bypass Input: Indicates whether the PDU has a Bypass Input

 

 

switch (B).

 

Fuse: Indicates whether the PDU has fuses protecting the

 

 

SCRs in the UPS. The fuses are present only on dual-fed

 

 

PDUs and single-fed PDUs without a transformer.

Output Config

Configure the following items:

 

Panel Voltage: The nominal voltage of the distribution panel

 

 

supplying power to the load equipment. (This is measured

 

 

line-to-neutral.)

 

Panel Breaker: The rating, in amps, of the breaker feeding

 

 

the distribution panel.

 

Load Test Port: Indicates whether the InfraStruXure PDU

 

 

has a Load Test Port.

 

Frequency: The frequency, in hertz, of the output.

 

Cross Tie Out: Indicates whether the PDU has a Cross Tie

 

 

Output breaker.

Other Config Items Configure the following items:

Load Test Port: Indicates whether the PDU has a load test port installed.

Max Power: Maximum power of your InfraStruXure PDU (40kW or 80kW).

Subfeed Port: Indicates the port at which the subfeed resides (port 3).

80kW InfraStruXure PDU—Operation and Configuration

29

Page 37
Image 37